Report No: Schneider/P343/JSW-001

CHECK LIST AND RECORDING FORMAT FOR GENERATOR PROTECTION


RELAY TYPE MiCOM P343
CUSTOMER: JSW STEEL LTD -BELLARY. KARNATAKA
MiCOM P343 Generator Protection Relay

TEST REPORT

Customer: JSW Date: 10.05.2013


Model No: P343318Q2M0368K Aux. Voltage: 110 /250V DC
Serial No: 36146142/01/12 Rated Current: 1 A
Frequency: 50 Hz Rated Voltage: 110 V

General Inspection:
Physical inspection of the Relay : Ok
AC/DC Voltage Checks : Ok
Panel Earthing Checks : Ok
Panel Illumination & Heaters : Ok
CT & PT Wiring Checks : Ok
CT& PT Earthing as per the scheme : OK

Metering Checks:
PT Ratio: 11000V / 110V
CT Ratio: 6000/1A

Injected Current Relay Metered value


A1- Ph Current 1A 6.009 kA
B1- Ph Current 1A 6.009 kA
C1- Ph Current 1A 6.009 kA

Differential i/p Injected Current Relay Metered value


A2- Ph Current 1A 6.009 kA
B2- Ph Current 1A 6.009 kA
C2- Ph Current 1A 6.009 kA

Applied Voltage Relay Metered value


A-B Ph Volts 110 V 11.02 kV
B-C Ph Volts 110 V 11.02 kV
C-A Ph Volts 110 V 11.02 kV

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
1
Report No: Schneider/P343/JSW-001

Differential Protection:
Settings:
Gen Diff Is1> : 50.00 mA
Gen Diff K1> : 0%
Gen Diff Is2> : 1.000 A
Gen Diff K2> : 120.0%

A Side Pickup Test


Is1> Sensitivity & timing test:

Actual Pickup Value Operating time


A ph 50 mA 40 msec
B ph 50 mA 40 msec
C PH 50 mA 40 msec

B Side Pickup Test


Is1> Sensitivity & timing test:

Actual Pickup Value Operating time


A ph 50 mA 40 msec
B ph 50 mA 40 msec
C PH 50 mA 40 msec

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
2
Report No: Schneider/P343/JSW-001

FULL LOAD CURRENT IN SIDE A : 5184 A @PRIMARY 0.864 A @SECONDARY


FULL LOAD CURRENT IN SIDE B : 5184 A @PRIMARY 0.864 A @SECONDARY

Stability Checks (87G):

Expected
Injected current ( A ) Measured Values(kA)
values(kA)
S.NO at Secondary At Primary STATUS Time (Sec)
At primary
SIDE A SIDE B Id IR Id IR
0.864 ∟0° 0.864 ∟180° 0.00 5184 0.006 5189
Stable
1. 0.864 ∟240° 0.864 ∟60° 0.00 5184 0.006 5189 In K1 slope No –Trip
región
0.864 ∟120° 0.864 ∟300° 0.00 5184 0.006 5189

1.000 ∟0° 1.000 ∟180° 0.00 6000 0.000 6007


Stable
2. 1.000 ∟240° 1.000 ∟-60° 0.00 6000 0.000 6007 In K2 slope No-Trip
región
1.000 ∟120° 1.000 ∟300° 0.00 6000 0.000 6007

0.814 ∟0° 0.864 ∟180° 0.05 0.830 0.05 0.838


Un Stable
Trip
3. 0.814 ∟240° 0.864 ∟60° 0.05 0.830 0.05 0.838 In K1 slope
0.04
región
0.814 ∟120° 0.864 ∟300° 0.05 0.830 0.05 0.838

2.000 L0° 1.200 ∟180° 0.792 1.607 0.792 1.607


Un stable
Trip
4. 2.000 ∟240° 1.200 ∟60° 0.792 1.607 0.792 1.607 in K2 slope
0.04
región
2.000 ∟120° 1.200 ∟300° 0.792 1.607 0.792 1.607

3.000 L0° 1.460 L180° 1.545 2.235 1.545 2.235


Un stable
1.545 1.545 Trip
5. 3.000 ∟240° 1.460 ∟60° 2.235 2.235 in K2 slope
0.04
1.545 1.545 región
3.000 ∟120° 1.460 ∟300° 2.235 2.235

K1 ~ SLOPE: IdIFF, s1 = K1*IBIAS + IS1 (IF IBIAS < IS2)

