CALCULATION OF NO OF EARTH PITS AS PER IS 3043-2018
Site Location- ATC Mhow
Average Soil resistivity( ρ). as per test report ρ= Based on Soil resistivity document , 280.00 Ohm-mtr Refer document "Soil Test Report- MHOW Indore" time(t) 1 Sec
Maintenance free with 250 microns Cu plated 50 mm pipe
Diameter of Pipe d= 0.1 mtr Resistivity of compound ρc= 0.12 Ohm-mtr length of Pipe L= 3 mtr Surface area S= 0.9426 Sqmtr Electrode resistance Rb =1/2∏L{(ρ-ρc)[log(8L/d)-1]+ρc[log(8L/d)-1] as per IS3043-2018 section 14.2.5 Resistance of an Electrode Encased 66.5912 Ohms in Low Resistivity Material No of pits proposed 26 No's
Resistance achieved by Interconnecting strips & other burried strips
Conductor size 50mm (interconnecting strips) 150 m Conductor size 40mm (Cu for Transformer Neutral) burried length 49 m Conductor size 25mm (Cu and GI) 77 m Average Width of strip 4.1 cm Length of grid strip in m l= 27600 cm Resistivity of interconnection strip and other burried strips 1.647 R=100ρ/2∏l(log(4l/d)
Cummilative resistance at site
Cumulative Resistance of Pipe electrodes.(Resistance of one Pipe 2.56 Ohm electrode / No.of Pipe electrodes considered) Cumulative Resistance of Interconnecting & other strips (only strips 1.65 Ohm burried in soil) Effective Resistance with Earth electrodes and strips in ground 1.0 Ohm
Conductor size calculation based on maximum fault current
if I= 15000 A t= 1 Sec K= 80 For steel conductor K= For Cu 205 conductor
Then the cross section of the grid
electrode is give by the equation S= I x Sqroot(t)/K Neutral Grounding Thus Conductor size S = 73.2 mm2 Conductor selected 25 x 6 - Cu Body Grounding Thus Conductor size S = 187.5 mm2 Conductor selected 40 x 10 - GI