You are on page 1of 8

Amps X 100 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref.

kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
R 700-TF-004-S3_W2 - P
OC1 R 700-TF-004-S2_W2 - P
300 300
ABB OC1
REF 615 ABB
CT Ratio 3000:5 REF 630
Group 1 CT Ratio 3000:5
100 IEC Very Inverse Group 1 100
Pickup = 1.2 (0.05 - 5 xCT Sec) IEC Very Inverse
Time Dial = 0.2 Pickup = 1.2 (0.05 - 5 xCT Sec)
50 3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s Time Dial = 0.25 50
3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
30 30

R 700-SG-002 J47 - P
R 700-TF-001-S2_W2 - P
OC1
10 OC1 10
ABB
REF 630 ABB
CT Ratio 800:5 REF 545
5 Group 1 CT Ratio 3000:5 5
Seconds

Seconds
ANSI Extremely Inverse Very Inverse
3 Pickup = 0.4 (0.05 - 5 xCT Sec) Pickup = 1.2 (0.1 - 5 xCT Sec) 3
Time Dial = 3 Time Dial = 0.25
3x = 10.9 s, 5x = 3.89 s, 8x = 1.71 s 3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
Inst = 5.5 (0.1 - 40 xCT Sec) R 700-TF-003-S2_W2 - P
Time Delay = 0.05 s OC1
1
R 700-TF-002-S2_W2 - P 1
OC1
R 700-TF-003-S3_W2 - P
R 700-TF-001-S3_W2 - P OC1
.5 .5
ABB OC2
REF 541
.3 CT Ratio 3000:5 R 700-TF-002-S3_W2 - P .3

OC1 OC1
Very Inverse OC2
Pickup = 1.2 (0.1 - 5 xCT Sec)
.1 Time Dial = 0.2 .1
3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s
OC2
.05 Inst = 40 (0.05 - 40 xCT Sec) .05
R 700-TF-002-S2_W2 - 3P
Time Delay = 0.05 s
R 700-TF-003-S3_W2 - 3P
.03 R 700-TF-003-S2_W2 - 3P .03
R 700-TF-002-S3_W2 - 3P
R 700-TF-004-S2_W2
R 700-SG-002 J47 - 3P - 3P
R 700-TF-001-S2_W2 - 3P
R 700-TF-004-S3_W2 - 3P R 700-TF-001-S3_W2 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

51_J47 (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Phase
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Arco
Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 R 700-TF-003-S3_W2 - G 500

OC1
300 300
OC2

100
R 700-TF-002-S3_W2 - G 100
OC1
OC2
50 50

30 30

R 700-SG-002 J47 - G
OC1
10 ABB 10
REF 630
CT Ratio 100:5
5 Group 1 5
Seconds

Seconds
Inst = 0.1 (0.1 - 40 xCT Sec)
Time Delay = 0.2 s
3 3

R 700-TF-004-S3_W2 - G
1
ABB 1
REF 615
CT Ratio 200:5
.5
Group 1 .5
OC1
.3 R 700-TF-001-S3_W2 - G Group 1 .3
ABB IEC Definite Time
REF 541 Pickup = 0.1 (0.01 - 5 xCT Sec)
CT Ratio 100:5 Time Dial = 0.4
OC1 3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
.1 OC2 .1
Definite Time
Pickup = 20 (1 - 500 xCT Sec) Group 1
Time Dial = 0.4 IEC Definite Time
.05
3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s Pickup = 0.1 (0.01 - 5 xCT Sec) .05

OC2 Time Dial = 0.6


.03 3x = 0.6 s, 5x = 0.6 s, 8x = 0.6 s .03
Inst = 0.2 (0.1 - 12 xCT Sec)
R 700-TF-004-S3_W2 - G - LG
Time Delay = 0.6 s
R 700-TF-003-S3_W2
R 700-SG-002
- G- -J47
R 700-TF-001-S3_W2 GLG - G - LG
- LG
R 700-TF-002-S3_W2 - G - LG

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

51_J47 (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Ground
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar
Amps X 100 700-SG-001 Bus1 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

