LOAD COMPUTATION AND TABULATION

CKT LOAD DESCRIPTION


NO OF TRIP SIZE OF WIRE AND
OUTLETS WATTS VOLTS AMPS SIZE OF CONDUIT
NO PROTECTION
1 60 AMP MAIN
2
2 LIGHTING OUTLET 16 1600 230V 6.95 AMP 15AMPS 2-2.0mm THW, 15mm O PVC
2
3 LIGHTING OUTLET 15 1500 230V 6.52 AMP 15AMPS 2-2.0mm THW, 15mm O PVC
2
4 LIGHTING OUTLET 17 1700 230V 7.39 AMP 15AMPS 2-2.0mm THW, 15mm O PVC
2
5 LIGHTING OUTLET 15 1500 230V 6.52 AMP 15AMPS 2-2.0mm THW, 15mm O PVC
2
6 CONVENIENCE OUTLET 7 1260 230V 5.47 AMP 20AMPS 2-3.5mm THW, 15mm O PVC
2
7 CONVENIENCE OUTLET 8 1440 230V 6.26 AMP 20AMPS 2-3.5mm THW, 15mm O PVC
2
8 REFRIGERATOR 1 500 230V 2.17AMP 30AMPS 2-5.5mm THW, 15mm O PVC
2
9 RANGE 1 3500 230V 15.21AMP 30AMPS 2-5.5mm THW, 15mm O PVC
2
10 1.5 HP ACU 1 2760 230V 12.00AMP 30AMPS 2-5.5mm THW, 15mm O PVC
2
11 1.5 HP ACU 1 2760 230V 12.00AMP 30AMPS 2-5.5mm THW, 15mm O PVC
2
12 1.5 HP ACU 1 2760 230V 12.00AMP 30AMPS 2-5.5mm THW, 15mm O PVC
2
13 2.5 HP MOTOR PUMP 1 3450 230V 15.00AMP 30AMPS 2-5.5mm THW, 15mm O PVC
14
TOTAL: 24,730 WATTS TOTAL: 107.52 AMPS
DEMAND FACTOR @ 80%
IT=24,730 /230 = 107.52 AMP.
IT= 107.52(80%)DF =86.016 AMP.