You are on page 1of 5

GENERAL NOTES LEGEND:

LIGHTING FIXTURES
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE DISTRIBUTION BOX
WITH THESE PLANS AND SPECIFICATIONS. THE APPLICABLE
SURFACE MOUNTED FLUORESCENT
PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE CONVENIENCE OUTLET
ELECTRICAL CODE (PEC). THE RULES AND REGULATION OF THE R
S1
RECESSED SINGLE POLE
LOCAL ENFORCING AUTHORITY AND THE REQUIREMENTS OF DUPLEX CONVENIENCE OUTLET
THE LOCAL POWER COMPANY, THE ELECTRICAL WORKS SHALL 2
PENDANT S2 DUPLEX POLE
BE DONE UNDER THE IMMEDIATE SUPERVISION OD A DULY COOKING RANGE
REGISTERED ELECTRICAL ENGINEER. R
WALL MOUNTED
GFCI OUTLET
GFCI
2. THE ELECTRICAL SERVICE POWER IS1-PHASE, 2 WIRE, 230 V AC,
60 Hz

3. WIRING METHOD SHALL BE AS FOLLOWS:


LOAD TABULATION COMPUTATION
a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONSULT
b. LIGHTING, POWER RECEPTAB;E - POLYVINYL CHLORIDE GENERAL LIGHTING AND CONVENIENCE OUTLET
CONDUIT SCH. 40 BRANCH CKT., & AUXILIARY
LOAD SCHEDULE =6880 WATTS

4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED APPLICATION OF DEMAND FACTOR (D.F.)
TYPE "THW" UNLESS OTHERWISE INDICATED IN THE PLAN. THE BRANCH OUTLETS SWITCH THHN CONDUIT CIRCUIT
MINIMUM SIZE OF WIRE FOR POWER AND LIGHTING CUIRCUIT CIRCUIT WATTS VOLTS AMPS SIZE BREAKER FIRST 3000 WATTS AT 100% DF
NO. SIZE
HOMERUN SHALL BE 3.5mm² AND INSULATED FOR 600 VOLTS.
SMALLEST RACEWAY SHALL BE 15mmØ TRADE/NOMINAL SIZE.
LO CO S1 S2 (3000
230 ) = 13.04 AMPERES
SECOND 3000 WATTS AT 100% DP

5. ALL PUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP 1 14 1400 230 6.0900 1 1 2-2.0
mm ²
13mm 15 (3000
230 ) = 13.04 APMERES
REMAINING 880 WATTS AT 35% DF
TYPE WITH FACTORY KNOCKOUTS.
2 5 500 230 2.1700 1 2-2.0
mm ²
13mm 15 (880
230) = 3.826086957 x .35
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND = 1.34 AMPERES
TOTAL = 27.42 AMPERES
APPROVED TYOE FOR THE PARTICULAR LOCATION AND
PURPOSE OF USAGE.
3 3 300 230 1.3000 1 1 2-2.0
mm ²
13mm 15
SUBTOTAL FROM PANEL BOARD = 27.42 AMPERES
7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING 4 2 200 230 0.8700 1 2-2.0
mm ²
13mm 15 NET TOTAL CURRENT = 27.42 x 0.80 = 21.936 AMP.
AND POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE
REQUIREMENT. 5 7 700 230 3.0400 1 2-2.0
mm ²
13mm 15 MAIN BREAKER RATING
USE 35 AMPERES CIRCUIT
8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS 6 7 1260 230 5.4800 2-3.5
mm ²
15mm 20 BREAKER 2 POLES. 250 VOLTS
FOLLOWS:
SIZE OF SERVICE ENTRANCE WIRES
a. LIGHT SWITCH - 1.2m ABOVE FINISH FLOOR
7 6 1080 230 4.7000 2-3.5
mm ²
15mm 20 USE 2-14mm THW COPPER WIRE
b. CONVENIENCE OUTLET - 0.30m ABOVE FINISH FLOOR USE 2-2.0mm THW GROUND WIRE
8 8 1440 230 6.2600 2-3.5 15mm 20
c. PANEL BOARD - 1.50m ABOVE FINISH FLOOR mm ²
d. PUSH BUTTON OUTLET - 1.20m ABOVE FINISH FLOOR

