JAM 27/01/15: Con Comentarios

CUSTOMER ABB CHILE


PURCHASE ORDER REF. 063-87501 DATED 6 JAN 15
CONTROL VOLTAGE 125 VDC
Tensión Motor debe ser 125
SPRING CHARGE MOTOR 230 VAC VDC
HEATER VOLTAGE 230 VAC
ABB ORDER REF 5000033109

SCHEMATIC DRG.NO. YN1V300013-EBM


GENERAL ARRANGEMENT DRAWING YN1V300015-DKS
RATING PLATE YN1V300303-725
LAYOUT OF ELECTRICAL COMPONENT YN1V300015-HAU

Breaker Quantity : 1 No.


COVER SHEET FOR GK COVER SHEET
36 kV OUTDOOR SF6 NB
YN1V300015-JHS
CIRCUIT BREAKER TYPE OHB BU PTMVE 12 19
LEGEND
B5-41 R
SF6 CIRCUIT BREAKER IND. BREAKER ON (R-RED)
B5-42 G
IND. BREAKER OFF (G- GREEN)
B5-43 B
IND. SPRING CHARGED (B-BLUE)
CLOSING COIL (CC) F01-01:1
B5-44 B
TRIPPING COIL1 (TC1) F01-01:2 GAS PRESSURE LOW (A-AMBER)
TRIPPING COIL2 (TC2) F01-01:3
G1-12
NC CONTACT ILLUMINATING LAMP
NO CONTACT B10-16
B10-01 (FOR MOTOR) TN C
MCB B10-02 (FOR CONTROL CIRCUIT)
B10-03 (CB ACCESSORIES)
A2-01 (FOR HEATER)
A2-02 (FOR SOCKET)
BREAKER CONTROL SWITCH

M SPRING DRIVE MOTOR


F01-01:4
B10-15
B10-04 L R
THERMOSTAT

F10-01,02
LOCAL REMOTE SEL.SWITCH with key
HEATER

B10-39
PUSH BUTTON WITH 4NO CONTACTS
B10-14/B10-17 B10-14 - GAS PRESSURE LOW ALARM RELAY
B10-17 - GAS PRESSURE LOW TRIP RELAY
A2-03
DOOR LIMIT SWITCH
B10-13/B10-18/B10-19/B10-20 B10-13 - ANTIPUMPING RELAY
B10-18 - SPRING CHARGED CONTACT MULTIPLIER
A3-01 B10-19 - AUXILIARY RELAY
SOCKET B10-20 - AUXILARY REALY
TERMINAL SYMBOL:

TERMINAL OF APPARATUS.
TERMINAL BLOCK IN CONTROL BOX.
TERMINAL BLOCK FOR CUSTOMER CONNECTIONS

GK
OUTDOOR SF6 CIRCUIT LEGEND
NB 1
BREAKER TYPE OHB YN1V300013-EBM 2
BU PTMVE 12 19
TOTAL
LEGEND /DESIGNATION/ITEM NAME LOCATION DESCRIPTION MAKE QUANTITY/BREAKER
SHT NO.

OHB CIRCUIT F01-01 4- 2/C OUTDOOR SF6 CIRCUIT BREAKER TYPE OHB 36.25.32 ABB 01 NO.
BREAKER

CLOSING COIL(CC) F10-01:1 4- 2/C CLOSING COIL,110 VDC RATED VOLTAGE,180W WATTAGE ABB 01 NO.
TRIP COIL1(TC1) F10-01:2 4- 4/C TRIPPING COIL 1, 110 VDC RATED VOLTAGE,180W WATTAGE ABB 01 NO.
TRIP COIL2(TC2) F10-01:3 4- 5/C TRIPPING COIL 2, 110 VDC RATED VOLTAGE,180W WATTAGE ABB 01 NO.
B10-01 6- 5/B MCB FOR SPRING CHARGING MOTOR,1 POLE & N ,4A ABB /EQUIV. 01 NO.
MCB
B10-02 4- 1/A,1/D MCB FOR CONTROL CIRCUIT,2 POLE,10A ABB / EQUIV. 01 NO.
B10-03 6- 2/A,2/C MCB FOR CB ACESSORIES,1 POLE & NEUTRAL,10A ABB /EQUIV. 01 NO.

B10-04
THERMOSTAT 6- 3/B THERMOSTAT,RTR-E 6708,10-60 CENTIGRADE. EBERLE/EQUIV. 01 NO.

