1. All electrical works herein shall be done in accordance with the latest provisions of the EQUIPMENT
QTY. DETAILS HP VOLTAGE PHASE hz SIZE OF WIRE AND CONDUIT
NO
PHILIPPINE ELECTRICAL CODE (PEC), ordinances of the local government Minimum Size of Main Circuit Breaker:
and with the requirements of the local power company concerned in the enforcement of AB1/AB2 2 AIR BLOWER 5 400 3 60 3-5.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
electrical laws and ordinances. AB1/AB2 2 ANOXIC OUMP 1 230 1 60 3-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC IBreaker = [ 21.6 + 1.5 (6.8) + 3 (2.9)) ] 80% = 29.46Amp.
2. Service voltage to the Sewage Treatment Plant (STP) shall be 460volts, 60hz ,
AB1/AB2 2 EFLUENT PUMP 1 230 1 60 3-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
3phase, three wires and ground. Use Phelpdodge (THHN) wires.
WAS PUMP
Use: 75 AT / 75 AF, 3 PHASE 220V MCCB
AB1/AB2 1 1 230 1 60
3. Minimum size of wires to used herein shall be 3.5 mm² THHN with corresponding 3-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
ground wire of 2.0 mm² THHN. AB1/AB2 1 ASD PUMP 1 230 1 60 3-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
4. Minimum size of conduit to be used herein shall be 20 mm dia. metallic conduit for
AB1/AB2 2 DECANTER PUMP 1 230 1 60 3-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
expose, PVC for embedded.
AB1/AB2 1 SUBMERSIBLE MIXER 1 400 3 60 3-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
Minimum Size of Main Feder Conductor:
5. All materials to used herein , shall be new and of the approved type.
6. Circuit breakers, magnetic starters, relays, timer and other pilot devices shall AB1/AB2 1 EXHAUST FAN 1 230 1 2-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
60
be of industrial type. IWire = [21.6 + 1.25 (6.8) + 3 (2.9) ] 80% = 28.1 Amp.
AB1/AB2 1 INLINE FAN 1 230 1 2-3.5 mm² THHN WIRE, 1-2.0mm² THHN(G) IN 15mmØ IMC
60
7. Motor Controls Center shall be of NEMA 3 standard.
8. Electrical motors subject for vibration shall be provided with liquid tight flexible metallic
24 DIFFUSERS FINE (10 IN) - - - Use: 3 -14 mm² THHN, 1 - 5.5 mm² TW (G) IN 35mmØ PVC
tubing of at least 0.4m from the termination box of the electric motor to the branch circuit 6 DIFFUSERS COARSE (4 IN) - - -
conduit.
1 BAR SCREEN (MANUAL) - - -
9. The contractor shall submit shop drawing prior to the electrical installations five(5) days
AB1/AB2 2 CHLORINATOR (40GPD) - 230 1 60
before the commissioning of the Sewage Treatment Plant. The contractor shall submit
three(3) copies of as- built plans to the engineer or owner.
10. All electrical works and installation herein shall be done under the direct supervision of
3 - 14 mm² THHN,
duly Registered Master Electrician, Registered Electrical Engineer or Professional 1 - 5.5 mm² THHN(G)
Electrical Engineer. in 35 mmØ PVC
75 AT / 75 AF, 230V,
3PHASE, MCCB
30 AT / 30 AT / 30 AT / 30 AT / 30 AT / 30 AT / 30 AT / 30 AT / 30 AT / 30 AT /
50 AF 50 AF 50 AF 50 AF 50 AF 50 AF 50 AF 50 AF 50 AF 50 AF
10 KAIC 10 KAIC 10 KAIC 10 KAIC 10 KAIC 10 KAIC 10 KAIC 10 KAIC 10 KAIC 10 KAIC
3P 3P 3P 3P 3P 3P 2P 2P 2P 2P
FVNR FVNR
ST PB PB PB
OL1 OL2 OL3 FS OL4 FS OL5 FS OL6 OL7 OL8 OL9 OL9
AERATION ANOXIC EQT
1 2 3 4 5 6 7 8 9 9
AIR BLOWER 1 AIR BLOWER 2 TRANSFER P. 1 TRANSFER P. 2 EFFLUENT P. 1 DECANTER 1 DECANTER 2 SUBM. MIXER CHLORINATOR 1 CHLORINATOR 2
5 hp, 3Ø 5 hp, 3Ø 1 hp, 1Ø 1 HP, 1Ø 1 hp, 1Ø 1 HP, 1Ø 1 HP, 1Ø 1HP, 1Ø 1/4 HP, 1Ø 1/4 HP, 1Ø
CCT
SITE DEVELOPMENT
CCT
ANOXIC
5000
ST
AERATION EQT
SITE DEVELOPMENT
2 STP PLUMBING LAYOUT
SCALE 1:100 MTS.
