Starting time on DOL (second ) = ( load GD² + motor GD² ) * motor RPM
375 ( Motor average torque - load average torque )
= 25.11
6256 15.00
761 4.00
775 4.00
798 8.00
829 16.00
870 26.00
920 40.00
979 54.00
1047 69.00
1124 85.00
1210 100.00
1415.36363636 lbf inch 421.00
16.3410165289 kg-m 38.27
STARTING TIME CALCULATION ( STAR - DELTA )
Equp. AIR FAN Load GD² =
Curve Number : 1060
Motor kW 90
Load GD² referred to motor shaft (kgm²) 1060 Load GD² * ( load RPM ² / Motor RPM² )
Load RPM 980 From load T-N curve
Load Average Torque(kgm) 53.24 From load T-N curve
Motor GD² ( kgm²) 17
Load Full load torque(kgm) 79.00 From load T-N curve
Motor RPM 980
Motor FLT ( kgm ) 89.45 974 * motor kW / motor RPM
Motor starting torque ( %FLT) 200
Motor pullup torque ( %FLT) 150
Motor pullout torque ( %FLT) 250
Motor average torque ( kgm ) ( DOL ) 156.54 Motor flt * (stg+put+pot+100)/400
Changeover from ' Star ' to ' Delta ' at 80% motor speed
Before changeover : ( From 0% speed to 80% speed )
Voltage available at motor terminals at 100% V at 80% V at 110% v
( k = factor for % of Rated Voltage ) 1 0.80 1.10
Motor average torque during star
=0.01*(sgt+put+pot) / 9 * motor FLT* k ² 59.63 38.16 72.16
Load Average torque upto 80% speed 14.77
( taken from curve ) ( kgm )
Starting time in star(second ) = (Load GD²+Motor GD²) * motor RPM * 0.9
I.e. upto 80% speed 375 ( Motor avg.torque - load avg. torque)
CUSTOMER :ISGEC
Load Curve points
0 0
10 3
20 3
30 6
40 12
50 22
60 33
70 46
80 62
90 84
100 96
AV LOAD TORQUE (KGM) 0.3336363636
THESE ARE CALCULATED
Load Curve points
0 0
10 3
20 3
30 6
40 12
50 25
60 36
70 50
80 65
90 84
100 96
AVE TORQ 0.35
Crompton Greaves Ltd.
LT Motors Division
Maximum permissible load gd2 values
NOTE: Permissible maximum load gd square values are given above considering one hot start
& 2 consecutive cold starts.
Driven equipment is considered as fan.
Absorbed power by driven equipment at full load is 15% less than motor full load kw.
load gd square value is in kg-m sq referred at load rpm.
Starting time on DOL (second ) = ( load GD² + motor GD² ) * motor RPM
375 ( Motor average torque - load average torque )
75%V 110%V
Thermal Withstand Time ( second ) 25 14 30
Load Curve points
0 0
10 3
20 3
30 6
40 12
50 22
60 33
70 46
80 62
90 84
100 96
AV LOAD TORQUE (KGM) 0.3336363636
wr2
131 lb-ft2
5.531 kg-m2
70.9090909091
45.0378333333
112
14.625
14.62*2.5 360.00
63.5*10 42.66
50 1.23
51.5 1.00
169.2
112.8
170
STARTING TIME CALCULATION primary
Equp.: CENTRIFUGAL FAN Load GD² =
1980
Motor kW 55
Load GD² referred to motor shaft (kgm²) 1980.0 Load GD² * ( load RPM ² / Motor RPM² )
LOAD RPM 1475 From load T-N curve
Load Average Torque(kgm) 58.11 From load T-N curve
Motor GD² ( kgm²) 3.45
Load Full load torque(kgm) 36.32 From load T-N curve LOAD KG-M * FACTOR
Motor RPM 1475
Motor FLT ( kgm ) 36.32 974 * motor kW / motor RPM
fluid coupling setting torque 160
200
Motor pullout torque ( %FLT) 300
Motor average torque ( kgm ) 108.96 Motor flt * (stg+put+pot+100)/400
Starting time on DOL (second ) = ( load GD² + motor GD² ) * motor RPM
375 ( Motor average torque - load average torque )
75%V 110%V
Thermal Withstand Time ( second ) 160 90 194
thermal withstand time shall be at 160% FLC
Load Curve points
0 0
10 3
20 3
30 6
40 12
50 22
60 33
70 46
80 62
90 84
100 96
AV LOAD TORQUE (KGM) 0.3336363636
wr2
131 lb-ft2
5.531 kg-m2
70.9090909091
45.0378333333
112
14.625
14.62*2.5 360.00
63.5*10 42.66
50 1.23
51.5 1.00
169.2
112.8
170