SINGLE LINE DIAGRAM

UTILITY

TRANSFORMER

F0 SUMMARY
X
BASED ON THE CALCULATIONS, THE MINIMUM INTERRUPTING CAPACITY
MDP OF DIFFERENT PANEL BOARDS ARE AS FOLLOWS:

PANEL FAULT COMPUTED VALUE INDUSTRY VALUE


MDP F0 7759.93 A 10KAIC
PB01 F1 5870.83 A 10KAIC
PB02 F2 5525.08 A 10KAIC
F1 F2
X X

PB01 PB02

MOTOR CONTRIBUTION

Assume 50% motor load based


on the transformer rating.

IFL, 3 - 25 KVA Transformer = (3 x 25)KVA


(1.732 x 0.23)KV

= 188.27

50% of IFL = 188.27 / 2 = 94.13 A

I(asym) = 5 x 94.13 = 470.67 A

I(sym) = I(asym) / 1.25 = 376.53 A

JOSEPH FREEMAN E. DIAZ, PEE


PRC LICENSE NO.
PTR NO.
DATE ISSUED:
PLACE ISSUED:
KVA BASE = 85000
KV BASE = 0.230
IMPEDANCE DIAGRAM -1 PUR PUX

UTILITY
85000 KVA SC X= 85000 1.00
13.2 KV, SOURCCE 85000

TRANSFORMER R= (0.9)(85000) 10.20


Z%= 2% (100)(75)
Z%= 0.9 + j 1.8 %
D.T.= 3 - 25 KVA X= (1.8)(85000) 20.40
SOURCE V= 13.2 / 0.230 KV (100)(75)

MDP
#4/0 WIRE= 3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90
LENGTH 15 M (1000)(0.23)^2
Z= 0.062 + j 0.041 OHMS/1000FT
X= (1)(0.041x15/305)(85000) 3.24
F0 (1000)(0.23)^2

X TOTAL P.U. @ F0 15.10 24.64

FAULT @ F0

ZU

ZT

ZC

M
Motor
Contribution

TOTAL P.U. ZF0 = √(15.1)^2 + (24.64)^2


TOTAL P.U. ZF0 = 28.90

IF0 = 85000
+ 376.53 A
28.90 X 1.732 X 0.23

IF0 = 7,759.93 A
KVA BASE = 85000
KV BASE = 0.230
IMPEDANCE DIAGRAM -2 PUR PUX

UTILITY
85000 KVA SC X= 85000 1.00
13.2 KV, SOURCCE 85000

TRANSFORMER R= (0.9)(85000) 10.20


Z%= 2% (100)(75)
Z%= 0.9 + j 1.8
D.T.= 3 - 25 KVA X= (1.8)(85000) 20.40
Supply V= 13.2 / 0.230 KV (100)(75)

MDP
WIRE= 3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90
LENGTH 15 M (1000)(0.23)^2
Z= 0.062 + j 0.041 OHMS/1000FT
X= (1)(0.041x15/305)(85000) 3.24
(1000)(0.23)^2
F0
X TOTAL P.U. @ F0 15.10 24.64

PB01
WIRE= 3 - 60 sq.mm. R= (1)(0.1x20/305)(85000) 10.54
LENGTH 20 M (1000)(0.23)^2
Z= 0.1 + j 0.043 OHMS/1000FT
X= (1)(0.043x20/305)(85000) 4.53
(1000)(0.23)^2

F1
X TOTAL P.U. @ F1 25.64 29.17

FAULT @ F1

ZU

ZT

ZC

M
Motor
Contribution

TOTAL P.U. ZF1 = √(25.64)^2 + (29.17)^2


TOTAL P.U. ZF1 = 38.83

IF1 = 85000
+ 376.53 A
38.83 X 1.732 X 0.23

IF1 = 5,870.83 A
KVA BASE = 85000
KV BASE = 0.230
IMPEDANCE DIAGRAM -3 PUR PUX

UTILITY UTILITY
85000 KVA SC X= 85000 1.00 85000
13.2 KV, SOURCCE 85000 13.2

TRANSFORMER R= (0.9)(85000) 10.20 TRANSFORMER


Z%= 2% (100)(75) Z%=
Z%= 0.9 + j 1.8 Z%=
D.T.= 3 - 25 KVA X= (1.8)(85000) 20.40 D.T.=
Supply V= 13.2 / 0.230 KV (100)(75) Supply V=

MDP MDP
WIRE= 3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90 WIRE=
LENGTH 15 M (1000)(0.23)^2 LENGTH
Z= 0.062 + j 0.041 OHMS/1000FT Z=
X= (1)(0.041x15/305)(85000) 3.24
(1000)(0.23)^2
F0
X TOTAL P.U. @ F0 15.10 24.64

PB02 PB02
WIRE= 3 - 60 sq.mm. R= (1)(0.1x25/305)(85000) 13.17 WIRE=
LENGTH 25 M (1000)(0.23)^2 LENGTH
Z= 0.1 + j 0.043 OHMS/1000FT Z=
X= (1)(0.043x25/305)(85000) 5.66
(1000)(0.23)^2

F2
X TOTAL P.U. @ F2 28.27 30.30

FAULT @ F2

ZU

ZT

ZC

M
Motor
Contribution

TOTAL P.U. ZF2 = √(28.27)^2 + (30.3)^2


TOTAL P.U. ZF2 = 41.44

IF2 = 85000
+ 376.53 A
41.44 X 1.732 X 0.23

IF2 = 5,525.08 A
KVA BASE = 85000
KV BASE = 0.230
IMPEDANCE DIAGRAM -4 PUR PUX

KVA SC X= 85000 1.00


KV, SOURCCE 85000

TRANSFORMER R= (0.9)(85000) 10.20


2% (100)(75)
0.9 +j 1.8
3 - 25 KVA X= (1.8)(85000) 20.40
13.2 / 0.230 KV (100)(75)

3 - 100 sq.mm. R= (1)(0.062x15/305)(85000) 4.90


15 M (1000)(0.23)^2
0.062 +j 0.041 OHMS/1000FT
X= (1)(0.041x15/305)(85000) 3.24
(1000)(0.23)^2
F0
X TOTAL P.U. @15.10
F0 24.64

3 - 60 sq.mm. R= (1)(0.1x25/305)(85000) 13.17


25 M (1000)(0.23)^2
0.1 +j 0.043 OHMS/1000FT
X= (1)(0.043x25/305)(85000) 5.66
(1000)(0.23)^2

F2
X TOTAL P.U. @28.27
F2 30.30

FAULT @ F2

ZU

ZT

ZC

M
Motor
Contributi
on

TOTAL P.U. ZF2 = √(28.27)^2 + (30.3)^2


TOTAL P.U. ZF2 = 41.44

IF2 = 85000
+ 0.00 A
41.44 X 1.732 X 0.23

IF2 = 5,148.55 A