You are on page 1of 3

2-8.0 sq.

mm THHN IN 32mm PVC


REFFERENCE: STALLS PANEL BOARD FEEDER:
Equipment Grounding Conductor
LOCATION: GROUND FLOOR MAINS: 40AT, 2P, 230V,
FED FROM: STALL PB - MCCB
SCHEDULE OF LOADS
CKT. NO. LOAD DISCRIPTION NO. OF OUTLET
L.O C.O
1 LIGHTING OUTLET 7
2 CONVINIENCE OUTLET 6
3 ACU - 1HP
4 SPARE

TOTAL

APPLICATION OF DEMAND FACTORS:


With 80% D.F.
IT = 15.7193 * D.F. + ( 25% * HRM )
IT = ( 15.7193 * 0.8 ) + ( 0.25 * 8 )
IT = 14.5913043478261

SERVICE INTRANCE CUONDUCTORS:


USE : 2 - 8.0 mm sq. THWN/THHN CU WIRE
1-5.5 mm sq. THWN/THHN CU WIRE
in 25 mm dia. RSC conduit

MAIN PROTECTION:
USE: 1 - 40 AT, 2P CKT BREAKER
2-8.0 sq.mm THHN IN 32mm PVC + 1 - 5.5 sq mm
Equipment Grounding Conductor
40AT, 2P, 230V,

SCHEDULE OF LOADS
VOLT-AMPHERE VOLTAGE AMPHERE PROTECTION - CB CONDUCTORS
( VA ) (V) (I) AMPHERE TRIP (AT) AF P
700 230 3.043478 15 50 2 2-2.0mm^2 THHN
1080 230 4.695652 20 50 2 2-3.5mm^2 THHN
1840 230 8 20 50 2 2-5.5mm^2 THHN
20 50

3620 15.73913

APPLICATION OF DEMAND FACTORS:


With 100% D.F.
IT = 15.7193 * D.F. + ( 25% * HRM )
IT = ( 15.7193 * 1.0 ) + ( 0.25 * 8 )
IT = 17.73913

SERVICE INTRANCE CUONDUCTORS:


USE : 2 - 8.0 mm sq. THWN/THHN CU WIRE
1-5.5 mm sq. THWN/THHN CU WIRE
in 25 mm dia. RSC conduit

MAIN PROTECTION:
USE: 1 - 40 AT, 2P CKT BREAKER
CONDUIT

20mmØ PVC
20mmØ PVC
20mmØ PVC