You are on page 1of 1

GENERAL NOTES: SCHEDULE OF LOADS AND COMPUTATIONS:

DISTRIBUTION PANELBOARD " DPA " (GROUND FLOOR) DISTRIBUTION PANELBOARD " DPC " (FOURTH FLOOR)
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH BRANCH BRANCH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CKT. VA PER CKT. BREAKER SIZE OF HOMERUN CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT ) NO. CKT. ( WIRES IN CONDUIT )
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C AF P AT AF P AT

3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE 1 LIGHTING OUTLETS 1260 230 100 2 20 2 - 3.5mm² THHN IN 15mm Ø C 1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
POWER COMPANY SERVICE POINT.
2 LIGHTING OUTLETS 890 20 2 - 3.5mm² THHN IN 15mm Ø C 2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED.
3 LIGHTING OUTLETS 1070 20 2 - 3.5mm² THHN IN 15mm Ø C 3 LIGHTING OUTLETS 1080 20 2 - 3.5mm² THHN IN 15mm Ø C
5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED WITH NOT LESS THAN 3.5 mm² IN SIZE.
4 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 4 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
5 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 5 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6 CONVENIENCE OUTLETS 1440 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 6 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C

8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 3HP, 1Ø, BOOSTER PUMP 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C
7 CONVENIENCE OUTLETS 1440 20 7 3910 40
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. 8 REFRIGERATOR 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 8 SPARE 1500 20

10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN 9 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 9 SPARE 1500 20
THE PLAN.
10 FACP 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 10 SPARE 1500 20
a) WALL SWITCHES @ 1300mm
b) WALL CONVENIENCE OUTLETS @ 300 mm
c) SPECIAL PURPOSE OUTLET @ 300 mm 11 CCTV 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 11 SPARE 1500 20

11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED 12 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C 12 SPARE 1500 20
3.0 TR, 1Ø, SPLIT TYPE ACU 4850
ELECTRICAL ENGINEER.

13 SPARE 1500 20 TOTAL 14340 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC

ELECTRICAL SYMBOLS: 14 SPARE 1500 20 TOTAL CONNECTED LOADS: 14340 VA

15 SPARE 1500 20 14340 (0.85) + 0.25 (17) = 57.25 AMPERES


I L @ 85% D.F. =
230

CEILING LIGHT OUTLET 16 SPARE 1500 20


USE : 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
REFER TO SCHEDULE OF
TOTAL 25650 MAIN LUGS ONLY: 150AMPS, 2P, 250V, 18KAIC (57.25 A / 115 A )
CEILING LIGHT OUTLET LIGHTING FIXTURES AND LAMPS

TOTAL CONNECTED LOADS: 25150 VA


CF CEILING FAN, 60 WATTS, 230V, 60Hz POWER PANELBOARD "PPH"
25650 (0.85) + 0.25 (21.09) = 100.07 AMPERES
I L @ 85% D.F. = BRANCH
SCF 230 USE : 2 - 50mm² THHN + 1 - 14mm² THHN (G) IN 50mm Ø C
CEILING FAN CONTROL SWITCH CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
(100.07 A / 150 A ) LOAD DESCRIPTION VOLTS ( WIRES IN CONDUIT )
NO. CKT.
S SINGLE POLE WALL SWITCH IN ONE SWITCH PLATE AF P AT
(10 AMP., 230 VOLTS)
DISTRIBUTION PANELBOARD " DPB " (SECOND & THIRD FLOOR)
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE 1 2.0HP, 1Ø, 230V, WATER PUMP MOTOR 2760 230 50 2 30 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
(10 AMP., 230 VOLTS) BRANCH
3 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
S³ LOAD DESCRIPTION VOLTS 2 2.0HP, 1Ø, 230V, WATER PUMP MOTOR 2760 230 50 2 30 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
(10 AMP., 230 VOLTS) NO. CKT. ( WIRES IN CONDUIT )
AF P AT
TOTAL 5520 MACB : 50AF, 2P, 250V, 50AT, 10KAIC
S3W THREE WAY WALL SWITCH (10 AMP., 230 VOLTS)
1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 20A, 250VOLTS
"WP" DENOTES WEATHERPROOF OUTLET 2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C TOTAL CONNECTED LOADS: 4600 VA

SPECIAL PURPOSE OUTLET, GROUNDING TYPE (20 AMP., 300 VOLTS) 3 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C 5520 (1.0) + 0.25 (12) = 27 AMPERES
SP I L @ 100% D.F. =
230 USE : 2 -8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
SINGLE CONVENIENCE OUTLET, GROUNDING TYPE 4 LIGHTING OUTLETS 1260 20 2 - 3.5mm² THHN IN 15mm Ø C
EF "EF" DENOTES EXHAUST FAN (15 AMP., 230 VOLTS)

CONCEALED OR EMBEDDED CONDUIT RUN


MAIN DISTRIBUTION PANELBOARD "MDP "
5 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C
BRANCH
UNDERGROUND OR UNDERFLOOR CONDUIT RUN 6 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
AF P AT
CIRCUIT HOMERUN 7 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
1 "DPA" 25650 230 225 2 150 2 - 50mm² THHN + 1 - 14mm² THHN (G) IN 50mm Ø C
ENCLOSED CIRCUIT BREAKER 8 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
RATING AS SHOWN ON THE PLAN
2 "DPB" 19580 230 225 2 100 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
9 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
PB PULLBOX
3 "DPC" 14340 230 225 2 100 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C
10 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
MAIN DISTRIBUTION PANELBOARD 4 "PPH" 5520 230 225 2 50 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
11 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
TOTAL 65090 MACB : 400AF, 2P, 250V, 300AT, 25KAIC
DISTRIBUTION PANELBOARD 12 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C

