PROJECT: ZAAM HOTEL MAIN: 175 AT

PANEL: PB1 PER ROOM FEEDER: 2-8.0mm2 THHN


PHASE: RN EGC: 1-5.5mm2 TW
SUPPLY: 230 - 1P+N+E CONDUIT: 16 mm PVC
Circuit Protection
Circuit # Description Volts VA Amps
AT AF KaIC P
1 12- Lo 230 1200 5.22 20 50 5 1
2 9-Duplex C.O 230 1620 7.04 20 50 5 1
3 1.5Hp WCU 230 2300 10.00 20 50 5 1
4 Water Heater 230 4000 17.39 20 50 5 1
5 1.5HP ACU 230 2300 10.00 20 50 5 1
6 Oven 230 4000 17.39 20 50 5 1
7 Refregerator 230 4000 17.39 20 50 5 1
8 Range 230 4000 17.39 20 50 5 1
9 1.5 WCU 230 2300 10.00 20 50 5 1
10 1.5 WCU 230 2300 10.00 20 50 5 1
11 11-Duplex C.O 230 1980 8.61 20 50 5 1
12 Spare 230 1500 6.52 20 50 5 1

TOTAL 31500 136.96


Motor Table 4.30.14.2 Table 2.40.1.6(A) Page 88
Page 372
FEED FROM:
ENCLOSURE: NEMA 1 IOCPD=TOTAL AMPS(125%)
LOCATION: IOCPD=22.78(125%)
MOUNTING: WALL MOUNTING IOCPD=28.475=30AT
Number & Size of Wire
Conduit
Conductor Grounding ICON=AT(125%)
2-3.5mm TW 1-5.5mm2
2-3.5mm TW 1-5.5mm2
2-3.5mm TW 1-5.5mm2
2-3.5mm TW 1-5.5mm2
2-3.5mm TW 1-5.5mm3
2-3.5mm TW 1-5.5mm4
2-3.5mm TW 1-5.5mm5
2-3.5mm TW 1-5.5mm6
2-3.5mm TW 1-5.5mm7 ICON=30(125%)
2-3.5mm TW 1-5.5mm8 ICON=37.5=8.0mm2
2-3.5mm TW 1-5.5mm9
2-3.5mm TW 1-5.5mm10

Table 3.10.2.6(B)(16) Table 2.50.6.15 Table C.12


Column THHN
PROJECT: MAIN:
PANEL: Distribution Panel 1 FEEDER:
PHASE: 3Ø EGC:
SUPPLY: CONDUIT:
Amps Circuit Protection
Circuit # Description Volts VA
3Ø RN YN BN AT AF KaIC P
1 12- Lo 230 1200
2 9-Duplex C.O 230 1620
3 1.5Hp WCU 230 2300
4 Water Heater 230 4000
5 1.5HP ACU 230 2300
6 Oven 230 4000
7 Refregerator 230 4000
8 Range 230 4000
9 1.5 WCU 230 2300
10 1.5 WCU 230 2300
11 11-Duplex C.O 230 1980
RYB Elevator 230

TOTAL
Motor Table 4.30.14.4 Table 2.40.1.6(A) Page 86
Page 370
FEED FROM:
ENCLOSURE:
LOCATION:
MOUNTING:
Number & Size of Wire
Conduit
Conductor Grounding

Table 3.10.2.6(B)(16) Table 2.50.6.13 Table C.12


Column THHN
PROJECT: ZAAM HOTEL MAIN: 80AT
PANEL: PB TYPICAL ROOM (8 Units) FEEDER: 2-38mm2 THHN CU
PHASE: 1Ø EGC: 1-8.0mm2 TW CU
SUPPLY: 230 - 3P+N+E CONDUIT: 35 mm PVC
Circuit Protection
Circuit # Description Volts VA Amps
AT AF KaIC P
1 12 - LO 230 1200 5.22 20 50 5 1
2 9 - CO 230 1620 7.04 20 50 5 1
3 REFRIGERATOR 230 1500 6.52 20 50 5 1
4 ELECTRIC RANGE 230 4000 17.39 20 50 5 1
5 WATER HEATER 230 4000 6.52 20 50 5 1
6 1.5 HP ACU 230 2300 10.00 20 50 5 1
7 OVEN 230 4000 6.52 20 50 5 1
8 Spare 230 1500 6.52 20 50 5 1

TOTAL 20120 65.74


Motor Table 4.30.14.2 Table 2.40.1.6(A) Page 86
Page 370
PROJECT: ZAAM HOTEL MAIN: 20AT
PANEL: PB HALLWAY/STAFF/CONTROL FEEDER: 2-3.5mm2 THHN
PHASE: 1Ø EGC: 1-5.5mm2 TW
SUPPLY: 230 - 3P+N+E CONDUIT: 16 mm PVC
Circuit Protection
Circuit # Description Volts VA Amps
Circuit # Description Volts VA Amps
AT AF KaIC P
1 12 - LO 230 1200 5.22 15 50 5 1
2 9- LO 230 900 3.91 15 50 5 1
3 11- LO 230 1100 4.78 15 50 5 1

TOTAL 3200 13.91


Motor Table 4.30.14.2 Table 2.40.1.6(A) Page 86
Page 370
FEED FROM: SMDP 3
ENCLOSURE: NEMA 1
LOCATION: EE ROOM G
MOUNTING: WALL MOUNTING
Number & Size of Wire
Conduit
Conductor Grounding IOCPD=TOTAL AMPS(125%)
2 - 3.5 mm2 THHN CU 1 - 3.5 mm2 TW 16mm Ø PVC IOCPD=59.21(125%)
2 - 3.5 mm2 THHN CU 1 - 3.5 mm2 TW 16mm Ø PVC IOCPD=74.01=80AT
2 - 3.5 mm2 THHN CU 1 - 5.5 mm2 TW 16mm Ø PVC
2 - 3.5 mm2 THHN CU 1 - 5.5 mm2 TW 16mm Ø PVC ICON=AT(125%)
2 - 3.5 mm2 THHN CU 1 - 5.5 mm2 TW 16mm Ø PVC ICON=80(125%)
2 - 3.5 mm2 THHN CU 1 - 3.5 mm2 TW 16mm Ø PVC ICON=100=38mm2
2 - 3.5 mm2 THHN CU 1 - 5.5 mm2 TW 16mm Ø PVC
16mm Ø PVC

Table 3.10.2.6(B)(16) Table 2.50.6.13 Table C.12


Column THHN
FEED FROM: SMDP 4
ENCLOSURE: NEMA 1
LOCATION: CONTROL ROOM
MOUNTING: WALL MOUNTING IOCPD=TOTAL AMPS(125%)
Number & Size of Wire IOCPD=13.91(125%)
Conduit
Conduit
Conductor Grounding IOCPD=17.3875=20AT
2 - 2.0 mm2 THHN CU 1 - 3.5 mm2 TW 16mm Ø PVC
2 - 2.0 mm THHN CU
2
1 - 3.5 mm TW
2
16mm Ø PVC ICON=AT(125%)
2 - 2.0 mm2 THHN CU 1 - 3.5 mm2 TW 16mm Ø PVC ICON=20(125%)
ICON=25=3.5mm2

Table 3.10.2.6(B)(16) Table 2.50.6.13 Table C.12