R 700-TF-004-S2_W2 - P
500 OC1 500
R 700-SG-002 J52 - P
ABB
OC1 REF 630
300 300
ABB CT Ratio 3000:5
REF 630 Group 1
CT Ratio 800:5 IEC Very Inverse
Group 1 Pickup = 1.2 (0.05 - 5 xCT Sec)
100
ANSI Extremely Inverse Time Dial = 0.25 100
Pickup = 0.72 (0.05 - 5 xCT Sec) 3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
Time Dial = 0.3
3x = 1.09 s, 5x = 0.389 s, 8x = 0.171 s R 700-TF-004-S3_W2 - P
50 50
Inst = 5 (0.1 - 40 xCT Sec) OC1
Time Delay = 0.05 s ABB
30 REF 615 30

CT Ratio 3000:5
Group 1
IEC Very Inverse
Pickup = 1.2 (0.05 - 5 xCT Sec)
10 10
Time Dial = 0.2
3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s

5 5
Seconds

Seconds
R 700-TF-001-S2_W2 - P
OC1
3 3

R 700-TF-003-S2_W2 - P
OC1

1 1
R 700-TF-002-S2_W2 - P
OC1R 700-TF-003-S3_W2 - P
R SAGMILL R 700-TF-001-S3_W2 - P OC1
.5 .5
Siemens ABB OC2
7UT51 REF 541
.3 CT Ratio 3000:5 R 700-TF-002-S3_W2 - P .3
CT Ratio 500:5
Definite Time OC1 OC1
Pickup = 0.806 (0.1 - 30 xCT Sec) Very Inverse OC2
Time Dial = 1 Pickup = 1.2 (0.1 - 5 xCT Sec)
.1
3x = 1 s, 5x = 1 s, 8x = 1 s Time Dial = 0.2 .1
Inst = 2.31 (0.1 - 30 xCT Sec) 3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s
Time Delay = 0.15 s OC2
.05 Inst = 40 (0.05 - 40 xCT Sec) .05
R 700-TF-002-S2_W2 - 3P
Time Delay = 0.05 s
R 700-TF-003-S3_W2 - 3P
.03 R 700-TF-003-S2_W2 - 3P .03
R 700-TF-002-S3_W2 - 3P
R 700-TF-004-S2_W2
R 700-SG-002 J52R- 3P
SAGMILL - 3P - 3P
R 700-TF-001-S2_W2 - 3P
R 700-TF-004-S3_W2 - 3P R 700-TF-001-S3_W2 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 700-SG-001 Bus1 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

55_J52 SAGMILL (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Phase
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar
Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

R 700-TF-003-S3_W2 - G
500 OC1 500

OC2
300 300

100
R 700-TF-002-S3_W2 - G 100
OC1
OC2
50 50
R 700-TF-001-S3_W2 - G
30 ABB 30
REF 541
CT Ratio 100:5
OC1
Definite Time
10 10
Pickup = 20 (1 - 500 xCT Sec)
Time Dial = 0.4
3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
5 5
OC2
Seconds

Seconds
Inst = 0.2 (0.1 - 12 xCT Sec)
3 Time Delay = 0.6 s 3

R 700-TF-004-S3_W2 - G
1
ABB 1
REF 615
CT Ratio 200:5
.5
Group 1 .5
OC1
.3
Group 1 .3
R 700-SG-002 J52 - G IEC Definite Time
Pickup = 0.1 (0.01 - 5 xCT Sec)
OC1
Time Dial = 0.4
ABB
3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
REF 630
.1 OC2 .1
CT Ratio 100:5
Group 1 Group 1
Inst = 0.1 (0.1 - 40 xCT Sec) IEC Definite Time
.05
Time Delay = 0.2 s Pickup = 0.1 (0.01 - 5 xCT Sec) .05
Time Dial = 0.6
.03 3x = 0.6 s, 5x = 0.6 s, 8x = 0.6 s .03
R 700-TF-004-S3_W2 - G - LG
RR700-SG-002
700-TF-003-S3_W2
J52 - G - -LG
R 700-TF-001-S3_W2 G- -GLG
- LG
R 700-TF-002-S3_W2 - G - LG

