Holcim Indonesia Tbk- Narogong Cement Process Instrumentation and Interlock list for ABC-inlet
cooler
No Condition of Interlock, Unit Rang Type of Low Low High High Comments Timer
Equipment shut down or e interlock Low High (Sec)
Analog value
Temperature at Fixed ABC Inlet,
Deg H-Alarm.
1 Grate plates (if any one out of 02) Protect 150 250 120
C HH - Trip Cooler Drives.
*
Low 1 - minimum pressure requirement
Operational 500
before ABC inlet air blasters can fire
mm
2 ABC fan Compartment pressure Start 300 Low 2 - Cooler drive start permissive
WC
Protect 200 Low Low - Alarm & trip cooler drives 5
Air-blaster firing sequence must be
stopped if the kiln,
3 ABC-Fixed inlet Air Blasters Operational Cooler, Kiln feed Off or at a kiln speed
less than 1.5 rpm
Note: 1. *Timer display should be flash in CCR screen for Grate plate temp alarm
2. **Timer display should be flash in CCR screen for compressed air pressure switch alarm and the pressure switch to be set at minimum 5.5 bar
pressure alarm