Professional Documents
Culture Documents
prior autorization
Client:
JD-132-QA-E41-01
Project number: 58/2017 Archives number: Sheet: Total sheets:
1 14
1 of 14
CONTENTS
Content 2
Standards 3
1 Tubular conductor selection calculation for bus-bar 120/104 4~10
2 ATTACMENTS 11~14
2 of 14
1. Standards
IEC 60865-1 Short-circuit currents - Calculation of effects Part 1: Definations and calculation methods
3 of 14
1. Tubular conductor selection calculation for bus-bar
Project: 132kV QUEEN ALIYA INTERNATIONAL AIRPORT 132/33 kV Substation Time: 26.12.2018
Location: 132kV Switchyard COPPER TBULAR BUSBAR
Standard IEEE 605-2008
Design parameters
Maximum operating voltage (Attachment No.1) Schedule D1 Us = 145 kV
Nominal current during normal operation Inom = 3150 A
Maximum fault current (Attachment No.2) Schedule D1 Ik3.p = 40 kA
Short circuit time (Attachment No.2) Schedule D1 tk = 3 s
Maximum Ambient temperature (Attachment No.3) Schedule D1 Tmax = 50 ℃
Minimum Ambient temperature (Attachment No.3) Schedule D1 Tmin = -10 ℃
Operating bus temperature (Attachment No.4) IEEE-605-2008 - c.8.2.1 and Schedule D1-14.1 Tc = 80 ℃
Maximum allowable temperature (Attachment No.5) IEC60865-1-2011 c 7.3. Table 6 Tmax = 200 ℃
Altitude (Attachment No.3) Asumed ha = 800 m
Wind Velocity Vw = 1 m/s
Frequency Schedule D1 f = 50 Hz
Conductor parameters
Conductor material JD-132-T58-GEN-E-08 Copper Cu-ETP
Conductor size 120/104 mm
Outer diameter D = 0.12 m
Outer diameter Di = 0.104 m
Wall thickness t = 0.008 m
Specific electric resistivity at 20℃ (Attachment No.6) JD-132-T58-GEN-E-08 ralloy 1.78E-08 Ω/m
IACS (Attachment No.7) ICAS(%) = (1.724*10-8 /ralloy) *100% C' = 97 %
Span parameters
span length (Attachment No.8) JD-132-QH-E11-02 - Electrical section L = 5.3 m
busbar height from ground (Attachment No.8) JD-132-DE-E11-02 - Electrical section hb = 4.3 m
phase-to-phase spacing (Attachment No.9) JD-132-DE-E11-01 - Electrical plan a = 2 m
4 of 14
1 Ampacity calculation
1.1 DC resistance
Using the data from above, the cross-sectional area of selected tubular bus is
Ac
4
D 2 (D 2 t ) 2 Ac = 0.0028 m2
The magnitude of the convective heat loss generally is a function of dimensionless number known as Reynolds number. Given by formula:
𝐷 × 𝜌𝑓 × 𝑉𝑓
𝑁𝑅𝑒 =
𝜇𝑓 IEEE 738 Equation 2c Nre = 5500.99
Since the wind speed is greater than zero, the forced convectional heat loss for perpendicular wind calculated according to both Equation (3a and 3b) with K angle =1.
0.52
𝑞𝑐1 = 𝐾𝑎𝑛𝑔𝑙𝑒 × [1.01 + 1.35 × 𝑁𝑅𝑒 ] × 𝑘𝑓 × (𝑇𝑐 − 𝑇𝑚𝑎𝑥) IEEE 738 Equation 3a 104.49 W/m
0.6
𝑞𝑐2 = 𝐾𝑎𝑛𝑔𝑙𝑒 × 0.754 × 𝑁𝑅𝑒 × 𝑘𝑓 × (𝑇𝑐 − 𝑇𝑚𝑎𝑥) IEEE 738 Equation 3b 115.52 W/m
qc = 115.5 W/m
5 of 14
6 of 14
1.3 Radiation loss
The surface area by unit length of the selected tubular bus, 1m long is
A Dl A = 0.38 m2/m
Refer to equation C.13, the emissivity of copper is dependent on its age and environment conditions.
