INSTALLATION INSTRUCTIONS

Dresser Wayne Dispenser Sumps - Generic

SHEAR VALVE SUPPORT RAIL


(Up to 4)

CHANNEL SPRING NUT (4 PER RAIL)

MPK-10 (ORDER SEPARATELY)


SHEAR VALVE MOUNTING
SUPPORT BRACKET

DISPENSER SIDE RAILS (x2)

DISPENSER SUMP SUPPORT FRAME

ANCHOR BOLTS

GRP CORBEL

CONCRETE TIE RODS


(U BOLTS)

CONCRETE TIE RODS

GRP SOLID BASE SUMP


EL-W-V387 = S80 SUMP
EL-W-GC-G2200 = S80 SUMP
EL-W-VIS-35 = S80 SUMP
EL-W-VIS390 & 399 = S11 SUMP

FIBRELITE DOUBLE SIDED ENTRY BOOT


(SUPPLIED SEPARATELY)

40FC SEALANT
TUBES (x 4)

1-5 Issue: 12/06/2016


INSTALLATION INSTRUCTIONS
Dresser Wayne Dispenser Sumps - Generic

1 2
Island Level

300

A = 952 MAX
A = 802 MIN
KEY
EL-W-V387
A EL-W-GC-G2200
EL-W-VIS-35

B EL-W-VIS390 & 399

B = 825 MAX
B = 675 MIN
B = 525
A = 652
Dispenser top has been supplied pre-assembled with
metalwork.
Haunching
Permitted
3

100
1300 x 1000
300

NB:- Sump should be embedded into the support base when


installed.
B = 675 MIN
A = 802 MIN

Dry fit the corbel on top of the sump to check level and
150

prepare a adequate support base.

4
!
A =502
B= 375

If larger holes will be drilled please contact Fibrelite for


maximum trim point.

Sump can be trimmed to reduce the height of the


system by up to 150mm, if 150mm holes will be drilled
for pipe entry kits.
40

5
OD Flange Ring 190mm
TRIM LINE
110

!
NB:- Hole size drilled is Ø150mm. OD of flange is Ø190mm
Before trimming the sump, ensure that all pipe seal kits
If sump is trimmed to minimum height centre point of are fitted and the position of the highest pipe seal kit
hole is 110mm from base internally. flanges is at least 40 mm below the trim line.

2-5
INSTALLATION INSTRUCTIONS
Dresser Wayne Dispenser Sumps - Generic

6 7

OUTSIDE INSIDE

DETAIL OF DOUBLE SIDED ENTRY BOOT

Run pipework through side wall and connect to


upward riser. Cap off pipework to allow vacuum testing
in stage 12.
For PSB 50 to 110, PSBD 50 to 110 and PDBD pipe
entry kit models a 150mm hole should be drilled.
9
Mark up hole positions as illustrated.

AC
ET
ON
E

Mark trim point around the sump. Check position of


pipe entry sealkits before trimming with a jig saw. Abrade internal groove of corbel and top edge of the
Refer to stages 4 and 5 for pipework positions with and sump (inside & outside) with sandpaper. Degrease with
without trimming. acetone.

3-5
INSTALLATION INSTRUCTIONS
Dresser Wayne Dispenser Sumps - Generic

10 11

Apply sealant to BOTH the internal and external joint


between the sump and corbel. Smooth off and press
Apply a bead of sealant to the top of the sump flange. If into the joint with soapy water to remove trapped air.
this has been removed during trimming, apply sealant Allow 12 hours for the sealant to set.
inside the groove of the corbel. Position the corbel onto
the sump and push down firmly. 13

12 OPTIONAL HYDROSTATIC TEST

NB:- Vacuum test at 0.6m depth setting only.

Optional vacuum water or hydrostatic test.


Ensure pipework is capped off below the upward riser. Complete pipework and secure to shear valve rails
Tighten clips on pipe entry sealkits against the pipe. with the MPK-10 mounting kit. Refer to the shear valve
Tighten nuts on upper support frame metalwork. arrangement plan detail on page 1.

14 Backfill around the


sump equally in levels
to prevent uneven
load against the sump
wall.

4-5
INSTALLATION INSTRUCTIONS
Dresser Wayne Dispenser Sumps - Generic

15 Concrete island depth


“A” fixed as per architect
500
5-10 300 drawing.

Minimum Allow concrete to cure


200
Maximum
350 VERY IMPORTANT
OUTER EDGE “A” OF
FRAME SET 5-10mm
ABOVE GENERAL
GRADE AREA WITH
CONCRETE RAMPED
AWAY OVER 300mm

16

DISPENSER

NUT
x4
WASHER
SUMP
FRAME

Remove upper nut & washer on the 4 anchor bolts. Install & connect
the dispenser to the sump frame & anchor bolt. Fit & tighten nut &
washer.

5-5