TEST REPORT
General Inspection:
Physical inspection of the Relay : Ok
AC/DC Voltage Checks : Ok
Panel Earthing Checks : Ok
Panel Illumination & Heaters : Ok
CT & PT Wiring Checks : Ok
CT& PT Earthing as per the scheme : OK
Metering Checks:
PT Ratio: 11000V / 110V
CT Ratio: 6000/1A
Differential Protection:
Settings:
Gen Diff Is1> : 50.00 mA
Gen Diff K1> : 0%
Gen Diff Is2> : 1.000 A
Gen Diff K2> : 120.0%
Expected
Injected current ( A ) Measured Values(kA)
values(kA)
S.NO at Secondary At Primary STATUS Time (Sec)
At primary
SIDE A SIDE B Id IR Id IR
0.864 ∟0° 0.864 ∟180° 0.00 5184 0.006 5189
Stable
1. 0.864 ∟240° 0.864 ∟60° 0.00 5184 0.006 5189 In K1 slope No –Trip
región
0.864 ∟120° 0.864 ∟300° 0.00 5184 0.006 5189
I>> : Disabled
I>> : Disabled
Power Protection:
Ffail1 Settings:
Ffail1 – Xa1 : 9.000 ohms
Ffail1 Xb1 : 160 ohms
tFfail1 : 0.0 secs
DO Ffail1 : 0 secs.
Ffail2 Settings:
Ffail2 – Xa2 : 20.00 ohms
Ffail1 Xb2 : 74.00 ohms
tFfail2 : 0 secs
DO Ffail2 : 0 secs.
Reverse Angle
Ph Voltage ( V ) Current ( A ) Impedance Time Status
R 63.5 L0 0.7 L164
Y 63.5 L240 0.7 L44 90 2.01 Sec
B 63.5 L120 0.7 L284
Note:86B TRIP
Voltage Relay Operated at I vector reaching the No of Slip Count Optd Time
Current and angle value:- (Sec)
35.0 ∟+0°,240°,120° 1.00 ∟+150°,30°,270° 1 0.024
35. ∟+0°,240°,120° 1.00 ∟+160°,40°,280° 2 0.024
12.10 ∟+0° 1.00 ∟+135° Continuous Rotate No trip
Zone checking:
Stage STATUS
Poleslip ZONE1 Trip Found Ok
Poleslip ZONE2 Trip Found Ok
Pole slip Reset time -30sec Found ok (by injecting second count pole slip after 30sec
time delay)
Inhibit of Poleslip function when External VT-1 fail condition – found ok
Note: 86C TRIP
Expected TRIP
SET PICKUP Voltage OPEARTING TRIP
S.NO Phase TIME
Volts (VN>derived )Volts TIME ( Sec )
( Sec )
INJECTING:
Ph Voltage ( V ) Hz
R 50.0 L0 50Hz
Y 50.0 L240 50Hz
B 50.0 L120 50Hz
SET Pick
Phase
Volts Volts Hz
VN1 0.5 0.5 150
1.000 1.04
Under Frequency:
F<1 Status Enabled
F<1 Setting 48.50 Hz
F<1 Time Delay 2.000 s
F<2 Status Enabled
F<2 Setting 47.50 Hz
F<2 Time Delay 1.500 s
Note:86B TRIP
Over Frequency:
F>1 Status Enabled
F>1 Setting 51.00 Hz
F>1 Time Delay 1.000 s
F>2 Status Enabled
F>2 Setting 51.50 Hz
F>2 Time Delay 1.500 s
Note:86B TRIP
I2> pick up :
FUNCTION SET I2> PICK UP CURRENT SET TIME OPEARTING
ALARM (A) I2> ( A ) ( Sec ) TIME ( Sec )
Actual
SET Injected Expected Status
S. Operating
I2> Current (A) Operating
no Time(Sec)
(A) Time(Sec)
R Y B AT K=6 AT K=6 Tripping
1. 0.07 0.5∟0° 0.5 ∟120° 0.5∟240° 24.23 24.23 Found Ok
Status
Injected Frequency Expect Operated Actual Operated
Sl.No Stage V/F Pickup V/f
(Hz) Time(Sec) Time(Sec)
Note:86C TRIP
Setting:
Dead Mach Status Enabled
DM CT Source IA-1 IB-1 IC-1
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.
B 63.5
Note:86C TRIP
Stage -2:
B 63.5
B 63.5
Stage -2:
PH Voltage Set Voltage Pickup Voltage Set Time Pickup Time
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.
(V)
R 63.5
72.74 V 72.16 V 2.0 Sec 2.04 Sec
Y 63.5
B 63.5
51.96 51.96 51.96 1.0 1.0 1.0 V>VS1 V>VS1 Blocking Blocking Found ok
51.96 51.96 51.96 1.1 1.1 1.1 V>VS1 V>VS1 1.83 1.77 Found ok
51.96 51.96 51.96 2.0 2.0 2.0 V>VS1 V>VS1 0.25 0.26 Found ok
46.18 46.18 46.18 1.1 1.1 1.1 V>VS1 V>VS1 1.83 1.72 Found ok
46.18 46.18 46.18 2.0 2.0 2.0 V>VS1 V>VS1 0.25 0.25 Found ok
28.86 28.86 28.86 0.25 0.25 0.25 V <VS2 V <VS2 Blocking Blocking Found ok
28.86 28.86 28.86 0.3 0.3 0.3 V <VS2 V <VS2 0.958 0.955 Found ok
34.64 34.64 34.64 0.3 0.3 0.3 V <VS2 V <VS2 0.958 1.05 Found ok
Note:86A TRIP
Testing of P343 using P391 injection unit for Rotor Earth Fault
Resistance Resistance
in Relay
A 500 Ohms 550ohm
B 500 Ohms 550ohm
A&B 1000 Ohms 1050ohm