Professional Documents
Culture Documents
16)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 630-ACO-004-PDP-100% 230SUB001B2
1K
Ampacity
500 294MCC001P1/P2/P3 294 - MCC - 001 500
Ampacity
300 CB7 300
Allen Bradley
630-ACO-004-PDP 140U-K6
Size = 150 Amps
Thermal Trip = Fixed
100 Magnetic Trip = 10 100
Fuse7 230-SUB-001B
50 50
Cutler-Hammer
RDB-400 (77)
30 Time Lag 15.5 kV 30
40E
OL20 - OL
CB24 Allen Bradley
General Electric Power+ (MCCB) 193-EA
10 10
Sensor = 150 Plug = 0.5X Class 20 (Hot)
LT Pickup = Fixed (75 Amps) Pickup = 85 (26 - 85 Primary)
LT Band = 1
5 ST Pickup = 2 (150 Amps) 5
Seconds
Seconds
630-ACO-004-PDP-Hot
1 CB6 1
General Electric Spectra RMS SK
Frame = 500 Plug = 500 Amps 294MCC001P1/P2/P3 - P
.5 LT Pickup = Fixed (500 Amps) .5
LT Band = Fixed Cable3 - P
ST Pickup = Fixed (1506 Amps)
.3 .3
ST Band = Fixed (I^x)t = IN Cable3
Inst. Pickup = 3 (2410 Amps) Ampacity
CB7 - 3P
1-3/C 500
Fuse7
.03 .03
230-SUB-001B
2.5 MVA
CB6
294MCC001P1/P2/P3
1-3/C 500
CB7
CB24
OL9
.01 .01
630-ACO-004-PDP
Amps 230-XFR-002/2 (Nom. kV=4.16, Plot Ref. kV=4.16) ETAP Star 16.0.0C