OF LOAD
ELECTRICAL COMPUTATIONS
PREPARED BY
Computations to be applied in a
circuit.
OBJECTIVES!
After the lecture ends, you must able to
determine:
LIGHTING
11 1100
OUTLET (CFL)
1 230 5.83
PIN LIGHT 16 240
STEP 3
Determine the no. of control switch
installed according to the plan.
11 L.O
NOTE:
COUNT THE SWITCHES
INSTALLED ACCORDING
TO ITS CLASS.
SWITCH AMP. BR. RATING
CKT LOAD WATT SIZE OF WIRE
L.O. C.O. VOLTS LD/CK
NO. DESCRIPTION LOAD AND CONDUIT
S1 S2 S3 T AT AF
LIGHTING
11 1100
OUTLET (CFL)
1 3 3 2 230 5.83
PIN LIGHT 16 240
STEP 4
Determine the circuit protection rating
(CKT. BREAKER) and Wire & Conduit size
to be installed based on the ampere load
of the circuit.
BREAKER
LIGHTING
11 1100
OUTLET (CFL) 100
1 3 3 2 230 5.83 15A
A
PIN LIGHT 16 240
WIRE & CONDUIT
• Determine the size of wire to be used
by following the rule, that the amperage
capacity of the conductor and the fuse
shall not exceed to 80%. Refer also to
the table provided for wire and conduit
size.
WIRE size guide
CONDUIT size guide
SWITCH AMP. BR. RATING
CKT LOAD WATT SIZE OF WIRE
L.O. C.O. VOLTS LD/CK
NO. DESCRIPTION LOAD AND CONDUIT
S1 S2 S3 T. AT AF
LIGHTING 2 – 14 AWG
11 1100
OUTLET (CFL) 100 THHN in
1 3 3 2 230 5.83 15A
A 13mm DIA.
PIN LIGHT 16 240 CONDUIT
CONVENIENCE
OUTLET
STEP 1
Determine the number of convenience
outlets by direct counting.
CKT.2
6 C.O.
CKT.3
5 C.O.
NOTE:
GET THE TOTAL COUNT
OF CONVENIENCE
OUTLET WITH IN A
SINGLE CIRCUIT.
SWITCH AMP. BR. RATING
CKT LOAD WATT SIZE OF WIRE
L.O. C.O. VOLTS LD/CK
NO. DESCRIPTION LOAD AND CONDUIT
S1 S2 S3 T AT AF
LIGHTING 2 – 14 AWG
11 1100
OUTLET (CFL) 100 THHN in
1 3 3 2 230 5.83 15A
A 13mm DIA.
PIN LIGHT 16 240 CONDUIT
CONVENIENCE
2 6
OUTLET
CONVENIENCE
3 5
OUTLET
STEP 2
Determine the number of special outlets
(SP.O.) by direct counting.
CKT.4
A.C.U.
CKT.5
REF
CKT.6
RANGE
SWITCH AMP. BR. RATING
CKT LOAD WATT SIZE OF WIRE
L.O. C.O. VOLTS LD/CK
NO. DESCRIPTION LOAD AND CONDUIT
S1 S2 S3 T AT AF
LIGHTING 2 – 14 AWG
11 1100
OUTLET (CFL) 100 THHN in
1 3 3 2 230 5.83 15A
A 13mm DIA.
PIN LIGHT 16 240 CONDUIT
CONVENIENCE
2 6
OUTLET
CONVENIENCE
3 5
OUTLET
4 A.C.U. 1
5 REF 1
6 RANGE 1
STEP 3
Compute the Total Power (watts) of C.O.
by multiplying the Total number of
Convenience outlets to its corresponding
Wattage rating provide by the NEC.
LIGHTING 2 – 14 AWG
11 1100
OUTLET (CFL) 100 THHN in
1 3 3 2 230 5.83 15A
A 13mm DIA.
PIN LIGHT 16 240 CONDUIT
CONVENIENCE
2 6 2160 230 9.39
OUTLET
CONVENIENCE
3 5 1800 230 7.83
OUTLET
4 A.C.U. 1
5 REF 1
6 RANGE 1
STEP 4
Determine the Power (watts) of SP.O. by
referring to the corresponding Wattage
rating of appliance at the provided
general wattage chart.
LIGHTING 2 – 14 AWG
11 1100
OUTLET (CFL) 100 THHN in
1 3 3 2 230 5.83 15A
A 13mm DIA.
PIN LIGHT 16 240 CONDUIT
CONVENIENCE 100
2 6 2160 230 9.39 20A
OUTLET A
CONVENIENCE 100
3 5 1800 230 7.83 20A
OUTLET A
100
4 A.C.U. 1 900 230 3.91 20A
A
100
5 REF 1 600 230 2.61 20A
A
100
6 RANGE 1 750 230 3.26 20A
A
STEP 5
Determine the circuit protection rating
(CKT. BREAKER) and Wire & Conduit size
to be installed based on the ampere load
of the circuit.
BREAKER
7 SPARE
32.8 100
TOTAL 27 14 3 3 2 7550 230
3 A
FEEDER LINE
SWITCH AMP. BR. RATING
CKT LOAD WATT SIZE OF WIRE
L.O. C.O. VOLTS LD/CK
NO. DESCRIPTION S1 S2 S3 LOAD AT AF AND CONDUIT
T
LIGHTING
11 1100 100 2 – 14 AWG
1 OUTLET (CFL) 3 3 2 230 5.83 15A THHN in 13mm
A DIA. CONDUIT
PIN LIGHT 16 240
2 – 12 AWG
CONVENIENCE 100
2 6 2160 230 9.39 20A THHN in 13mm
OUTLET A DIA. CONDUIT
2 – 12 AWG
CONVENIENCE 100
3 5 1800 230 7.83 20A THHN in 13mm
OUTLET A DIA. CONDUIT
2 – 12 AWG
100
4 A.C.U. 1 900 230 3.91 20A THHN in 13mm
A DIA. CONDUIT
2 – 12 AWG
100
5 REF 1 600 230 2.61 20A THHN in 13mm
A DIA. CONDUIT
2 – 12 AWG
100
6 RANGE 1 750 230 3.26 20A THHN in 13mm
A DIA. CONDUIT
7 SPARE
2 – 8 AWG TW
1 – 8 AWG TW in
32.8 100
TOTAL 27 14 3 3 2 7550 230 60A 32mm DIA.
3 A CONDUIT
DEMAND FACTOR (80%): 32.83A X 0.80= 26.26 AMPERES