The value e 0.85 for weathered copper will be used. The radiation loss from a surface is given by:
qr 5.6697 108 eA (Tc 273) 4 (Ta 273) 4 IEEE 605 Equation C.13 qr = 84.35 W/m
1.4 solar heat gain
For solar heat gain calculation, the projected area for a cylinder is equal to its diameter:
A'=D A' = 0.12 m2/m
From Table 1 SCHEDULE D1-1 the total radiated heat flux, Qs,for a clear atmosphere is Qs = 1150 W/m2
From Table C.4, the heat multiplying factor K based on elevation less than 1000 m is K = 1.00
Angle of incidence of sun is assumed to be:
Where Hc - Altitude of sun for latitude of 31o N at noon time IEEE 605 Annex C,Table C.2 Hc = 83 o
o
Zc - Azimuth of sun for latitude of 31°N at noon time. IEEE 605 Annex C,Table C.2 Zc = 180
Zl - Azimuth of conductor line for a north–south orientation IEEE 605 Annex C,C3.2.6 Zl = 0 o
o
θ = 97
q s e Q s A ' K sin( )
IEEE 605 Equation C.15 qs = 116.43 W/m
Where e 0.85 for copper
Where s is skin depth. For copper s = 9.27mm EU Copper Publ.No.Cu0201. 2A.1.2 page 34
7 of 14
The approximate formula for shape factor S is:
𝛽
𝐹 = 1 + 𝐴𝑔( − 𝛽2 ∗ 𝐵𝑔) EU Copper Publ.No.Cu0201. 2A.1.2 page 34 F = 1.15090341
2
for g <1.6:
qc q r q s
I IEEE 605 Equation C.1 Ic = 3516.08 A
RF
8 of 14
2 Minimum size for short circuit current
The short circuit current rating of the selected tubular bus should be verified
to ensure that they are capable of carrying the available short circuit current(40 kA) for the time specified(3s)
Equation 3 will be used to determine the maximum current that the conductor can carry for 3s and a maximum conductor temperature of 200℃
9 of 14
3 Voltage gradient
3.1 onset voltage gradient
The relative air density is given by equation D.2 and D.3
273 + 𝑇𝑜 ℎ𝑎
𝐷𝑎 =( )(1 − ) IEEE 605 Equation D.2 Da = 0.85
273 + 𝑇𝑎 10
where To=25℃ is the air temperature used in determining constants Eo and C and factor m
The corona onset gradient is given by equation D.1
where m=0.85, is Air density factor, use worst case of 0.6–0.85 range suggested in D.1.1
Eo=21.1kV/cm, is Empirical constant per D.1.1
rc=D/2, is conductor outside radius
C'=0.301cm-1 is Empirical constant
3.2 maximum voltage gradient
Equivalent distance from center of conductor to ground per equation D.8
hb a
he
4hb a 2
2
IEEE 605 Equation D.8 he = 97.40 cm
Average voltage gradient per equation D.6
V1
Ea
D 4 he
ln( ) IEEE 605 Equation D.6 Ea = 4.41 kV/cm
2 D
he
Em Ea IEEE 605 Equation D.7 Em = 4.70 kV/cm
D
he
2
For satisfactory operation, Em<Ec, the selected tubular bus meets this criteria and is acceptable.
10 of 14
ATTACHMENT No.1 - SCHEDULE D1
NOTES: Means if 100% IACS copper resistivity equal 1.7241 mOhm/cm, we can determine actuall alloy resistivity by formula:
IACS= (rIACS100%/ractual)*100%
For Example:
Determine IACS for Aluminum alloy 6160B T6:
ralloy = 3.33*10-8 Ohm/m
rIACS100% = 1.724*10-8 Ohm/m
IACSalloy = (1.724*10-8/3.33*10-8)*100% = 52 %
ATTACHMENT No.8 - ELECTRICAL SECTION