F10-01,02
SPACE HEATER,70W,230 VAC 02 NOS.
HEATER 6- 3/C HORN/EQUIV.

B10-39 5- 1/C 01 NO.


PUSH BUTTON PUSH BUTTON FOR LAMP TESTING TEKNIC /EQUIV.
WITH 4NO CONTACTS 5- 2/C

A2-01 6- 3/A MCB FOR HEATER CIRCUIT, 1POLE & NEUTRAL,2A ABB /EQUIV. 01 NO.
MCB
A2-02 6- 3/A MCB FOR SOCKET CIRCUIT, 1POLE & NEUTRAL,2A ABB /EQUIV. 01 NO.

DOOR LIMIT SWITCH


A2-03 6- 3/A DOOR LIMIT SWITCH FOR LAMP,15A,230 VAC KAYCEE /EQUIV. 01 NO.

G1-12
6- 4/C ANCHOR/ EQUIV. 01 NO.
LAMP LAMP,11W,230 VAC ,CFL

SOCKET 6- 4/C 3 PIN SOCKET,15A,230 VAC 01 NO.


ABB / EQUIV.
A3-01

GK
OUTDOOR SF6 CIRCUIT BILL OF MATERIAL-1 2
NB
BREAKER TYPE OHB
BU PTMVE 12 19
YN1V300013-EBM 3
LOCATION TOTAL
LEGEND/DESIGNATION/ITEM NAME DESCRIPTION MAKE
SHEET NO QUANTITY/BREAKER
B10-13 ANTIPUMPING RELAY 4- 3/D RELAY WITH BASE FOR
ABB /EQUIV. 01 NO.
PLUG IN RELAY AUX VOLTAGE,

B5-41 R IND. BREAKER ON 5- 1/C 2PLBR4L, LED INDICATING LAMP TEKNIC 01 NO.
RED COLOUR LENS
B5-42 G IND. BREAKER OFF 5- 2/C 2PLBR4L, LED INDICATING LAMP TEKNIC 01 NO.
GREEN COLOUR LENS

B5-43 B SPRING CHARGED 5- 2/C 2PLBR4L, LED INDICATING LAMP TEKNIC 01 NO.
BLUE COLOUR LENS
B5-44 A GAS PR.LOW 5- 2/C 2PLBR4L, LED INDICATING LAMP TEKNIC 01 NO.
AMBER COLOUR LENS

B10-16
T NC
BREAKER CONTROL SWITCH 4- 2/A,4/B BREAKER CONTROL SWITCH
LABEL.TRIP-NEUTRAL-CLOSE SWITRON / BACO 01 NO.
3 POSITIONS,4 WAYS,SPRING RETURN TO NEUTRAL
ANGULAR MOVEMENT 45+45 DEG.
2 CONTACTS IN EACH POSITION

B10-15
L R LOCAL REMOTE SEL.SWITCH WITH KEY
LOCAL REMOTE SEL.SWITCH 4- 2/A,3/A,4/A LABEL LOCAL -REMOTE
2 POSITIONS,6 WAYS,STAYPUT, LOCKABLE, SWITRON/BACO 01 NO.
WING TYPE HANDLE, ANGULAR MOVEMENT 90 DEG.
3 CONTACTS IN LOCAL POSITION
& 3 CONTACTS IN REMOTE POSITION

B10-14/17 GAS PR.LOW ALARM RELAY 4-5/D,5/D RELAY WITH BASE FOR 01 NO.
ABB / EQUIV.
GAS PR. LOW TRIP RELAY 4-5/D,5/D PLUG IN RELAY AUX VOLTAGE, ABB / EQUIV. 01 NO.
B10-18 RELAY 5- 3/C RELAY WITH BASE FOR ABB / EQUIV. 01 NO.
PLUG IN RELAY AUX VOLTAGE 01 NO.
B10-19 /B10-20 RELAY 5- 4/C ABB / EQUIV.

F01-01:4 6-4/C,5C SPRING CHARGING MOTOR,230 VAC,200W AT RATED VOLTAGE WUXI / MESS/EQUIV. 01 NO.

