SCHEDULE OF LOADS

BRANCH CKT. NO. LOAD DESCRIPTION QUANT. WATTAGE VA VOLTAGE AMP CKT FUSE SIZE WIRING SIZE CONDUIT SIZE

1 LIGHTING OUTLET 5 100 500 230 2.17 15 A 2 - #14 AWG THW 13 MM Ø CONDUIT

2 LIGHTING OUTLET 6 100 600 230 2.61 15 A 2 - #14 AWG THW 13 MM Ø CONDUIT

3 LIGHTING OUTLET 8 100 800 230 3.48 15 A 2 - #14 AWG THW 13 MM Ø CONDUIT

4 CONVENIENCE OUTLET (2 PLUG) 2 (2) 180 720 230 3.13 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

5 REFRIGERATOR 1 250 250 230 1.09 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

6 CONVENIENCE OUTLET (2 PLUG) 4 (2) 180 1440 230 6.26 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

7 CONVENIENCE OUTLET (2 PLUG) 3 (2) 180 1080 230 4.70 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

8 REFRIGERATOR 1 250 250 230 1.09 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

9 CONVENIENCE OUTLET (2 PLUG) 3 (2) 180 1080 230 4.70 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

10 CONVENIENCE OUTLET (2 PLUG) 4 (2) 180 1440 230 6.26 20 A 2 - #12 AWG THW 13 MM Ø CONDUIT

11 AIR CONDITIONING UNIT (1 HP) 1 746 746 230 30 A 2 - #10 AWG THW 20 MM Ø CONDUIT
3.24
12 AIR CONDITIONING UNIT (1 HP) 1 746 20 MM Ø CONDUIT
746 230 3.24 30 A 2 - #10 AWG THW

13 AIR CONDITIONING UNIT (1 HP) 1 746 746 230 30 A 2 - #10 AWG THW 20 MM Ø CONDUIT
3.24
14
SPARE

TOTAL 10,398 230 33.16