Professional Documents
Culture Documents
201700068
LAB ASSIGNMENT 2
Contents
AIMS AND OBJECTIVES................................................................................................................................2
INTRODUCTION...........................................................................................................................................2
THEORY........................................................................................................................................................3
PROCEDURE.................................................................................................................................................6
RESULTS AND ANALYSIS..............................................................................................................................7
DISCUSSION...............................................................................................................................................10
CONCLUSION.............................................................................................................................................10
REFERENCES..............................................................................................................................................11
2
INTRODUCTION
A transmission line having a length more than 240 km is considered as a long transmission line. In a long
transmission line, parameters are uniformly distributed along the whole length of the line. For a long
transmission line, it is considered that the line may be divided into various sections, and each section
consists of an inductance, capacitance, resistance and conductance. Long transmission lines can be in
either T-nominal or pi-nominal .In this experiment a long transmission line of T-nominal with inductive
loading will be studied and analyzed.
3
THEORY
In a nominal T model of a long transmission line, the series impedance is divided into two equal parts,
while the shunt admittance is concentrated at the Centre of the line. In the nominal T model of a long
transmission line the lumped shunt admittance is placed in the middle, while the net series impedance is
divided into two equal halves and placed on either side of the shunt admittance[1]. The circuit so
formed resembles the symbol of a capital T. The nominal T model of a long transmission line is shown in
the figure 1 below.
Here;
Or
comparing equation for VS and IS with the standard ABCD parameter equations
The phasor diagram of the nominal T-circuit is shown below. It is drawn for a lagging power factor.
5
PROCEDURE
EQUIPMENT USED
Distribution Trainer
Digital Multimeters
Connection leads
The experiment was done for a single-phase long T-nominal transmission line. A certain voltage was
applied from the sending end and the load connected to the secondary line was varied. Readings were
collected for applied voltages, receiving end voltage, load current, sending end and receiving end power
and were tabulated. It was always ensured that the current transformer secondary was either short
circuited or connected to a meter.
7
MEASUREMENTS
VS(v) VC(v) VR(v) IS(A) IR(A) IC(A) PS(W) PR(W)
228 220 227 0.25 0.13 0.65 20 5
228 220 227 0.25 0.70 0.75 30 10
228 220 226 0.50 1.10 0.70 40 20
228 217 224 0.85 1.50 0.70 40 20
228 218 221 1.20 1.85 0.71 45 25
TABLE 1; MEASURED VALUES
CALCULATIONS
SAMPLE CALCULATIONS
a. Power factor
Power=IVCos(φ)
Power( W )
∴ power factor =Cosφ=
IV
Power (W ) 5
power factor=Cosφr= = =0.16943409
IV 0.13∗227
Cosφr=0.16943409
φr =80.24 °
Power (W ) 20
power factor=cos φ S= = =0.350877193
IV 0.25∗228
power factor=0.350877193
φ S=69.46°
b. Impedance1
impedance=R+ jXl
( V S−V C ) 228−220
Z L1= =
IS 0.25
impedance 1=32 Ω
2× π × 60
Line inductance L = =10.44 H
30.1
c. Voltage regulation
Vs−Vr
%tage Voltage regulation= ×100
Vr
9
228−227
¿ ×100
227
= 0.44%
Efficiency
PR
efficiency = × 100
PR+ PL
5
¿ 2 2
×100=84.9 %
5+0.13 ×11.2+0.25 ×11.2
DISCUSSION
From the calculated values in table 2, it can be seen that as the power at the receiving end increases the
load power factor or the power factor at the receiving end also increases. As the line resistance
decreases it is noticed that the voltage regulation increases. This shows that there is an indirect relation
between the voltage regulation and the line resistance.
From the results it can also be noticed that the long transmission line has high efficiency, this high
efficiency is caused by high sending end and receiving end power of the long line [4]. There were errors
that were encountered during the progression of the lab experiment. These errors in measurement
were caused by added resistances that were added by the connecting wires. These added errors
contributed to the low accuracy of some of the readings and calculations of the long transmission line
that.
CONCLUSION
The aims of this experiment were to; analyze and investigate a long transmission line so that;the
parameters of the line can be determined,the line regulation can be determined,the efficiency of
transmission can be calculatedThe phasor diagram can be drawn to scale.These aims were satisfied and
it can be concluded that the long transmission has a lagging power factor. This means that the receiving
end current Ir is lagging the receiving end Voltage Vr by an angle α.The long transmission line also has a
high efficiency.
11
REFERENCES
[1] Fink, D.G. and Beaty, H.W (1993) Standard Handbook for Electrical Engineers, 13th ed., McGraw-
Hill ,New York.
[2] Mohammad H. Rashid. (2004): Power Generation and Transmission, Prentice Hall of India Pty Ltd,
India.
[3] Singh M.D. (2008), Engineering for Beginners, Tata McGraw Hill Publishing Company Ltd, Chicago..
[4] Theraja B.L , A textbook of electrical technology, Ram Nagar, New Delhi, India: S. Chand & Co., 2010.