K2 ~ SLOPE: IdIFF, s2 = K2*(IBIAS – IS2) + K1*IS2+IS1 (IF IBIAS > IS2)


Note: 86A TRIP
Over Current Protection:
Settings:
I>1 : 910 mA
I>1 Function: DT
tI>1 Time delay: 10 secs
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
3
Report No: Schneider/P343/JSW-001

I>> : Disabled
I>> : Disabled

I>1 Sensitivity & timing test:

Actual Pickup Value Operating time


A ph 0.910 A 10.05 secs
B ph 0.910 A 10.05 secs
C PH 0.910 A 10.05 secs

Power Protection:

Power1 Function : Low Forward.


P>1 : 1 Watts
tP>1 : 1.5 secs

Ph Voltage ( V ) Current ( A ) Measuring Measuring Watts


Watts in relay in relay
( Primary ) (Secondary )
R 63.5 L0 0.005 L0
Y 63.5 L240 0.005 L240 0.685 MW 1 watts
B 63.5 L120 0.005 L120

tP>1 : 1.54 secs


Note: Testing carried out At Unity Power factor.,L1GCB CLOSED, VT Fail Alarm is
not come 86B Relay OPTD
Note: 86C TRIP

Power2 Function : Reverse Power.


P>2 : -1 Watts
tP>2 : 1.5 secs

Ph Voltage ( V ) Current ( A ) Measuring Measuring Watts


Watts in relay in relay
( Primary ) (Secondary )
R 63.5 L0 0.006 L180
Y 63.5 L240 0.006 L60 0.685 MW 1 watts
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
4
Report No: Schneider/P343/JSW-001

B 63.5 L120 0.006L300

tP>2 : 1.54 secs


Note: 86C TRIP

Field Failure Protection:


Ffail1 Settings:
Ffail Alm Settings:
Ffail1Alm Angle: 15.00 deg
Ffail1Alm Delay: 2.00 Sec

Ffail1 Settings:
Ffail1 – Xa1 : 9.000 ohms
Ffail1 Xb1 : 160 ohms
tFfail1 : 0.0 secs
DO Ffail1 : 0 secs.

Ffail2 Settings:
Ffail2 – Xa2 : 20.00 ohms
Ffail1 Xb2 : 74.00 ohms
tFfail2 : 0 secs
DO Ffail2 : 0 secs.

Ffail Alm Check:


Forward Angle
Ph Voltage ( V ) Current ( A ) Impedance Time Status
R 63.5 L0 0.7 L16
Y 63.5 L240 0.7 L225 90 2.01 Sec
B 63.5 L120 0.7 L135

Reverse Angle
Ph Voltage ( V ) Current ( A ) Impedance Time Status
R 63.5 L0 0.7 L164
Y 63.5 L240 0.7 L44 90 2.01 Sec
B 63.5 L120 0.7 L284

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
5
Report No: Schneider/P343/JSW-001

Ffail Stage-1 Check: Without under Voltage


A side:
Ph Voltage ( V ) Current ( A ) Impedance Status
R 63.5 L0 0.376 L90
Y 63.5 L240 0.376 L330 168.88 Tripping
B 63.5 L120 0.376 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 63.5 L0 0.370 L90 Not
Y 63.5 L240 0.370 L330 171.62 Tripping
B 63.5 L120 0.370 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 63.5 L0 0.380 L90 Continually
Y 63.5 L240 0.380 L330 167.10 Pickup
B 63.5 L120 0.380 L210
D Side:
Ph Voltage ( V ) Current ( A ) Impedance Status
R 63.5 L0 7.1 L90 Not
Y 63.5 L240 7.1 L330 8.94 Tripping
B 63.5 L120 7.1 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 63.5 L0 7.04 L90
Y 63.5 L240 7.04 L330 9.01 Tripping
B 63.5 L120 7.04 L210 Region

Set Time Tripping


Time
1.00 Sec 1.05 Sec

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
6
Report No: Schneider/P343/JSW-001

