DATA
SHORT CIRCUIT ANALYSIS 2
GRID LINE UTILITY IMPEDANCE:
(WITH TRANSFORMER IN THE VICINITY) 34.5 KV GRID LINE
ASSUME SC = 1000 MVA D. TOTAL IMPEDANCE
KVA BASE 75 KVA
ZU = =
KVA SC KVA 1000000 KVA ZCOMBINE = ZU + ZT + ZDL + Zse
A. SYSTEM DIAGRAM
ZU = 0.000075 Ω
ZCOMBINE = 0.000075 + 0.044 + 0.007419 + 0.007901
TRANSFORMER IMPEDANCE:
75 AMPS 22.62 FT
MAIN
XDL = 0.00317 x = 0.00717 Ω
15 AMPS 15 AMPS
100 FT
L.O. 1 2 L.O.
F. USE OTHER TRANSFORMER
20 AMPS 20 AMPS
FAULT ZDL = (0.001909)² + (0.00717)² ASSUME POLE MOUNTED DT = 75KVA SINGLE PHASE TRANSFORMER
C.O.
4 %Z = 1.2 % (CU-CU WINDING ANSI/IEEE STANDARD)
20 AMPS 60 AMPS
Zse = 0.007901 Ω
SCHOOL: PROJECT TITLE: PREPARED BY: PRC REGISTRATION: APPROVED BY: SEAL: SHEET CONTENT: SHEET NO.