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

55_J52 SAGMILL (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Ground
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar
Amps X 100 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
R 700-TF-004-S3_W2 - P
OC1 R 700-TF-004-S2_W2 - P
300 300
ABB OC1
REF 615 ABB
CT Ratio 3000:5 REF 630
Group 1 CT Ratio 3000:5
100 IEC Very Inverse Group 1 100
Pickup = 1.2 (0.05 - 5 xCT Sec) IEC Very Inverse
Time Dial = 0.2 Pickup = 1.2 (0.05 - 5 xCT Sec)
50 3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s Time Dial = 0.25 50
3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
30 30

R 700-SG-002 J54 - P
OC1
10 10

5 5
Seconds

Seconds
R 700-TF-001-S2_W2 - P
3 OC1 3

R 700-TF-003-S2_W2 - P
OC1
1 R 700-TF-002-S2_W2 - P 1
OC1
R 700-TF-003-S3_W2 - P
R BALLMILL 7UT
.5
OC1 .5
Siemens
7UT51 OC2
.3 CT Ratio 800:5 R 700-TF-001-S3_W2 - P R 700-TF-002-S3_W2 - P .3
Definite Time OC1
Pickup = 0.836 (0.1 - 30 xCT Sec) OC1
OC2 OC2
Time Dial = 1
3x = 1 s, 5x = 1 s, 8x = 1 s
.1 Inst = 2.406 (0.1 - 30 xCT Sec) .1
Time Delay = 0.15 s

.05 .05
R 700-TF-002-S2_W2 - 3P
R 700-TF-003-S3_W2 - 3P
.03 R 700-TF-003-S2_W2 - 3P .03
R 700-TF-002-S3_W2 - 3P
R 700-TF-004-S2_W2 - 3P
R 700-SG-002 J54 - 3P
R 700-TF-001-S2_W2 - 3P
R 700-TF-004-S3_W2 - 3P R 700-TF-001-S3_W2 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

56_J54 BALLMILL (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Phase
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar
Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
R 700-TF-003-S3_W2 - G
300 OC1 300

OC2
R 700-TF-002-S3_W2 - G
OC1
100 OC2 100

R 700-TF-001-S3_W2 - G
50 ABB 50
REF 541
30 CT Ratio 100:5 30
OC1
Definite Time
Pickup = 20 (1 - 500 xCT Sec)
Time Dial = 0.4
10 3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s 10

OC2
Inst = 0.2 (0.1 - 12 xCT Sec)
5 5
Time Delay = 0.6 s
Seconds

Seconds
3 3

R 700-TF-004-S3_W2 - G
1
ABB 1
REF 615
CT Ratio 200:5
.5
Group 1 .5
OC1
.3
Group 1 .3
R 700-SG-002 J54 - G IEC Definite Time
OC1 Pickup = 0.1 (0.01 - 5 xCT Sec)
ABB Time Dial = 0.4
REF 630 3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
.1 CT Ratio 100:5 OC2 .1
Group 1
Group 1
Inst = 0.1 (0.1 - 40 xCT Sec)
IEC Definite Time
Time Delay = 0.2 s
.05 Pickup = 0.1 (0.01 - 5 xCT Sec) .05
Time Dial = 0.6
.03 3x = 0.6 s, 5x = 0.6 s, 8x = 0.6 s .03
R 700-TF-004-S3_W2 - G - LG
RR700-SG-002
700-TF-003-S3_W2
J54 - G - -LG
R 700-TF-001-S3_W2 G- -GLG
- LG
R 700-TF-002-S3_W2 - G - LG

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

56_J54 BALLMILL (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Ground
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar
Amps X 100 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
R 700-TF-004-S3_W2 - P
OC1 R 700-TF-004-S2_W2 - P
300 300
ABB OC1
REF 615 ABB
CT Ratio 3000:5 REF 630
Group 1 CT Ratio 3000:5
100 IEC Very Inverse Group 1 100
Pickup = 1.2 (0.05 - 5 xCT Sec) IEC Very Inverse
Time Dial = 0.2 Pickup = 1.2 (0.05 - 5 xCT Sec)
50 3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s Time Dial = 0.25 50
3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
30 30

