DISTRIBUTION PANELBOARD " DPA " (GROUND FLOOR) DISTRIBUTION PANELBOARD " DPC " (FOURTH FLOOR)
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND REGULATIONS OF THE LOCAL GOVERNMENT AND WITH BRANCH BRANCH
THE REQUIREMENTS OF THE LOCAL POWER COMPANY. CKT. VA PER CKT. BREAKER SIZE OF HOMERUN CKT. VA PER CKT. BREAKER SIZE OF HOMERUN
LOAD DESCRIPTION VOLTS LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT ) NO. CKT. ( WIRES IN CONDUIT )
2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60 HERTZ, A.C AF P AT AF P AT
3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE 1 LIGHTING OUTLETS 1260 230 100 2 20 2 - 3.5mm² THHN IN 15mm Ø C 1 LIGHTING OUTLETS 1260 230 50 2 20 2 - 3.5mm² THHN IN 15mm Ø C
POWER COMPANY SERVICE POINT.
2 LIGHTING OUTLETS 890 20 2 - 3.5mm² THHN IN 15mm Ø C 2 LIGHTING OUTLETS 840 20 2 - 3.5mm² THHN IN 15mm Ø C
4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED SHALL BE
3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED.
3 LIGHTING OUTLETS 1070 20 2 - 3.5mm² THHN IN 15mm Ø C 3 LIGHTING OUTLETS 1080 20 2 - 3.5mm² THHN IN 15mm Ø C
5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED WITH NOT LESS THAN 3.5 mm² IN SIZE.
4 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 4 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT CONVENIENT AND
INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE PLAN NOR MENTIONED IN THE SPECIFICATIONS.
5 CEILING FAN OUTLETS 600 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 5 CEILING FAN OUTLETS 900 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ACCORDANCE
WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE. 6 CONVENIENCE OUTLETS 1440 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 6 CONVENIENCE OUTLETS 2160 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C
8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND PURPOSE. 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 3HP, 1Ø, BOOSTER PUMP 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C
7 CONVENIENCE OUTLETS 1440 20 7 3910 40
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER APPURTENANCES FOR THE ENTIRE
ELECTRICAL INSTALLATION SHALL BE USED. 8 REFRIGERATOR 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 8 SPARE 1500 20
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED FLOOR LEVEL UNLESS NOTED IN 9 SPECIAL PURPOSE OUTLET 3000 30 2 - 5.5mm² THHN + 1 - 5.5mm² THHN (G) IN 15mm Ø C 9 SPARE 1500 20
THE PLAN.
10 FACP 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 10 SPARE 1500 20
a) WALL SWITCHES @ 1300mm
b) WALL CONVENIENCE OUTLETS @ 300 mm
c) SPECIAL PURPOSE OUTLET @ 300 mm 11 CCTV 1500 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) IN 15mm Ø C 11 SPARE 1500 20
11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY REGISTERED 12 60 2 - 8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C 12 SPARE 1500 20
3.0 TR, 1Ø, SPLIT TYPE ACU 4850
ELECTRICAL ENGINEER.
13 SPARE 1500 20 TOTAL 14340 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC
SPECIAL PURPOSE OUTLET, GROUNDING TYPE (20 AMP., 300 VOLTS) 3 LIGHTING OUTLETS 1030 20 2 - 3.5mm² THHN IN 15mm Ø C 5520 (1.0) + 0.25 (12) = 27 AMPERES
SP I L @ 100% D.F. =
230 USE : 2 -8.0mm² THHN + 1 - 5.5mm² THHN (G) IN 20mm Ø C
SINGLE CONVENIENCE OUTLET, GROUNDING TYPE 4 LIGHTING OUTLETS 1260 20 2 - 3.5mm² THHN IN 15mm Ø C
EF "EF" DENOTES EXHAUST FAN (15 AMP., 230 VOLTS)
GROUNDING SYSTEM
16 SPARE 1500 20 CAPACITY OF TRANSFORMER:
TOTAL 19580 MAIN ACB: 100AF, 2P, 100AT, 250V, 18KAIC KVA = EI @ D.F. = 80%, DIVERSITY FACTOR = 1.10
DECKROOF
FACP FIRE ALARM CONTROL PANEL 1000
300mm
ONE (1)-18W, 230V, 60Hz AC,COMPACT FLUORESCENT LIGHTING FIXTURE WITH SURFACED CEILING
ELECTRIC SERVICE
ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT METER (CTC METERING)
NOTE: WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES, "MDP"- 2 2ND FLOOR
WIRED AND READY FOR USE.
"PPH" PROPOSED: 2.0HP, 1Ø, 230V,
60Hz., AC, WATER PUMP MOTOR
M "DPA" "MDP"
MANHOLE SIZE
AS REQUIRED
1800mm
WP WP
REPUBLIC OF THE PHILIPPINES PROJECT AND LOCATION: SHEET CONTENTS: DESIGNED: SIGNED SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SET NO. SHEET NO.
MARU BRYAN T. ZAPLAN
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS GENERAL NOTES
ENGINEER II
SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE SEE COVER SHEET FOR SIGNATURE
MODIFIED STANDARD DPWH - DEPED ELECTRICAL SYMBOLS CADD: SIGNED
BUREAU OF DESIGN FOUR (4) STOREY, TWENTY (20) SCHEDULE OF LOADS MARU BRYAN T. ZAPLAN
ENGINEER II
APPROVED WITH SIGNATURE BOD
E-8
BUILDINGS DIVISION SCHEDULE OF LIGHTING FIXTURES AND LAMPS JOSEPHINE P. ISTURIS LEA N. DELFINADO GILBERTO S. REYES LEONOR M. BRIONES
CLASSROOM SCHOOL BUILDING ELECTRICAL RISER DIAGRAM CHECKED: SIGNED B 12 90
ERIBERTO B. SIOSON OIC, UNDERSECRETARY FOR
BONIFACIO DRIVE PORT AREA, MANILA CHIEF, BUILDINGS DIVISION OFFICER-IN-CHARGE, BOD SECRETARY, DEP ED
ENGINEER IV TECHNICAL SERVICES, DPWH