M ELECTRIC SERVICE METER 13 SPARE 1500 20 TOTAL CONNECTED LOADS: 64590 VA

14 SPARE 1500 20 65090


ELECTRIC SERVICE ENTRANCE I L @ 85% D.F. = (0.85) + 0.25 (21.09) = 245.82 AMPERES USE : 2 -150mm² THHN + 1 - 30mm² THHN (G) IN 80mm Ø RSC
230 (245.82 A / 295 A )
15 SPARE 1500 20

GROUNDING SYSTEM
16 SPARE 1500 20 CAPACITY OF TRANSFORMER:

TOTAL 19580 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC KVA = EI @ D.F. = 80%, DIVERSITY FACTOR = 1.10
DECKROOF
FACP FIRE ALARM CONTROL PANEL 1000

TOTAL CONNECTED LOADS: 19580 VA = (230) (283) (0.80) = 47.34 kVA


1000 (1.10) NOTE:
19580 (0.85) = 72.36 AMPERES ALL SIZES OF SERVICE FEEDER (WIRES IN CONDUIT)
I L @ 85% D.F. = USE: ONE (1) SET - 50 kVA, 34.5 kV/230V, 1Ø, 60Hz, AC, OISC, POLE MOUNTED,
230 REFER TO SCHEDULE OF LOADS AND COMPUTATIONS
DISTRIBUTION TRANSFORMER

USE : 2 - 30mm² THHN + 1 - 8.0mm² THHN (G) IN 40mm Ø C 4TH FLOOR


SCHEDULE OF LIGHTING FIXTURES AND LAMPS (72.36 A / 115 A ) "DPC"
INSTALLATION/
SYMBOLS DESCRIPTION SERVICE LATERAL PROVIDED WITH 80mmØ
MOUNTING
"TYPE F" CONDULETS FOR 230V, 2-WIRE,
SURFACED CEILING 60Hz, A.C. TO CONNECT TO AVAILABLE
1 ONE (1)-28W, 230V,60Hz AC, FLUORESCENT LIGHTING FIXTURE, BOX TYPE.
MOUNTED
POWER LINES.
"MDP"- 3 3RD FLOOR
SURFACED CEILING
2 TWO (2)-28W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE
MOUNTED
REINFORCED CONCRETE ELECTRIC
PEDESTAL 5.00m X 0.30m X 0.30m "DPB"

300mm
ONE (1)-18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE WITH SURFACED CEILING

3100mm (MIN.) - 5500mm (MAX.)


MEDIUM BASE KEYLESS TYPE PORCELAIN RECEPTACLE MOUNTED

ELECTRIC SERVICE
ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT METER (CTC METERING)
NOTE: WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES, "MDP"- 2 2ND FLOOR
WIRED AND READY FOR USE.
"PPH" PROPOSED: 2.0HP, 1Ø, 230V,
60Hz., AC, WATER PUMP MOTOR
M "DPA" "MDP"
MANHOLE SIZE
AS REQUIRED

1800mm
WP WP

FIN. FLOOR LINE A A


FIN. GRADE LINE
MH
TO "MDP"- 4
1-30mm² THHN IN 20mmØ C. -
2- 150mm² THHN + 1-30mm²THHN(G) CLAMPED TO A 25mmØ X
1-5.5mm² THHN IN 15mmØ C.
IN 80mmØ RSC 3000mm COPPERCLAD AUTOMATIC CIRCUIT BREAKER
A - CLAMPED TO A 16mmØ X
GROUNDING ELECTRODE 50AF, 2P, 240VOLTS, 30AT
2400mm COPPERCLAD
IN NEMA 3R ENCLOSURE
GROUNDING ELECTRODE
ELECTRICAL RISER DIAGRAM B
AUTOMATIC CIRCUIT BREAKER
NOT TO SCALE 50AF, 2P, 240VOLTS, 40AT
IN NEMA 3R ENCLOSURE

AUTOMATIC CIRCUIT BREAKER


C 100AF, 2P, 240VOLTS, 60AT
IN NEMA 3R ENCLOSURE

REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED: SIGNED SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO. SHEET NO.
MARU BRYAN T. ZAPLAN
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS GENERAL NOTES
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
MODIFIED STANDARD DPWH - DEPED ELECTRICAL SYMBOLS CADD: SIGNED
BUREAU OF DESIGN FOUR (4) STOREY, TWENTY (20) SCHEDULE OF LOADS MARU BRYAN T. ZAPLAN
ENGINEER II
APPROVED WITH SIGNATURE BOD
E-8
BUILDINGS DIVISION SCHEDULE OF LIGHTING FIXTURES AND LAMPS JOSEPHINE P. ISTURIS LEA N. DELFINADO GILBERTO S. REYES LEONOR M. BRIONES
CLASSROOM SCHOOL BUILDING ELECTRICAL RISER DIAGRAM CHECKED: SIGNED B 12 90
ERIBERTO B. SIOSON OIC, UNDERSECRETARY FOR
BONIFACIO DRIVE PORT AREA, MANILA CHIEF, BUILDINGS DIVISION OFFICER-IN-CHARGE, BOD SECRETARY, DEP ED
ENGINEER IV TECHNICAL SERVICES, DPWH

You might also like