R 700-SG-002 J57 - P R 700-TF-001-S2_W2 - P


10 OC1 OC1 10
ABB ABB
REF 630 REF 545
5 CT Ratio 800:5 CT Ratio 3000:5 5
Seconds

Seconds
Group 1 Very Inverse
3
ANSI Extremely Inverse Pickup = 1.2 (0.1 - 5 xCT Sec) 3
Pickup = 0.4 (0.05 - 5 xCT Sec) Time Dial = 0.25
Time Dial = 3 3x = 1.69 s, 5x = 0.844 s, 8x = 0.482 s
3x = 10.9 s, 5x = 3.89 s, 8x = 1.71 s
Inst = 5.5 (0.1 - 40 xCT Sec) R 700-TF-003-S2_W2 - P
1 Time Delay = 0.05 s R 700-TF-002-S2_W2 - P OC1 1
OC1
R 700-TF-003-S3_W2 - P
R 700-TF-001-S3_W2 - P OC1
.5 .5
ABB OC2
REF 541
.3 CT Ratio 3000:5 R 700-TF-002-S3_W2 - P .3

OC1 OC1
Very Inverse OC2
Pickup = 1.2 (0.1 - 5 xCT Sec)
.1 Time Dial = 0.2 .1
3x = 1.35 s, 5x = 0.675 s, 8x = 0.386 s
OC2
.05 Inst = 40 (0.05 - 40 xCT Sec) .05
R 700-TF-002-S2_W2 - 3P
Time Delay = 0.05 s
R 700-TF-003-S3_W2 - 3P
.03 R 700-TF-003-S2_W2 - 3P .03
R 700-TF-002-S3_W2 - 3P
R 700-TF-004-S2_W2
R 700-SG-002 J57 -- 3P
3P
R 700-TF-001-S2_W2 - 3P
R 700-TF-004-S3_W2 - 3P R 700-TF-001-S3_W2 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

58_J57 (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Phase
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar
Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500
R 700-TF-003-S3_W2 - G
300 OC1 300
OC2

100
R 700-TF-002-S3_W2 - G 100
OC1
OC2
50 50

30 R 700-TF-001-S3_W2 - G 30
ABB
REF 541
CT Ratio 100:5
OC1
10 10
Definite Time
Pickup = 20 (1 - 500 xCT Sec)
Time Dial = 0.4
5 5
3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
Seconds

Seconds
OC2
3 3
Inst = 0.2 (0.1 - 12 xCT Sec)
Time Delay = 0.6 s

R 700-TF-004-S3_W2 - G
1
ABB 1
REF 615
CT Ratio 200:5
.5
Group 1 .5
OC1
.3
Group 1 .3
IEC Definite Time
R 700-SG-002 J57 - G Pickup = 0.1 (0.01 - 5 xCT Sec)
OC1 Time Dial = 0.4
3x = 0.4 s, 5x = 0.4 s, 8x = 0.4 s
ABB
.1 REF 630 OC2 .1

CT Ratio 100:5 Group 1


Group 1 IEC Definite Time
.05 Inst = 0.1 (0.1 - 40 xCT Sec) Pickup = 0.1 (0.01 - 5 xCT Sec) .05

Time Delay = 0.2 s Time Dial = 0.6


.03 3x = 0.6 s, 5x = 0.6 s, 8x = 0.6 s .03
R 700-TF-004-S3_W2 - G - LG
R 700-TF-003-S3_W2 R
-G
R 700-TF-001-S3_W2 700-SG-002
- -GLG
- LG J57 - G - LG

R 700-TF-002-S3_W2 - G - LG

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps 7011-SG-002 Bus4 (Nom. kV=23, Plot Ref. kV=23) ETAP Star 19.5.0C

58_J57 (Bus4)

Project: ECP Date: 02-14-2021


Location: UM TOROMOCHO SN:
Contract: Rev: Propuesto
Engineer: Fault: Ground
Filename: C:\Users\Hamilton\Desktop\TOROMOCHO\Rev E\BD ETAP\Chinalco Ar