OUTDOOR SF6 CIRCUIT


GK
BILL OF MATERIAL-2
NB 3
BREAKER TYPE OHB YN1V300013-EBM
BU PTMVE 12 19 4
J1
B10-02,10A
DC-MCB K1 LOCAL CLOSE REMOTE CLOSE LOCAL TRIP REMOTE TRIP (+VE BUS) (TO SHEET NO.5)
151

B10-15 1 B10-15 2 B10-15 3 B10-15 4


LOCAL L L LOCAL L LOCAL L
LOCAL
REMOTE SEL. R REMOTE SEL. R REMOTE R REMOTE R
SWITCH A SWITCH B SWITCH C SWITCH D
K3 K5 K13 REMOTE
TNC SWITCH K19 168
1P1 171 TRIP CONT.
B10-16 T FOR REMOTE
BREAKER N CLOSE 153 154
172
CONTROL C
SWITCH 1P2 1P3 156
B10-16
K55 T 6 B10-17
BREAKER N REMOTE
CONTROL GAS PRESSURE
12 C FAULT TRIP 10 LOW TRIP
SWITCH
125 vDC B10-14
1P4 REMOTE 157
TRIP COIL REMOTE
4 K7 CONTINUITY TRIP COIL
SUPERVISION CONTINUITY SF6 GAS PRESSURE
12 11 SUPERVISION
155 NORMAL GAS PRESSURE : 3.8 bar
B10-13 158
B10-13 167 GAS PRESSURE LOW ALARM : 3.1 bar
4 7 K211 K211
K17 GAS PRESSURE LOW TRIP : 2.8 bar
110 VDC K9 K11 K21 K23

F01-01 101 117 103 112 O 107 113


5 3 11
NO CONTACT NO CONTACT
NC CONTACT AUX.SWITCH AUX.SWITCH
AUX.SWITCH 4 41 12
6 43
17 K9A NC CONTACT K21A
AUX.SWITCH L1 L2 L3 L1 L2 L3
CB POWER NO CONTACT 42 13 NC CONTACT
CONTACTS AUX.SWITCH NO CONTACT 9 AUX.SWITCH 44
NO CONTACT 11 11 11 11 11 11
18 AUX.SWITCH AUX.SWITCH
30 (1) 10 14
SPRING CHARGE 33 12 12 12
LS CONTACT 29 12 12 12
31 (4) 165 166
PRESSURE SWITCH PRESSURE SWITCH
K11 CONTACTS CONTACTS

YC
YO1 (29) YO2 (33)

102 118 104 108 114 111


A1 K25 A1 K27 A1
B10-13 B10-14
B10-02,10A B10-17
DC-MCB A2 A2 A2
J2 K2 (TO SHEET NO.5)
152 GAS PRESSURE GAS PRESSURE
ANTI PUMPING RELAY &
CLOSING CIRCUIT
TRIP COIL 1 TRIP COIL 2
(-VE BUS) LOW ALARM RELAY
LEVEL-1
LOW TRIP RELAY
LEVEL-2

Design checked by
GK
OUTDOOR SF6 CIRCUIT Drawing checked by CIRCUIT BREAKER OPERATION Rev Sheet
4
NB
BREAKER TYPE OHB Drawn by Iss by Dept Year Week YN1V300013-EBM Cont.Sh
Rev Revision Appd Year Week BU PTMVE 12 19 5
(FROM SHEET NO.4) K1 (+VE BUS)

SPARE CONTACT OF BREAKER AUXILLARY SWITCH ( 9NC + 6 NO)