SD 01
PROJECT TITLE / OWNER : OWNER : SHEET CONTENTS DESCRIPTION: PREPARED BY: SHEET NO.
REPUBLIC ACT 9266
REPUBLIC OF THE PHILIPPINES SEWAGE TREATMENT PLANT CAD DRAWN BY:
THIS DRAWING ACTING AS
MUNICIPALITY OF MAUBAN POWER LAYOUT PLAN
A. C. TUMANG CONSTRUCTION INSTRUMENT OF SERVICE IS
DESIGN AND BUILD OF TWO (2) STOREY PROVINCE OF QUEZON
SD-01
ENGINEER EXCLUSIVE PROPERTY OF
DATE STARTED:
A R C H I T E C T S
E N G I N E E R S B U I L D E R S ARCHITECT ALEX C.TUMANG
HOSPITAL BUILDING, PANDEMIC BUILDING AND SITE DEVELOPMENT RECOMMENDING APPROVAL: RECOMMENDING APPROVAL: APPROVED:
AND AS SUCH MUST NOT BE
DODGE STREET, PHASE 1, QUEENSBOROUGH NORTH, SAN JOSE, CITY OF SAN FERNANDO, PAMPANGA PRC NO: PTR NO: USED OR REPRODUCED IN
TEL. NO. (045) 435-2858 EMAIL: actumang.construction@yahoo.com PART OR IN WHOLE WITHOUT Engr. EnP. RONNIE BOY R. GAPASANGRA ENG'R. MANUEL P. AMBON HON. MARITA T. LLAMAS DATE STARTED:
DATE: ITS SPECIFIC PERMISSION ENGINEER IV MUNICIPAL ENGINEER MUNICIPAL MAYOR
TIN: PLACE :
LOCATION: NATIONAL HIGHWAY, BRGY. POLO, MAUBAN, QUEZON
1605,72
GI RAILING
4014,3
4014,3
1200
BLOWER
AIR LINE
3211,44
2000
BLOWER
8028,6
8028,6
ST
3000
AIR LINE CHEMICAL FEED PUMP
AERATION CCT
TANK 1
SAMPLING TANK
5000
ST
AERATION EQT
2106,14
GI RAILING
5265,36
1200
4212,29
10530,72
LIFT STATION
315,92
SITE DEVELOPMENT
3 SECTIONAL VIEW ELEVATION
SCALE 1:100 MTS.
SD 2
PROJECT TITLE / OWNER : OWNER : SHEET CONTENTS DESCRIPTION: PREPARED BY: SHEET NO.
REPUBLIC ACT 9266
REPUBLIC OF THE PHILIPPINES FLOOR PLAN LAYOUT & CAD DRAWN BY:
THIS DRAWING ACTING AS
MUNICIPALITY OF MAUBAN SECTIONAL VIEWS
A. C. TUMANG CONSTRUCTION INSTRUMENT OF SERVICE IS
DESIGN AND BUILD OF TWO (2) STOREY PROVINCE OF QUEZON
SD-02
ENGINEER EXCLUSIVE PROPERTY OF
DATE STARTED:
A R C H I T E C T S
E N G I N E E R S B U I L D E R S ARCHITECT ALEX C.TUMANG
HOSPITAL BUILDING, PANDEMIC BUILDING AND SITE DEVELOPMENT RECOMMENDING APPROVAL: RECOMMENDING APPROVAL: APPROVED:
AND AS SUCH MUST NOT BE
DODGE STREET, PHASE 1, QUEENSBOROUGH NORTH, SAN JOSE, CITY OF SAN FERNANDO, PAMPANGA PRC NO: PTR NO: USED OR REPRODUCED IN
TEL. NO. (045) 435-2858 EMAIL: actumang.construction@yahoo.com PART OR IN WHOLE WITHOUT Engr. EnP. RONNIE BOY R. GAPASANGRA ENG'R. MANUEL P. AMBON HON. MARITA T. LLAMAS DATE STARTED:
DATE: ITS SPECIFIC PERMISSION ENGINEER IV MUNICIPAL ENGINEER MUNICIPAL MAYOR
TIN: PLACE :
LOCATION: NATIONAL HIGHWAY, BRGY. POLO, MAUBAN, QUEZON