You are on page 1of 1

Amps X 1000 Bus8 (Nom. kV=0.433, Plot Ref. kV=0.

433)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
T3
FLA - Other 65
500 500

300 300

Incomer-1 PMCC - P
OC1
ALSTOM
100 100
P127
CT Ratio 2500:5
IEC - Extremely Inverse
50 50
Pickup = 0.979 (0.1 - 25 xCT Sec)
Time Dial = 0.359
30 3x = 3.59 s, 5x = 1.2 s, 8x = 0.456 s 30
Inst = 7.03 (0.5 - 40 xCT Sec)
Time Delay = 0.05 s

11kV ICOG - P
10 OC1 10

ABB
REF 601
5 CT Ratio 100:1 5

Seconds
Seconds

Extremely Inverse
3
Pickup = 0.924 (0.2 - 1 xCT Sec) 3
Time Dial = 1.19
3x = 11.9 s, 5x = 3.97 s, 8x = 1.51 s
Inst = 15 (2 - 15 xCT Sec)
Time Delay = 0.15 s
1 T3 1

1600 kVA (Secondary) 6.48 %Z


Delta-Wye Solid Grd
.5 .5

.3 .3 ±
11kV ICOG
I>

T3
Inrush Bus7

Multiplier = 8 xFLA (17067.17 Amps)


.1 Duration = 5 Cycles .1

T3
1600 kVA
.05 .05

.03 .03
BusDuct1

R Incomer-1 PMCC

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 1000 Bus8 (Nom. kV=0.433, Plot Ref. kV=0.433)


ETAP Star 16.0.0C
.01968 .05 .1 .3 .5 1 3 5 10 30 50 100 393.6