119 115 109 177 121 123 127 129 131 133 135 137 139 141 143 145 147 181 173 175

K101 K41 K1 U63 U67 U71 U75 U79 U83 U87 U105 U109 U113 U117 U121 U125

11 11 7
B10-18 B10-14 S33M
19 1 SPRING CHARGE 7 15 21 23 25 27 29 31 33 35 37 39 45 47 49 51
7 7 8 LIMITSWITCH CONTACT

20 2 8 16 22 24 26 28 30 32 34 36 38 40 46 48 50 52

K103 K43 K100 U65 U69 U73 U77 U81 U85 U89 U107 U111 U115 U119 U123 U127

120 116 110 178


B10-39 144 146
122 124 128 130 132 134 136 138 140 142 148 182 174 176
K139
K33 K35 K37 K45
B10-19 Relay Spare Contacts 4 NO B10-20 Relay Spare Contacts 4 NC
B10-18 B10-20
B10-19 187
B5-41 B5-42 B5-43 B5-44 K241 5 9 K243 188 195 K257 1 9 K259 196
RELAY RELAY
R G B A 189 K245 6 10 K247 190 197 K261 2 10 K263 198
(FROM SHEET NO.4) (-VE BUS) 191 K249 7 11 K251 192 199 K265 3 11 K267 200
K2
193 K255 194 201
IND.BKR.ON IND.BKR.OFF IND.SPRING IND.GAS. AUX. RELAY FOR K253 8 12 K269 4 12 K271 202
CHARGED PRESSURE LOW SPRING CHARGED
B10-15
INDICATION CIRCUIT GAS PRESSURE LOW ALARM LEVEL-1
SPRING CHARGE INDICATION
B10-18
LOCAL-REMOTE SEL.SWITCH
L R
B10-14 179 K113 6 10 K115 180 183 K201 6 F K203 184
163 K105 6 10 K107 164
SPRING DISCHARGED
GAS PRESSURE LOW TRIP LEVEL-2 5 E 186
B10-17 B10-18 185 K205 K207
169 K117
5 9 K119 170 125 K161 4 12 K163 126
SPARE CONTACTS FOR CUSTOMER USE
Design checked by
GK
OUTDOOR SF6 CIRCUIT Drawing checked by INDICATING CKT& SPARE CONTACTS Rev Sheet
NB 5
BREAKER TYPE OHB Drawn by Iss by Dept Year Week YN1V300013-EBM Cont.Sh
Rev Revision Appd Year Week BU PTMVE 12 17 6
Tensión Motor debe ser 125
B10-03,10A VDC
159 MCB H5
H1

230 VAC CONTROL SUPPLY FOR


A2-03 SPRING CHARGE MOTOR
DOOR LIMIT SW.
A2-01 A2-02 161 162
MCB 2A MCB 2A
H17 H19
1 3
H9 2 4
B10-01,4A
THERMOSTAT MCB
B10-04
M3 M4
105 106

230 VAC H11 H13 H15

149
IN DUCT IN CABINET SPRING CHARGE
F10-02 F10-01 LS CONTACT
A3-01
G1-12

150
H8 H10

C
A2-01 A2-02 R
MCB 2A MCB 2A

F01-01:4
B10-03,10A M
MCB 36 M4
H6 H6
160 H2
SPRING DRIVE MOTOR CKT.
HEATER SOCKET LAMP

Design checked by
GK MOTOR CIRCUIT &
OUTDOOR SF6 CIRCUIT Drawing checked by
CIRCUIT BREAKER ACCESSORIES Rev Sheet
NB 6
BREAKER TYPE OHB Drawn by Iss by Dept Year Week YN1V300013-EBM Cont.Sh
Rev Revision Appd Year Week BU PTMVE 12 19 7
Rev
Revision
K9 B10-13 A/P RELAY
J1 DC SUPPLY +VE 101
151 K2 B10-13 A/P RELAY
J2 DC SUPPLY -VE CONTROL SUPPLY 102
152 K211 B10-16 TNC SW
K211 REMOTE TNC SWITCH TRIP CONTACT 103
153 K2 TRIP COIL 1
K19 REMOTE TNC SWITCH TRIP CONTACT 104
154 M3 B10-01 MCB
K17 REMOTE TRIP COIL CONTINUITY SUPERVISON 105
155 M4 B10-01 MCB
K1 REMOTE FAULT TRIP 106
156 K21 REMOTE TRIP
K21 REMOTE FAULT TRIP 107
157 K2 TRIP COIL-2
K23 REMOTE TRIP COIL CONTINUITY SUPERVISON 108
158 K1 SPRING CHARGE CONTACT
H1 AC SUPPLY Ph 109
159 ACCESSORIES SUPPLY K37 SPRING CHARGE CONTACT
H2 AC SUPPLY N 110
160 K27 GAS PR.LOW RELAY COIL
H17 AC SUPPLY Ph 111
161 MOTOR SUPPLY K17 REMOTE TRIP COIL CONTINUITY SUPERVISON
H19 AC SUPPLY N 112
162 K1 DC SUPPLY(+VE)