Ffail Stage-2 Check: Without under Voltage


A side:
Ph Voltage ( V ) Current ( A ) Impedance Status
R 63.5 L0 0.7 L90 Not
Y 63.5 L240 0.7 L330 90.01 Tripping
B 63.5 L120 0.7 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 63.5 L0 0.766 L90
Y 63.5 L240 0.766 L330 82.89 Tripping
B 63.5 L120 0.766 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 63.5 L0 0.775 L90 Continually
Y 63.5 L240 0.775 L330 81.93 Pickup
B 63.5 L120 0.775 L210
D Side:
Ph Voltage ( V ) Current ( A ) Impedance Status
R 63.5 L0 7.1 L90 Not
Y 63.5 L240 7.1 L330 8.94 Tripping
B 63.5 L120 7.1 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 63.5 L0 7.04 L90
Y 63.5 L240 7.04 L330 9.01 Tripping
B 63.5 L120 7.04 L210 Region

Set Time Tripping


Time
0.0 Sec 0.030 Sec

Note:86B TRIP

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
7
Report No: Schneider/P343/JSW-001

Ffail Stage-2 Check: With under Voltage


A side:
Ph Voltage ( V ) Current ( A ) Impedance Status
R 50.0 L0 0.5 L90 Not
Y 50.0 L240 0.5 L330 100.0 Tripping
B 50.0 L120 0.5 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 50.0 L0 0.61 L90
Y 50.0 L240 0.61 L330 81.96 Tripping
B 50.0 L120 0.61 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 50.0 L0 0.65 L90 Continually
Y 50.0 L240 0.65 L330 76.9 Pickup
B 50.0 L120 0.65 L210
D Side:
Ph Voltage ( V ) Current ( A ) Impedance Status
R 50.0 L0 5.6 L90 Not
Y 50.0 L240 5.6 L330 8.92 Tripping
B 50.0 L120 5.6 L210 Region

Ph Voltage ( V ) Current ( A ) Impedance Status


R 50.0 L0 5.54 L90
Y 50.0 L240 5.54 L330 9.02 Tripping
B 50.0 L120 5.54 L210 Region

Set Time Tripping


Time
0.0 Sec 0.030 Sec
Note: 86A TRIP
POLE SLIPPING:
Pole Slip Mode Generating
PSlip Za Forward 13.00 Ohm
PSlip Zb Reverse 36.00 Ohm
Lens Angle 90.00 deg

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
8
Report No: Schneider/P343/JSW-001

PSlip Timer T1 15.00 ms


PSlip Timer T2 15.00 ms
Blinder Angle 80.00 deg
PSlip Zc 8.500 Ohm
Zone1 Slip Count 1
Zone2 Slip Count 2
PSlip Reset Time 30.00 S

Voltage Relay Operated at I vector reaching the No of Slip Count Optd Time
Current and angle value:- (Sec)
35.0 ∟+0°,240°,120° 1.00 ∟+150°,30°,270° 1 0.024
35. ∟+0°,240°,120° 1.00 ∟+160°,40°,280° 2 0.024
12.10 ∟+0° 1.00 ∟+135° Continuous Rotate No trip

Zone checking:

Stage STATUS
Poleslip ZONE1 Trip Found Ok
Poleslip ZONE2 Trip Found Ok

 Pole slip Reset time -30sec Found ok (by injecting second count pole slip after 30sec
time delay)
 Inhibit of Poleslip function when External VT-1 fail condition – found ok
Note: 86C TRIP

RESIDUAL OVERVOLTAGE (95% STATOR EARTH FAULT PROTECTION)


FUNCTION (59N):
Adopted Setting:
VN>3 Status Enabled
VN>3 Function DT
VN>3 Voltage Set 7.000 V
VN>3 Time Delay 0.5 s

Checking Pickup & Trip Time Test

Expected TRIP
SET PICKUP Voltage OPEARTING TRIP
S.NO Phase TIME
Volts (VN>derived )Volts TIME ( Sec )
( Sec )

1. VN1 7.00 7.10 0.500 0.54


Note:86A TRIP
100 % STATOR EARTH FAULT FUNCTION BY 3RD HARMONICS (59TN)
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
9
Report No: Schneider/P343/JSW-001

100%St EF Status VN3H< Enabled


100% St EF VN3H< 0.500 V
VN3H< Delay 1.000 s
V< Inhibit set 85.00 V

INJECTING:

Ph Voltage ( V ) Hz
R 50.0 L0 50Hz
Y 50.0 L240 50Hz
B 50.0 L120 50Hz

SET Pick
Phase
Volts Volts Hz
VN1 0.5 0.5 150

SET TIME OPEARTING


( Sec ) TIME ( Sec )

