You are on page 1of 1

SCHEDULE OF LOADS

CIRCUIT
CKT DESCRIPTION QTY VOLTS VA AMPHERE SIZE OF WIRE SIZE OF CONDUITS
PROTECTION
1 LIGHTING OUTLET 11 240 1100 4.58 20AT,2P 2-3.5 mm² THHN WIRE 20mmø PVC PIPE
2 LIGHTING OUTLET 12 240 1200 5.00 20AT,2P 2-3.5 mm² THHN WIRE 20mmø PVC PIPE
3 LIGHTING OUTLET 11 240 1100 4.58 20AT,2P 2-3.5 mm² THHN WIRE 20mmø PVC PIPE
4 POWER OUTLET 7 240 720 3.00 20AT,2P 2-3.5 mm² THHN WIRE 20mmø PVC PIPE
5 REFRIGERATOR 1 240 540 2.25 30AT,2P 2-5.5 mm² THHN WIRE 25mmø PVC PIPE
6 3 KW RANGE OUTLET 1 240 1560 6.5 30AT,2P 2-5.5 mm² THHN WIRE 25mmø PVC PIPE
7 1 HP WACU 1 240 1760 7.33 30AT,2P 2-5.5 mm² THHN WIRE 25mmø PVC PIPE
8 1 HP WACU 1 240 1760 7.33 30AT,2P 2-5.5 mm² THHN WIRE 25mmø PVC PIPE
9 1 HP WACU 1 240 1760 7.33 30AT,2P 2-5.5 mm² THHN WIRE 25mmø PVC PIPE
10 SPARE 1 240 1000 4.17
SERVICE ENTRANCE 240 12500 49.07 60AT,2P 30 mm² THHN/THWN 40mmø PVC PIPE
(TOTAL CONNECTED LOAD)
WIRE + 14 mm² grnd

lw = (0.80(12500+0.25(12500))+0.25(1760) =53.92 AMP


2-14 mm² THHN WIRE IN 40mmø PVC PIPE
240V MCB:100AF, 2P, 240V, 60AT, NEMA, ENTC
1760
lCB = 53.92 +( 240 )=61.25AMP