You are on page 1of 1

Amps X 100 TD-3900A AB1 (Nom. kV=4.16, Plot Ref. kV=4.

16)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
CFMT-02 3200A
Ampacity
500 500
CFMT-01 3200A
300
Ampacity 300
Relay3 - P
PA-3200A-Untitled OC1
600 HP Schweitzer
100
751A 100
CT Ratio 150:5
C3 - IEC Cls C Ext. Inverse
50 Pickup = 3.1 (0.5 - 16 Sec - 5A) 50
Time Dial = 1
30 3x = 10 s, 5x = 3.33 s, 8x = 1.27 s 30
Inst = 82.54 (0.5 - 96 Sec - 5A)
Time Delay = 0.02 s o

OCR Relay3

Cont1

10 10 Fuse1 TD3900A

CFMT-01 3200A - P
3 - 1/C 4/0 AWG CFMT‐01 3200A

3‐1/C 4/0

5 Copper EPR 5

Seconds
Seconds

Tc = 90C
3 Plotted - 1 x 4/0 AWG 3 VFD1

CFMT‐02 3200A

3‐1/C 4/0

1 1
CFMT-02 3200A - P
3 - 1/C 4/0 AWG PA‐3200A
.5 Fuse1 TD3900A .5 600 HP

Copper EPR
Bussmann Tc = 90C
.3 JCL (61/64) .3
Plotted - 1 x 4/0 AWG
Standard 5.08 kV
3R
Cont1
.1 .1
Interrupting current 10 kA
Dropout time 0.133 s
.05 .05
Fuse1 TD3900A - 3P
.03 .03

Relay3 - 3P

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 TD-3900A AB1 (Nom. kV=4.16, Plot Ref. kV=4.16) ETAP Star 19.0.1C

Star21

Project: Date: 12-16-2020


Location: SN:
Contract: Rev: Base
Engineer: Fault: Phase
Filename: D:\LAP TOP HP GRIS\ETAP 1901\AKAL-B\AKAL-B.OTI