1.000 1.04

 V<Inhibit function: Found ok


Note:86A TRIP

UNDER & OVER FREQUENCY PROTECTION (81U/O):


Settings:

Under Frequency:
F<1 Status Enabled
F<1 Setting 48.50 Hz
F<1 Time Delay 2.000 s
F<2 Status Enabled
F<2 Setting 47.50 Hz
F<2 Time Delay 1.500 s

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
10
Report No: Schneider/P343/JSW-001

Under Frequency Stage-1

PH Voltage Angle Set Pickup Set Time Pickup


(V) ( Hz ) Hz Time
R 63.5 0
50 Hz 48.5 2.0 Sec 2.14 Sec
Y 63.5 240
B 63.5 120

Under Frequency Stage-2

PH Voltage Angle Set Pickup Set Time Pickup


(V) ( Hz ) Hz Time
R 63.5 0
50 Hz 47.5 2.0 Sec 2.04 Sec
Y 63.5 240
B 63.5 120

Note:86B TRIP

Over Frequency:
F>1 Status Enabled
F>1 Setting 51.00 Hz
F>1 Time Delay 1.000 s
F>2 Status Enabled
F>2 Setting 51.50 Hz
F>2 Time Delay 1.500 s

Over Frequency Stage-1

PH Voltage Angle Set Pickup Set Time Pickup


(V) ( Hz ) Hz Time
R 63.5 0
50 Hz 51.0 1.0 Sec 1.04 Sec
Y 63.5 240
B 63.5 120

Over Frequency Stage-2

PH Voltage Angle Set Pickup Set Time Pickup


(V) ( Hz ) Hz Time
R 63.5 0
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
11
Report No: Schneider/P343/JSW-001

Y 63.5 240 50 Hz 51.5 1.5 Sec 1.54 Sec


B 63.5 120

Note:86B TRIP

NEGATIVE PHASE SEQUENCE THERMAL (46T):


Settings:
I2therm>1 Alarm Enabled
I2therm>1 Set 50.00 mA
I2therm>1 Delay 8.000 s
I2therm>2 Trip Enabled
I2therm>2 Set 70.00 mA
I2therm>2 kSet 6.000 s
I2therm>2 kRESET 6.000 s
I2therm>2 tMAX 1000 s
I2therm>2 tMIN 6.000 s

I2> pick up :
FUNCTION SET I2> PICK UP CURRENT SET TIME OPEARTING
ALARM (A) I2> ( A ) ( Sec ) TIME ( Sec )

I2> 0.051 0.051 8.0 8.07


Operating Time -

Actual
SET Injected Expected Status
S. Operating
I2> Current (A) Operating
no Time(Sec)
(A) Time(Sec)
R Y B AT K=6 AT K=6 Tripping
1. 0.07 0.5∟0° 0.5 ∟120° 0.5∟240° 24.23 24.23 Found Ok

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
12
Report No: Schneider/P343/JSW-001

2. 0.07 1 ∟0° 1 ∟120° 1 ∟-240° 6.01 6.02 Found Ok

3. 0.07 2.0∟0° 1.2 ∟120° 1.2∟-240° 1.50 1.5 Found Ok

 Reset NPS Thermal state (Measurement-3) – Done


Note:86B TRIP

Volts/Hz Protection (99):


Settings:
V/Hz Alm Status Enabled
V/Hz Alarm Set 2.310 V/Hz
V/Hz Alarm Delay 10.00 s
V/Hz>1 StatusEnabled
V/Hz>1 Trip Func DT
V/Hz>1 Trip Set 2.400 V/Hz
V/Hz>1 Delay 1.000 s
V/Hz>2 StatusDisabled
V/Hz>3 StatusDisabled
V/Hz>4 StatusDisabled
Status
Expect Operated Actual Operated
Sl.No Stage V/F Pickup V/f Injected Voltage(V)
Time(Sec) Time(Sec)

1 Stage-1 2.31 2.31 66.4V 10.00 10.03 Alarm


2 Stage-2 2.40 2.40 69.4V 1.0 1.03 Trip

Status
Injected Frequency Expect Operated Actual Operated
Sl.No Stage V/F Pickup V/f
(Hz) Time(Sec) Time(Sec)

1 Stage-1 2.31 2.31 47.6 10.00 10.03 Alarm


2 Stage-2 2.40 2.40 45.80 1.0 1.03 Trip

Note:86C TRIP

DEAD MACHINE PROTECTION (50/27):

