BASIC ELECTRICAL PLAN

Contents:
• Lighting Layout
• Power Layout
• Legend
• Schedule of Loads
• Riser Diagram / One-line Diagram
• Location Plan
• General Notes and Specifications
• Title Block
Standard Forms
Standard Forms
Standard Forms
Sample Electrical Plan
Lighting Layout
Power Layout
Legend:
Schedule of Loads:
CKT.
BREAKERS
CKT. VOLT
NO.
LOAD DESCRIPTION VOLT AMP SIZE OF WIRES AND CONDUIT
AMPERE AT AF P

8 – 100W INCANDESCENT USE 2-3.5mm2 THHN WIRE IN 15


1 800 230 3.48 20 50 2 mm DIAMETER CONDUIT.
LAMP

8 - DUPLEX CONVENIENCE USE 2-3.5mm2 THHN WIRE IN 15


2 1600 230 6.96 20 50 2 mm DIAMETER CONDUIT.
OULET

1 – 1 HP AIRCONDITIONING USE 2-3.5mm2 THHN WIRE IN 15


3 1840 230 8.00 20 50 2 mm DIAMETER CONDUIT.
UNIT

1 – 1 HP AIRCONDITIONING USE 2-3.5mm2 THHN WIRE IN 15


4 1840 230 8.00 20 50 2 mm DIAMETER CONDUIT.
UNIT
1 – 1 HP WATER PUMP USE 2-3.5mm2 THHN WIRE IN 15
5 1840 230 8.00 20 50 2 mm DIAMETER CONDUIT.

  TOTAL     34.44        

FULL LOAD CURRENT = 34.44 + 25%(8.00) = 36.44 AMPERES

MAIN FEEDER: 2 – 8.0 mm2 THW IN 20mm DIAMETER CONDUIT


 
PROTECTION: 50 AT, 100AF, 2P, 240V CIRCUIT BREAKER
 
 
OPTIONAL CALCULATIONS

Single Family Dwelling Unit, Up to 150 m2 Floor Area


COMPUTATION FOR TOTAL LOAD
General Lighting
88 m2 x 24 volt-amperes/m2 = 2,112 volt-amperes
The computed load is 2,112/230 = 9.18 Amps
*Provide one 20-ampere branch circuit
Small Appliance Load
One 20-ampere circuit @ 1,500 volt-amperes
*Provide one 20-ampere small appliance circuit.
Sub-total = 3,712 volt-amperes
Application of Demand Factor
First 3,000 volt-amperes @ 100% DF = 3,000 VA
Remainder @ 35%(712 VA x 0.35) = 249. 20VA

Other Loads
Two 1 HP room ACU, 2 x 8 A x 230 = 3,680 VA
One 1 HP water pump, 8 A X 230 = 1, 840 VA
*Provide two 20-ampere circuit. ____________
Total Net Computed Load = 8,769.2 VA

CIRCUIT REQUIREMENT
Use five 20-ampere branch circuits.
SERVICE ENTRANCE CONDUCTORS
Total Full load current:
[8,769.2 VA + 25%(1,840 VA)] /230 = 40.13 Amps.

Use two 8.0 mm2 THW wires in 20 mm(3/4 in)


diameter conduit.

SERVICE EQUIPMENT
Maximum current for protective device:
[3,000 VA +249. 20 VA + 3,680 VA
+ 250%(1,840 VA)] / 230 = 50.13 Amperes

Use 50-ampere trip, 2-pole, 240 –volt circuit


breaker.
Riser Diagram / One-line Diagram:
Location Plan:

P ST.
N A
A HA
HIN

DI M
ATA
GPU
AN
D
RIV
E
General Notes and Specifications:
1. All electrical works shall be done in accordance with these
plans and specifications, the applicable provisions of the
latest edition of the Philippine Electrical Code, the rules and
regulations of the local enforcing authority and the
requirements of the local power companies.
2. The electrical works shall be under the supervision of a duly
licensed electrical engineer.
3. All equipment, switches, panelboards, lighting fixtures and all
non-current carrying metal parts shall be properly grounded
in accordance with the Philippine Electrical Code.
4. Pullboxes, manholes or handholes shall be provided even if
not indicated in the plans if the field conditions require.
5. All materials to be used and the equipment to be installed
shall be new and must be of the approved type for the
particular location or purpose.
General Notes and Specifications:
6. The minimum size of wire and conduit shall be 3.5 mm2 THHN
and 15 mm diameter respectively unless otherwise indicated
in the plans.
7. All wires and cables to be used shall be manufactured by
Phelps Dodge or approved equivalent.
8. All branch circuit shall not be loaded more than 80% of its
rated capacity.
9. The type of power service supply shall be 230 volts, single-
phase, 60 hertz.
10. The mounting height of wiring devices shall be as follows:
a. Lighting switches………………1.40 meter above floor finish
b. Convenience Outlets…………0.30 meter above floor finish
c. Telephone outlets……………..0.30 meter above floor finish
d. Panelboards and cabinets…1.40 meter above floor finish
e. Special purpose outlets…….as indicated