SERVICE ENTRANCE SHORT CIRCUIT CALCULATION

CONDUCTOR
@ 300KVA TRANSFORMER, 3PHASE, 400V, 60HZ
THREE (3) PHASE LOAD CURRENT
I. Derived from Equation of Full Load Current @
I W = (1.732*36)+(19*0.80)+12.5
150KVA Transformer, 3Phase, 380V, 60Hz @ %Z=4.0
I W = 90.05 AMP.

Eq. 1. 3Ø Transformer: KVA X 1000


SERVICE EQUIPMENT I FL =
E L-L x 1.732
THREE (3) PHASE LOAD CURRENT
150KVA X 1000
I FL =
IP = I W +125% (LARGEST LOAD CURRENT) 400 V X 1.732
IP = 90.05 AMP. + 125% (12.5 AMP.) I FL = 216.51 A

IP = 105.67 AMP. 100 100


Multiplier = =M=
%ZTransformer 4.0
MAIN : 250AT/250AF, 400V, 3P, 10KAIC M = 25.00
USE: 4 SETS OF 4-80MM² THHN &
1-14MM² THHN (GW) IN 65MMØ RSC PIPE
ISC = I FLA x M
ISC= 216.51 A X 25.00
VOLTAGE DROP ISC = 5412.75 Amp

TOTAL CURRENT = 90.05 AMP. Eq. 2. Motor Contribution:


WIRE SIZE = 80mm2 THHN / THW WIRE
I MC = 4 x I FLA
LENGTH OF WIRE = 40meters
IMC = 4 x 36 A
CALCULATE; I MC = 144 Amp
1. Voltage Drop @ Service MAIN ENTRANCE PERCENT VOLTAGE DROP
VDSE Eq. 3. Short Circuit Symmetrical Current / Fault
(1.732) x ( L ) x ( I ) x R2+ X 2 VD % = x 100%
VDSE = VL I
305 x ( N ) SCSYMRMS = ISC+ I MC
0.45V = 5,412.75 Amp + 144 Amp
VD % = x 100%
(1.732) x ( 40 ) x ( 90.05 ) x 0.079 + 0.042 2 2 400 V
VDSE
= = 5556.75 Amp
305 x ( 4) VD % = 0.11 %
USE: 10KAIC , 250AT/250AF, 400V, 3P,
SE
VD = 0.45 V

E4 DESIGN ANALYSIS, VOLTAGE DROP AND SHORT CIRCUIT ANALYSIS


01 SCALE NTS

FROM THE OFFICE OF: NO. SEAL PROJECT TITLE APPROVED PER PLAN AND SPECIFICATIONS CAD BY: SHEET CONTENT: SHEET NO
PRC REG. SINGLE PHASE TRANSFORMER
INSTALLATION
VALIDITY
PTR
NO. AS BUILT PLAN FOR VROSS CORPORATION SATUR M. CADENAS E
PROFESSIONAL ELECTRICAL ENGINEER DATE
OWNER 46
PLACE
TN
NO. LOCATION:BRGY.10,CABADBARAN CITY AGUSAN DEL NORTE ADDRESS: BRGY.10,CABADBARAN CITY AGUSAN DEL NORTE

You might also like