Appd Year Week


K105 B10-14 (96) RELAY CONTACT 113
163 K25 B10-14 GAS PR.LOW ALARM RELAY
K107 B10-14 (96) RELAY CONTACT 114
164 K1 DC SUPPLY(+VE)
29 TRIP 1 115
165 K35 TO B5-42 IND .BKR OFF
33 TRIP 2 116
166 K7 B10-13 A/P RELAY
K21 B10-17 (96) RELAY CONTACT 117
167 K11 B10-13 A/ P RELAY
K1 B10-17 (96) RELAY CONTACT 118
168 K1 DC SUPPLY(+VE)
K117 B10-17 (96) RELAY CONTACT 119
169 K33 IND.BKR.ON
K119 B10-17 (96) RELAY CONTACT 120
170 K101
K5 FOR REMOTE CLOSE 121
171 K103 CIRCUIT BREAKER
K55 FOR REMOTE CLOSE 122
172 K41 AUX.SWITCH CONTACTS
U121 123

BREAKER TYPE OHB


173 K43

OUTDOOR SF6 CIRCUIT


U123 124
174 CIRCUIT BREAKER K161 B10-18 RELAY CONTACT
U125 AUX.SWITCH CONTACTS 125
175 K163 B10-18 RELAY CONTACT
U127 126
176 K1 DC SUPPLY(+VE)
K1 DC SUPPLY(+VE) 127
177 K100 B10-19 & 20 RELAY
K139 B10-18 RELAY CONTACT 128
U63

GK

BU
NB
178
K113 B10-18 SP.CHARGE RELAY CONTACT 129
179 U65

Drawn by
K115 B10-18 SP.CHARGE RELAY CONTACT 130
180 U67
U117 SPARE CONTACT OF AUX. SWITCH 131
181 U69

Design checked by

Drawing checked by
U119 SPARE CONTACT OF AUX. SWITCH 132
182 U71
K201 SPARE CONTACT OF LR SWITCH 133
183 U73
K203 134
184 SPARE CONTACT OF LR SWITCH U75
K205 SPARE CONTACT OF LR SWITCH 135
185 U77
K207
NOTE:-

186 SPARE CONTACT OF LR SWITCH 136


K241 U79 CIRCUIT BREAKER
B10-19 SPARE 'NO' CONATACTS 137
187 U81 AUX.SWITCH CONTACTS
K243 B10-19 SPARE 'NO' CONATACTS 138
188 U83
K245 B10-19 SPARE 'NO' CONATACTS
189 139
K247 B10-19 SPARE 'NO' CONATACTS U85
190 140
K249 B10-19 SPARE 'NO' CONATACTS U87
TERMINAL BLOCK ARRANGEMENT

191 141
K251 B10-19 SPARE 'NO' CONATACTS U89
192 SPARE 'NO' CONATACTS 142
K253 B10-19 U105
193 143
PTMVE

K255 B10-19 SPARE 'NO' CONATACTS U107


194 144
K257 B10-20 SPARE 'NC' CONATACTS U109
12

195 145
K259 B10-20 SPARE 'NC' CONATACTS U111
17

196 146
Iss by Dept Year Week

K261 B10-20 SPARE 'NC' CONATACTS U113


TERMINAL BLOCK ARRANGEMENT

197 147
K263 B10-20 SPARE 'NC' CONATACTS U115
198 148
K265 B10-20 SPARE 'NC' CONATACTS H11 TO HEATER IN DUCT
199 149
K267 B10-20 SPARE 'NC' CONATACTS H8
AND SUITABLE TO WIRE UPTO 6 SQ.MM.

200 150 TO HEATER IN DUCT


K269 B10-20 SPARE 'NC' CONATACTS
201
K271 B10-20 SPARE 'NC' CONATACTS
202
K2 DC SUPPLY -VE
203
YN1V300013-EBM
1)TYPE OF TERMINAL BLOCK USED IS PHOENIX/EQV.-UK6N

Rev
2)WIRE SIZE USED FOR CONTROL AND MOTOR CIRCUIT IS 1.5 SQ.MM.

Sheet

Cont.Sh
-
7
TERMINAL
BLOCK

B10-01 B10-02 B10-03 A2-01 A2-02 A3-01 B10-13 B10-14 B10-17 B10-18 B10-19 B10-20
TERMINAL
BLOCK

MCB MCB MCB MCB MCB

MCB FOR MCB FOR MCB FOR MCB FOR MCB FOR ANTIPUMPING GAS PRESSURE GAS PRESSURE SPRING CHARGE AUXILIARY AUXILIARY
MOTOR DC SUPPLY AC SUPPLY HEATER SOCKET SOCKET
RELAY LOW ALARM RELAY LOW TRIP RELAY CONTACT MULTIPLIER RELAY RELAY

B10-16 B10-15
B5-41 B5-42 B5-43 B5-44 B10-39 G1-12 B10-04

BREAKER ON BREAKER OFF SPRING CHARGED GAS PRESSURE LOW INDICATING ILLUMINATING
BREAKER LOCAL-REMOTE
LAMP TEST LAMP THERMOSTAT
CONTROL SWITCH SWITCH

Note:- This is tentative arrangement & it can be change with change in component make or for easy access to customer
disclosure to third parties without express authority
information contained therein. Reproduction, use or
We reserve all rights in this documents and in the

is strictly forbidden. ABB.

