You are on page 1of 1

1.

ALL DIMENSIONS ARE IN MILLIMETERS AND ELEVATIONS ARE IN METERS


UNLESS OTHERWISE NOTED.

2. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE


LATEST EDITION OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA 70
AND 72) AND SAUDI ARAMCO ENGINEERING STANDARDS (SAES-B-014).

3. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH A


LISTED AND UL 864, 9TH EDITION COMPLIANT ADDRESSABLE FIRE ALARM
CONTROL PANEL AND COMPONENTS.

4. FIRE ALARM SYSTEM WIRING SHALL BE INSTALLED IN ACCORDANCE WITH


NFPA 72 CLASS "A" FOR BOTH SIGNALING LINE CIRCUITS AND NOTIFICATION
APPLIANCE CIRCUITS.

5. ALL FIRE DETECTION SYSTEM TESTING SHALL BE WITNESSED BY


REPRESENTIVE OF THE AREA LEAD FIRE PREVENTION ENGINEER/LOSS
PREVENTION DEPARTMENT AND THE AREA FIRE MARSHAL/FIRE PROTECTION
DEPARTMENT.

6. IN ACCORDANCE WITH SAUDI ARAMCO ENGINEERING STANDARD SAES-B-014


SECTI9ONS 7.2 AND 7.9(b), ALL FIRE ALARM DRAWINGS SHALL REQUIRE
PROFESSIONAL DESIGN ENGINEER WRITTEN CERTIFICATION INDICATION THAT
THE SYSTEM IS DESIGNED AND PERFORM IN COMPLIANCE WITH NFPA 72.

7. IN ACCORDANCE WITH SAUDI ARAMCO ENGINEERING STANDARD SAES-B-014


SECTION 7.3, THE BEACON SHALL BE POSITIONED SHALL REQUIRE
PROFESSIONAL DESIGN ENGINEER WRITTEN CERTIFICATION INDICATING THAT
THE SYSTEM IS DESIGNED IT IS NOT BLOCKED BY ADJACENT BUILDINGS OR
STRUCTURES THE EXTENT POSSIBLE, THE BEACON COLOR SHALL FOLLOW
PLANT PRECEDENT: OTHERWISE, THE FIRE ALARM BEACON COLOR SHALL BE
RED.

8. WATER FOLLOW MONITORING SHALL BE INTERFACED WITH THE FIRE ALARM


CONTROL PANEL.

9. AS PER NFPA 70 (2023) ARTICLES 760.32 & 805.90(A), EACH FIRE DETECTION
(SLC) CIRCUIT THAT EXTENDS BEYOND A BUILDING AND RUNS OUTDOORS
SHALL BE PROTECTED WITH A SURGE PROTECTIVE DEVICE (SPD).

FA-L2-010

FA-L2-013 FA-L2-012 ADDRESSABLE PHOTO ELECTRIC SMOKE DETECTOR WITH BASE

ADDRESSABLE HEAT DETECTOR WITH BASE

STROBE09
STROBE07 ADDRESSABLE MANUAL CALL POINT

FA-L2-014 STROBE08 FA-L2-011 FA-L2-009 ADDRESSABLE WALL MOUNTED STROBE WITH HORN

ADDRESSABLE WALL MOUNTED STROBE WITH HORN


STROBE10
FIRE ALARM INITIATION COPPER CABLE

FA-L2-015 FIRE ALARM NOTIFICATION COPPER CABLE

FA-L2-019 ADDRESSABLE FIRE ALARM CONTROL UNIT

STROBE05 STROBE06
ADDRESSABLE WALL MOUNTED STROBE

FA-L2-008
STROBE04 FA-L2-016 MONITOR MODULE

STROBE06 FA-L2-007
STROBE03
FA-L2-018 FA-L2-006

FA-L2-004
FA-L2-017 FA-L2-005

FA-L2-003
STROBE02
STROBE03

- BUILDING 2 FIRE ALARM SYSTEM


ART CONCEPT ENGINEERING CONSULTING
TEL. 0594401619 / DAMMAM - TAIBA

06-30-2023