300 300
Tr3
MV_1 - P
100 OC1 100
ABB
REF 615 - AF
CT Ratio 1000:5
50 Group 1 50
ANSI Extremely Inverse
Pickup = 0.74 (0.05 - 5 xCT Sec)
Time Dial = 1
30 3x = 3.65 s, 5x = 1.3 s, 8x = 0.569 s 30
LV_1.
ABB SACE PR112
Sensor = 1600
LT Pickup = 0.92 (1472 Amps)
LT Band = 9
ST Pickup = 10 (16000 Amps)
ST Band = 0.11 (I^x)t = OUT R=400A@10s
10 10
6780 A, 4.58 s
5 5
HV - P
7927 A, 3.35 s
OC1
3 3
LV_2.
ABB
o
HV OFAF 2
R
1 Other 0.5 kV 1
355A
Tr1 20 MVA
∆ 0.438 s
.5 .5
R R
Tr1
R MV_1
.3 Inrush .3
o
R MV_2
Tr3 Tr2
Tr2 Inrush Inrush MV_2 - P
500 kVA
OC1
7359 A, 0.085 s
ABB
.1 REF 615 - AF
.1
CT Ratio 30:5
8446 A, 0.0391 s Group 1
LV_1.
ANSI Extremely Inverse
.05 Pickup = 0.85 (0.05 - 5 xCT Sec) .05
Time Dial = 9.85
LV_2. 3x = 35.9 s, 5x = 12.8 s, 8x = 5.61 s
Inst = 22.35 (1 - 40 xCT Sec)
.03 .03
Time Delay = 0.02 s
Tr3 150 kVA
LV_2.
LV_1.- -3P
3P MV_2 - 3P HV - 3P
MV_1
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Star1