Setting:
Dead Mach Status Enabled
DM CT Source IA-1 IB-1 IC-1
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
13
Report No: Schneider/P343/JSW-001

Dead Mach I> 950.0 mA


Dead Mach V< 80.00 V
Dead Mach tPU 1.000 s
Dead Mach tDO 500.0 ms

Dead Machine Pickup Voltage (V<) - 80.0 Volts (P-P)

Pickup Current & Timing


Applied
Voltage
Operated Operated Operated
(Ph-Ph) A-Ph(A) B-Ph(A) C-ph(A)
time(sec) time(Sec) time(Sec)

45.0 0.95 0.038 0.95 0.038 0.95 0.038

 Operation Of Dead Mach tPU – 1.00Sec Found ok


 Operation Of Dead Mach tDO – 0.50Sec Found ok
Note:86A TRIP
UNDER VOLTAGE PROTECTION (50/27):
Settings:
V< Measur't Mode Phase-Phase
V< Operate Mode Any Phase
V<1 Function DT
V<1 Voltage Set 99.00 V
V<1 Time Delay 5.000 s
V<1 Poledead Inh Enabled
V<2 Status Enabled
V<2 Voltage Set 88.00 V
V<2 Time Delay 0s
V<2 Poledead Inh Enabled
Stage -1:
PH Voltage Set Voltage Pickup Voltage Set Time Pickup Time
(V)
R 63.5
57.159 V 57.06 V 5.0 Sec 5.04 Sec
Y 63.5

B 63.5

Note:86C TRIP

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
14
Report No: Schneider/P343/JSW-001

Stage -2:

PH Voltage Set Voltage Pickup Voltage Set Time Pickup Time


(V)
R 63.5
50.8 V 50.72 V 0 Sec 0.03 Sec
Y 63.5

B 63.5

Note: R-Y Voltage decrees then relay should operated


B-R Voltage decrees then relay should operated
Breaker status also enabled

OVER VOLTAGE PROTECTION (50/27):


Settings:
V> Measur't Mode Phase-Phase
V> Operate Mode Any Phase
V>1 Function DT
V>1 Voltage Set 121.00 V
V>1 Time Delay 0.500 s
V>1 Poledead Inh Enabled
V>2 Status Enabled
V>2 Voltage Set 126.00 V
V>2 Time Delay 2.00 s
V>2 Poledead Inh Enabled
Stage -1:
PH Voltage Set Voltage Pickup Voltage Set Time Pickup Time
(V)
R 63.5
69.86 V 69.8 V 0.5 Sec 0.504 Sec
Y 63.5

B 63.5

Stage -2:
PH Voltage Set Voltage Pickup Voltage Set Time Pickup Time
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
15
Report No: Schneider/P343/JSW-001

(V)
R 63.5
72.74 V 72.16 V 2.0 Sec 2.04 Sec
Y 63.5

B 63.5

Note: R-Y Voltage ingress then relay should operated


B-R Voltage ingress then relay should operated
Note:86C TRIP
FUSEFAIL SUPERVISION (60):
Settings:
VTS Status Blocking
VTS Reset Mode Auto
VTS Time Delay 5.000 s
VTS I> Inhibit12.50 A
VTS I2> Inhibit 250.0 mA
SET TIME OPEARTING
S.NO Phase
Volts ( Sec ) TIME ( Sec )
R 0
1. Y 63.5 5.00 5.01
B 63.5
 VTS I> INHIBIT FUNC FOUND : OK
 VTS I2> INHIBIT FUNC FOUND : OK
CB FAIL & I< Function (50BF):
Settings:
CB Fail 1 Status Enabled
CB Fail 1 Timer 200.0 ms
CB Fail 2 Status Disabled
CBF Non I Reset CB Open & I<
CBF Ext Reset CB Open & I<
UNDER CURRENT
I< Current Set 100.0 mA
IN< Current Set 100.0 mA
ISEF< Current1.000 mA
I< CT Source IA-2 IB-2 IC-2

a) Actual Operated time of CB fail in case of fault persist : 0.248sec


b) Initiation from 86A, 86B, 86C, relay
Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
16
Report No: Schneider/P343/JSW-001

and LBB operation trip Found : Found OK


c) Non trip of CB fail(LBB) when Under current condition(I<0.1A&IN<0.1A) :Found
Ok

