Professional Documents
Culture Documents
Figure 1.11: Experiment circuit for measurements in the no-load, matching and
short-circuit modes
1.4.1 No-load
Disconnect the resistive load to study operating response under no-load.
For both line lengths, set the voltage to the nominal value (380 V) at the beginning of the line.
The outer conductors are designated L1 , L2 and L3 , the neutral conductor N. Measure the
variables indicated in the table (the powers always comprise three-phase values, i.e. total
power levels):
Compare the measurement results with the calculated values (all calculations are carried out
for single-phases on the basis of the associated phasor diagram).
To determine the voltage rise at the line's open end, it is best to use the voltage measured
there to calculate the voltage at the line's start. The calculations shown next apply according
to Figure 1.5.
UL = X * I20 = 2.53 V
U1 = U2 – UL = 220.5 V
UL = X * I20 = 10.48 V
U1 = U2 – UL = 220.5 V
The charging power can be ascertained with sufficient precision assuming that the voltages at
the start and end of the line are identical.
1.4.2 Matching
To study the response during matching, the resistive load is decreased from its maximum
value until attainment of the power levels specified in the table below. In the case of both line
lengths, the nominal voltage (380 V) is to be set at the start of the line and maintained at this
value through readjustment wherever necessary. The variables indicated next are to be
measured.
What can be said about the sign of the reactive power fed into the line?
Situated between these ranges is the operating state known matching. The supplied reactive
power is now at its minimum value (theoretically zero). This operating point is to be found by
slowly changing the load resistance, starting from its maximum value.
Measurement values during matching (line length of 150 km and supply voltage of 380 V):
Measurement values during matching (line length of 300 km and feed voltage of 380 V):
For the purpose of monitoring, this resistance can naturally also be measured by means of an
ohmmeter with the load disconnected.
Here too, a comparison is performed with the theoretically expected value for a lossless
line for both line lengths (the characteristic impedance is independent of the line length).
The deviation between the measured and theoretical values is explained by the fact that the
nominal voltage was not present across the load during the experiment, due to the line's
active resistance.
Finally, the measured values are used to determine the efficiency during matching for
both line lengths:
To study the response in the event of a three-pole (symmetric) short circuit, the resistive load
is disconnected, and the three outer conductors connected to each other as well as the return
conductor. These connections must be established before the power switch is turned on.
In this experiment, the line can be considered as a model of a 110-kV line possessing the
same line constants for R, X and CB as a 380-kV line. Even with these values, the line model
remains realistic.
Because of the high current in the short-circuited state, the experiment should be carried out
swiftly at a reduced supply voltage. The current should remain on only until the desired
measurement values have been obtained. Increase the line-to-line voltage at the start of the
line to 110 kV and measure the variables indicated below.
The current at the start of the line is lower than at the shorted
line end. This is explained by the influence of the working
capacitance.
The measurement results show that the line mainly consumes
inductive reactive power in the event of a short circuit.
As shown for a lossless line in Figure 6.7, the short-circuit Several answers
current is purely capacitive and reduced by the inductive may be correct.
transverse current at the end of the line. However, the
difference between the two amperages is minimal.
As shown for a lossless line in Figure 6.7, the short-circuit
current is purely inductive and reduced by the capacitive
transverse current at the end of the line. However, the
difference between the two amperages is minimal.
Note:
In this experiment, the currents were measured only in the steady state. The initial values
occurring on a short circuit of relatively short lines in meshed networks with multiple feeds can
be much higher. Unbalanced and earth faults, of equal importance to the design of protective
equipment, are treated in a separate experiment.
Figure 1.12: Experiment circuit for measurements with purely capacitive loads
Connect the capacitor in star configuration, and set the voltage at the start of the line to a
constant value of 340 V; perform any readjustment necessary to avoid excess voltages at the
end of the line. Enter the values of the specified parameters in the table below. The power
levels again comprise total values.
C= 2 µF 4 µF 6 µF 8 µF 10 µF 12 µF
Voltage L1 - L2 (line end)
Current L1 (at line end)
Reactive power (at line end)
Strom L1 (am Leitungsanfang)in A
Active power (at line start)
Reactive power (at line start)
How does the voltage at the line's end depend on the connected capacitance?
Evidently, the voltage at the end of the line rises
disproportionately with increasing inductive load. This can be
explained by the Ferranti effect, as already described in the
case of no-load.
Evidently, the voltage at the end of the line rises
disproportionately with increasing capacitive load. This can be
explained by the Ferranti effect, as already described in the
case of no-load.
Evidently, the voltage at the end of the line rises
disproportionately with increasing resistive load. This can be
explained by the Ferranti effect, as already described in the
case of no-load.
For measurements with purely inductive loads, assemble the circuit as shown next.
