You are on page 1of 1

Amps X 100 BUS-SF-LV1 (Nom. kV=0.415, Plot Ref. kV=0.

433)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

300 300 SF-LV-1Q


SF-LV-1Q
Merlin Gerin STR 38S
Sensor = 2500 Plug = 0.8X
LT Pickup = 1 (2000 Amps)
100 LT Band = Fixed 100
ST Pickup = 2 (4000 Amps)
ST Band = 0.2 (I^x)t = IN
50 Inst. Pickup = Fixed (35000 Amps) 50

SF-LV-1Q1
30
Merlin Gerin
30
BUS-SF-LV1
NS250-D
Size = 200 Amps
Thermal Trip = 100%
10 Magnetic Trip = 8X 10

5 5
SF-LV-1Q1
Seconds

Seconds
3 3

Cable8 - P
1 - 4/C 95 mm²
Copper XLPE
1 Tc = 90C 1
Plotted - 1 x 95 mm²

.5 .5
Cable8
.3 .3
1-4/C 95

.1 .1

SF-LV-1Q - 3P
.05 41.195kA @ 0.433kV .05
(Sym)
.03 .03
SF-LV-1Q1 - 3P
Kiln 2 Bus Arcing Current, Ia
7.354kA @ 0.415kV
41.195kA @ 0.433kV
(Sym) SW4
.01 .01 BUS-SF-LV-Kilns2
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K