TOTAL 31 21 230 29.9100 2-14 mm


² TWG
25mm 60

SUBJECT / CLASS CODE PLATE TITLE SHEET CONTENT STUDENT


GENERAL NOTES
AR 3151- BUILDING TECHNOLOGY 3 ELECTRICAL DRAWINGS LEGEND
MENDOZA, CZAREANA DANEILLE C.
INSTRUCTOR DATE DUE DATE SUB. SHEET NO. LOAD TABULATION ID NUMBER / COURSE&YEAR
COMPUTATION
AR. HENRY DESIERTO 2DEC'21 4DEC'21 E-1 2203601/BS ARCHITECTURE 3
SERVICE ENTRANCE
115
230 V. 3-WIRE
100 AT 30 AT
M 9
30 AT 20 AT
7 8
MAIN FEEDER 60 AT 20 AT
2-38 mm TW COPPER WIRE 5 6
1-22 mm TW COPPER WIRE 20 AT 20 AT
ON 32 mm CONDUIT PIPE 3 4
15 AT 15 AT
1 2

Cct Cct
GROUND BUS

No. No. POWER & LIGHTING PANEL

1 1 2 2 GROUND

3 3 4 4
5 5 6 6

7 7 8 8
2 RISER DIAGRAM
9 9 10 10 E 2 SCALE NTS

SPACE
11 12 SPACE

13 14
M
11 15 16 12 L
SPACE 17 18 SPACE

DUPLEX POLE
19 20

13 21 22 14 SINGLE POLE
23 24 SWITCH SWITCH
N

3-phase 4-wires panel


10 SP, 2-2P, 2-3P
CIRCUIT BREAKER

1 BREAKER DIAGRAM
SCALE NTS
E 2

GROUND

3 POLE DIAGRAM
E 2 SCALE NTS

SUBJECT / CLASS CODE PLATE TITLE SHEET CONTENT STUDENT


BREAKER DIAGRAM
AR 3151- BUILDING TECHNOLOGY 3 ELECTRICAL DRAWINGS RISER DIAGRAM
MENDOZA, CZAREANA DANEILLE C.
INSTRUCTOR DATE DUE DATE SUB. SHEET NO. POLE DIAGRAM ID NUMBER / COURSE&YEAR

AR. HENRY DESIERTO 2DUE'21 4DEC'21 E-2 2203601/BS ARCHITECTURE 3


A B C D E A B C D E
2560 3700 3000 3000 2560 3700 3000 3000

ROOF LINE
6
6
GFCI
2500
C-4

W.T.

ROOF LINE
W.T.

2500
ROOF LINE
5 2

2
2
5 GFCI W.H.
C-3
2
2
C-7
3500

NOOK
2 2

C-6

3500
R

4
2
C-2

ROOF LINE
2
C-1

2 4 2 GFCI

2
4200

GFCI
2

ROOF LINE
4200
FIREPLACE GFCI

3 GFCI
FIREPLACE 2

3
UP GFCI

4 3 2 1

5 C-5
3000

7 4 3 2 1

5 2
8 ROOF LINE

3000
9 6
GFCI 7
10

2
2
11 8

9
12

13 10

14
2 11

12
GFCI

ROOF LINE
3000

13

14

15
ROOF LINE
DOWN

3000
16

19 20

1
17 18

DOWN

1
ROOF LINE

1 GROUND FLOOR POWER SUPPLY LAYOUT 2 SECOND FLOOR POWER SUPPLY WATER
E 3 SCALE 1:100M E 3 SCALE 1:100M

SUBJECT / CLASS CODE PLATE TITLE SHEET CONTENT STUDENT


GROUND FLOOR POWER
AR 3151- BUILDING TECHNOLOGY 3 ELECTRICAL DRAWINGS SUPPLY LAYOUT MENDOZA, CZAREANA DANEILLE C.
INSTRUCTOR DATE DUE DATE SUB. SHEET NO. SECOND FLOOR POWER ID NUMBER / COURSE&YEAR
SUPPLY LAYOUT
AR. HENRY DESIERTO 2DEC'21 3DEC'21 E-3 2203601/BS ARCHITECTURE 3
A B C D E A B C D E
2560 3700 3000 3000
2560 3700 3000 3000

