You are on page 1of 2

Amps X 100 Bus179-2 (Nom. kV=0.48, Plot Ref. kV=0.

48)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500 MS-13.1A


4.16 kV
300 300

F52-TML 13.1A 400/5 R


2 MVA (Secondary) 6.84 %Z
Delta-Wye Solid Grd
100 100 MS13.1A- FPR1
F52-PC13.1 A CB
ABB Ekip Touch LSIG
Sensor = 3200
50 I1 = 0.94 (3008 Amps)
Trip Time@3I1 = 6 t1 = t=k/I^2 MS13.1A- FPR1 - P
50 MS13.1 F2 CB
I2 = 2.4 (7680 Amps) OC1
Trip Time = 0.73 t2 = t=k ABB
30 REF 615 30
CT Ratio 400:5 o
ANSI Extremely Inverse
Pickup = 0.9 (0.05 - 5 xCT Sec)
Time Dial = 5.3 50/5
3x = 19.3 s, 5x = 6.87 s, 8x = 3.02 s
Inst = 16 (1 - 40 xCT Sec)
Time Delay = 0.02 s
10 10

5 5
Seconds

Seconds
3 3

F52-TML 13.1A
2 MVA
1 1

.5 .5

.3 .3

R F52PC13.1 A 51
.1 .1 3200/1
F52-TML 13.1A
Inrush
Multiplier = 12 xFLA (28867.52 Amps)
.05 Duration = 6 Cycles .05
F52-PC13.1 A CB

.03 .03
F52-PC13.1 BUSA
0.48 kV

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 Bus179-2 (Nom. kV=0.48, Plot Ref. kV=0.48) ETAP Star 16.0.0C

MS 13.1 TO PC 13.1

Project: PETRO RABIGH COMPLEX Date: 03-26-2018


Location: RABIGH, KSA Rev: Base
Engineer: ABDUL HAKKEEM Fault: Phase
TYPICAL FOR: MS-13.1B TO PC13.1 BUSB; MS-13.1E TO
Amps Bus179-2 (Nom. kV=0.48, Plot Ref. kV=0.48)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500 MS-13.1A


4.16 kV
300 300

F52-PC13.1 A CB
400/5 R
ABB Ekip Touch LSIG
100 Sensor = 3200 100
I4 = 0.38 (1200 Amps) MS13.1A- FPR1
Trip Time = 1 t4 = t=k

50 50 MS13.1 F2 CB

30 30
o

50/5

10 10

5 5
Seconds

Seconds
3 3

F52-TML 13.1A
2 MVA
1 1

.5 .5
MS13.1A- FPR1 - G
OC1
.3 ABB .3
REF 615
CT Ratio 50:5
ANSI Definite Time
Pickup = 0.4 (0.01 - 5 xCT Sec)
o
Time Dial = 0.1
3x = 0.1 s, 5x = 0.1 s, 8x = 0.1 s
R F52PC13.1 A 51
.1 .1 3200/1

.05 .05
F52-PC13.1 A CB

.03 .03
F52-PC13.1 BUSA
0.48 kV

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps Bus179-2 (Nom. kV=0.48, Plot Ref. kV=0.48) ETAP Star 16.0.0C

MS 13.1 TO PC 13.1

Project: PETRO RABIGH COMPLEX Date: 03-26-2018


Location: RABIGH, KSA Rev: Base
Engineer: ABDUL HAKKEEM Fault: Ground
TYPICAL FOR: MS-13.1B TO PC13.1 BUSB; MS-13.1E TO