Figure 1.13: Experiment circuit for measurements with purely inductive loads
Connect the inductor in star configuration, and set the voltage at the start of the line to 380 V;
perform any necessary readjustments. Enter the values of the specified parameters in the
table below. The power levels again comprise total values.
How does the voltage at the end of the line depend on the connected inductance?
Besides purely resistive loads (lighting, process heat), operations in a real power network also
involve numerous loads of a resistive-inductive nature (transformers, electric motors). The
overall power factor cos f in this case usually ranges between 0.8 and 0.9. These load cases
are accordingly given due consideration below. All experiments here are conducted with a line
length of 150 km.
For tests involving mixed resistive-inductive loads, assemble the circuit as shown next.
Figure 1.14: Experiment circuit for measurements with mixed resistive-inductive loads
Connect the inductor and load resistor in parallel and star-configuration in each case; set the
voltage at the start of the line to 380 V and perform any necessary readjustments. Note the
values of the exemplified variables in the table. The power levels again comprise total values.
Measured values for L = 3.2 H and a load adjusted (starting with large values of R) so as
to consume an active power of 300 W:
Voltage L1 – L2 (line end) V
Current L1 (at line end) A
Reactive power (load) var
Power factor cos φ (load)
Current L1 (at line start) A
Active power (at line start) W
Reactive power (at line start) var
Measured values for L = 2.0 H and a load adjusted (starting with large values of R) so as
to consume an active power of 400 W:
Voltage L1 – L2 (line end) V
Current L1 (at line end) A
Reactive power (load) var
Power factor cosφ (load)
Current L1 (at line start) A
Active power (at line start) W
Reactive power (at line start) var
Measured values for L = 1.2 H and a load adjusted (starting with large values of R) so as
to consume an active power of 500 W:
Voltage L1 – L2 (line end) V
Current L1 (at line end) A
Reactive power (load) var
Power factor cos f (load)
Current L1 (at line start) A
Active power (at line start) W
Reactive power (at line start) var
As an example, the results of the last measurement are to be checked through calculation.
Perform single-phase calculations on the basis of the phasor diagram in Figure 1.8. The
load's active power at the measured voltage results the following active current:
The following applies to the load's power factor: tan j2 = I2 reactive / I2 active = 0.62 and cos φ2
= 0.85.
The transverse current due to half the working capacitance at the end of the line is:
The longitudinal current along the line is I12 = I2 + I20 = (0.844 – j 0.462) A.
Consequently, U1 = U2 + (R + j X) * I12.
If R = 3.6 W und X = 36.15 W (line values) are used, then U1 = (217.2 + j 28.847) V and U1Δ
= (376.19 + j 49.964).
The transverse current due to half the working capacitance at the start of the line is:
I10 = U1 * (j ωCB / 2) = (- 0.009 + j 0.068) A
The minor differences compared to the measured values can be explained by component
tolerances.
A load state involving a poor power factor will now to be simulated in order to demonstrate the
possibility of reactive power compensation.
Measured values for L = 1.2 H and a load adjusted (starting with large values of R) so as
to consume an active power of 300 W:
Voltage L1 – L2 (line end) V
Current L1 (at line end) A
Reactive power (load) var
Power factor cos f (load)
Current L1 (at line start) A
Active power (at line start) W
Reactive power (at line start) var
A computational verification of these capacitance values using the equations stated in section
"Theoretical Fundamentals" is somewhat complicated, because of the different voltages
present at the end of the line during the measurement series, and the need to account for the
influence of the line's working capacitance.
Measured values for L = 2.0 H and the load R adjusted so as to consume an active power
of 500 W:
Voltage L1 – L2 (line end) V
Current L1 (at line end) A
Reactive power (load) var
Power factor cos φ (load)
Current L1 (at line start) A
Active power (at line start) W
Reactive power (at line start) var
The experiment demonstrates that the load at the end of a long line causes an
impermissibly high voltage drop. A series capacitor can be used to reduce this drop.
Three individual capacitances with the value C = 1 / (ω * XL) are required for full
compensation. At a length of 300 km, the line model has a reactance XL = 72.3 O, so that
C = 44 µF. In the experiment, this value can be realized by a parallel connection of
capacitors rated respectively at 30, 8, 4 and 2 µF. The three capacitances formed in this
manner are to be connected between the end of the line and the multimeter in each case.
This permits continued measurement of the sought variables across the load. The
resistive load is to be readjusted until a consumption of 500 W is achieved again, and the
same variables as those in the uncompensated state are to be measured:
Voltage L1 – L2 (line end) V
Current L1 (at line end) A
Reactive power (load) var
Power factor cos φ (load)
Current L1 (at line start) A
Active power (at line start) W
Reactive power (at line start) var