6 6
S1
GFCI

2500
2500

a a a

C-9

5 5 S1 S1
R
b
R
b C-13
C-15 S2 b S1
R

C-14
b

3500
a b a
3500

S2
4 2 2 4 R
b b
R
b
R
S1 b

2
C-8

a a R

Rb

4200
a
4200

C-12

S2 S1
GFCI
FIREPLACE R R R R

3 3 b b
b

UP
1
4 3 2 1
2
5 R C-10

3000
3
6
3000

4
7
5
8
6 a a
9
7
10

2 8

10
2 11

12 R
b

13
11
14 a a
12
2

3000
13
3000

14

DOWN

2
R S1 S2
C-11

1
b

1 b b

1 BASEMENT FLOOR POWER SUPPLY LAYOUT 2 GROUND FLOOR LIGHTING LAYOUT


E 4 SCALE 1:100M E 4 SCALE 1:100M

SUBJECT / CLASS CODE PLATE TITLE SHEET CONTENT STUDENT


BASEMENT FLOOR
AR 3151- BUILDING TECHNOLOGY 3 ELECTRICAL DRAWINGS POWER SUPPLY MENDOZA, CZAREANA DANEILLE C.
INSTRUCTOR DATE DUE DATE SUB. SHEET NO. GROUND FLOOR ID NUMBER / COURSE&YEAR
LIGHTING LAYOUT
AR. HENRY DESIERTO 2DEC'21 4DEC'21 E-4 2203601/BS ARCHITECTURE 3
A B C D E
2560 3700 3000 3000 A B C D E
ROOF LINE
2560 3700 3000 3000
R R R R
b b b b

6 6
C-18

C-19

W.T.

ROOF LINE
W.T.
2500

2500
ROOF LINE a R
b a

R R R
b b b

5 S2
W.H.
5 S1
R
b

R R
b b R R C-24
b b
a

R
S1
3500

3500
b
a a
a a

C-22
S1 S2
a

C.O.
ROOF LINE

4 R
b
S1 4
R R
b b
S2
R
a b

R b R
b

ROOF LINE
4200

4200
a
a a

R
b
a
b b b b

FIREPLACE S2
C-21
S1 C-23
S1 S1
S1
3 3 R
b
R
b
R
b
R R
b b
R R
1
S2
4 3 2 1 b C-20 a b 2

ROOF LINE C-16 5 S1 3


3000

3000
6 4
7 5
8 6
9 a 7
R

2
b 10 8
R

2 S2
a
b a
11 9
a
12 R R R
ROOF LINE

b 10
b b
13 11

14 12
15
ROOF LINE
13
3000

3000
R 16 14
b
17 18 19 20 R R
b b
DOWN
S2 R
b
R
b
R
b
a

1 1
R R R
b b b

ROOF LINE

1 SECOND FLOOR LIGHTING LAYOUT 2 BASEMENT FLOOR LIGHTING LAYOUT


E 5 SCALE 1:100M E 5 SCALE 1:100M

SUBJECT / CLASS CODE PLATE TITLE SHEET CONTENT STUDENT


SECOND FLOOR
AR 3151- BUILDING TECHNOLOGY 3 ELECTRICAL DRAWINGS LIGHTING LAYOUT
MENDOZA, CZAREANA DANEILLE C.
INSTRUCTOR DATE DUE DATE SUB. SHEET NO. BASEMENT FLOOR ID NUMBER / COURSE&YEAR
LIGHTING LAYOUT
AR. HENRY DESIERTO 2DEC'21 4DEC'21 E-5 2203601/BS ARCHITECTURE 3