Voltage Restrained OC Method


Setting:
Backup Function Volt restrained
Vector Rotation None
V Dep OC Char IEC S Inverse
V Dep OC I> Set 1.000 A
V Dep OC TMS 25.00e-3
V Dep OC tRESET 0 s
V Dep OC V<1 Set 80.00 V
V Dep OC V<2 Set 60.00 V
V Dep OC k Set 250.0e-3

Pick Up & Timing Test


Signature TEST FORMAT OF GENERATOR PROTECTION RELAY
Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
17
Report No: Schneider/P343/JSW-001

PickUp Voltage (V) Injected Current (A) Expected Actual


Expected Actual
Operating Operating Remarks
Stage Stage
R Y B R Y B Time(Sec) Time(Sec)

51.96 51.96 51.96 1.0 1.0 1.0 V>VS1 V>VS1 Blocking Blocking Found ok

51.96 51.96 51.96 1.1 1.1 1.1 V>VS1 V>VS1 1.83 1.77 Found ok

51.96 51.96 51.96 2.0 2.0 2.0 V>VS1 V>VS1 0.25 0.26 Found ok

46.18 46.18 46.18 1.1 1.1 1.1 V>VS1 V>VS1 1.83 1.72 Found ok

46.18 46.18 46.18 2.0 2.0 2.0 V>VS1 V>VS1 0.25 0.25 Found ok

VS2 <V VS2 <V


40.41 40.41 40.41 0.625 0.625 0.625 Blocking Blocking Found ok
<VS1 <VS1

VS2 <V VS2 <V


40.41 40.41 40.41 0.70 0.70 0.70 1.542 1.55 Found ok
<VS1 <VS1

28.86 28.86 28.86 0.25 0.25 0.25 V <VS2 V <VS2 Blocking Blocking Found ok

28.86 28.86 28.86 0.3 0.3 0.3 V <VS2 V <VS2 0.958 0.955 Found ok

34.64 34.64 34.64 0.3 0.3 0.3 V <VS2 V <VS2 0.958 1.05 Found ok

Note:86A TRIP

ROTOR EARTH FAULT TEST :


Injection Frequency: 0.25HZ
64R<1 Alarm : 40.0Kohm
64R<1 Delay : 10.0Secs
64R<1 Trip : 5.0Kohm
64R<1 Delay : 0.0Secs
R Compensation : 0Ohm

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
18
Report No: Schneider/P343/JSW-001

Injected Resistance Measured


Resistance
in Relay
50.0Kohm 50.98Kohm
40.0Kohm 40.51Kohm
4.88Kohm 20.22Kohm
Note:86A TRIP

P391 ROTOR EARTH FAULT DETECTOR

CALIBRATION & TEST REPORT

Customer : M/s IOCL Vadodara Date: 29.12.2011


Model No: P3919P00A Aux. Voltage: 110 - 220 V DC
Serial No: 31761680/05/11 Rated Current: 1A

Calibration Connection Diagram :

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
19
Report No: Schneider/P343/JSW-001

Measured “64 R Fault “ & Chosen the R Compensation accordingly.


Actual Measurement in the relay is 382ohm to Compensate this “ R
Compensation “Setting is made as 118Ohm. So that the measurement is
500 Ohm.

Testing of P343 using P391 injection unit for Rotor Earth Fault

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
20
Report No: Schneider/P343/JSW-001

ROTOR EARTH FAULT TEST :


Injection Frequency: 0.25HZ
64R<1 Alarm : 40.0Kohm
64R<1 Delay : 10.0Secs
64R<1 Trip : 5.0Kohm
64R<1 Delay : 0.0Secs
R Compensation : 0Ohm

Side Injected Measured

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION


001
21
Report No: Schneider/P343/JSW-001

Resistance Resistance
in Relay
A 500 Ohms 550ohm
B 500 Ohms 550ohm
A&B 1000 Ohms 1050ohm

Dead short: 60 Ohms


1050 Ohms measured in Relay and amps 20 ma

Signature TEST FORMAT OF GENERATOR PROTECTION RELAY


Tested By JSW STEEL LTD,BELLARY
Witnessed By Customer
KARNATAKA
Witnessed By GPR-M Schneider Electrical Limited.

Report No: Schneider/P343/JSW- ENERGY AUTOMATION & INFORMATION