Prepared Checked Approved


Title
BU NB GK
Without Sep PL Sep PL Same No Sep PL Other No
WIRING LAYOUT FOR
Scale
Derived from Supersedes Superseded by
OUTDOOR SF6 BREAKER
TYPE OHB Lang
Revision Total Sh.
1
Sheet
ABB Ltd. YN1V300015-HAU 1

YN 6917 7512-AA
255 315
750 750
El interruptor debe
20 Fl Aa Terminals(Al.alloy)
incluir soporte para Cs Position indicatior ON-OFF,Mech Counter
TC, ver figura. Fl Interrupting chamber

501
501
Aa Fb Foundation bolt (M20)
Aa
Ge Earthing point (Galvanising Bus.)
20 Ms Control cubicle with spring drive

20
Vi Lh Lifting hook
Vi Supporting insulator column
Vs Supporting structure (Galvanised steel structure)

501
501 Lh

Total weight 900Kgs approx.


Creepage distance of bushing insulator 1116 mm

200
Paint shade for control cabinet : RAL 7035
1900 Insulator colour : BROWN
NOTE:-
Vs
Cs Ms 1)Structure is telescopic and has adjustment holes of 200 mm.
2) All dimensions are in mm.

930
44.5

44.5
Aa
15
Fb
Ge Terminal plate
Thickness 20 mm

900
TIGHTEN NUT FULLY
M20 HEX. NUT AFTER CEMENT HAS
SET IN

900
FOUNDATION BOLT

500
M20X500 MM LONG
disclosure to third parties without express authority

780 FRONT VIEW


information contained therein. Reproduction, use or
We reserve all rights in this documents and in the

SIDE VIEW
Foundation Plinth details
15 Hole
30-4Holes For C.B. mtg. Ge
(Foundation bolt) Prepared Checked Approved Title
NB NB GK
is strictly forbidden. ABB.

85 300
125

60 780 Detail for Earthing Revision


62.5

900 1

YN1V300015-DKS 1
YN 6917 7302-AA
210

200±0.3 R2
4Holes 5.5±0.1

14.7
Letter Height
4mm Serial number: *
Production year: * IEC 62271-100

3x6
TYPE:OHB 36.25.32 Circuit breaker
Rated Voltage 36 kV
Rated current 2500 A

113 ±0.3
Frequency 50/60 Hz
Insulation level 70 kV/170 kV peak

123
Short circuit breaking current 25 kA rms
Short circuit withstand current and duration 25 kA 3 sec

14x5.5
104.8

Short circuit making current 63 kA peak Tensión Motor


Letter Height
Operating sequence O-0.3s-CO-3min-CO debe ser 125
3.5mm
Closing coil supply voltage 125 VDC
Opening coil supply voltage 125 VDC VDC
Motor supply voltage 230 VAC
Mass of Circuit Breaker(Approx) 900 kg
Instruction manual 1VDU28005-YN
SF6 Gas Pressure (20°C) 380 kPa(abs) Mass of SF6 gas : 1.80 kg
MADE BY ABB

5
5 5

Quantity : 1 No.
NOTES:
Steel 07Cr18Ni9
S.S. Sheet ;t=0.7 mm.
as per IS:6611-'72
* TO BE FILLED BY PLANNING DEPARTMENT
- Text, line to be photoetched (Etching depth 0.2 min.)
or laser engraved on natural back ground.(Black colour) Prepared Checked Approved
BU NB GK
- ABB logo on natural background (Red colour-RAL3020) Without Sep PL Sep PL Same No Sep PL Other No RATING PLATE FOR 36 kV
- Blank text is to be engraved at ABB. OUTDOOR BREAKER TYPE OHB
Derived from Supersedes Superseded by
- General tolerance as per IN 2002 1030 SKVCB1093
Revision

ABB Limited. YN1V300303-725