Amps X 100 Bus1 (Nom. kV=0.208, Plot Ref. kV=0.

208) 65KW GEN‐1/2
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K

500 500

300 65KW GEN-1/2 300


FLA = 225.5

100 100

50 50
339.3 A, 26.3 s

30 30

65KW GEN-1/2
Stator Damage Curve
65 kW
10 10
65KW GEN‐1/2
5 5
CB-1/2 BREAKER
Seconds

Seconds
817.1 A, 2.88 s
Square-D Micrologic 3.3 (PP)
3 3
Sensor = 250
Ir = 225 A (225 Amps)
tr = 1.0
Ii = 4 x In (1000 Amps)

1 1

.5 .5

CU 100 ft
.3 .3
Cable1 - P
1 - 3/C 3/0 AWG 1‐3/C 3/0
Copper Rubber
Tc = 90C
.1
Plotted - 1 x 3/0 AWG
.1
0.208 kV
2451 A, 0.0495 s

.05 .05
CB‐1/2 BREAKER
.03 .03
CB-1/2 BREAKER - 3P 250 A
7.528kA @ 0.208kV
(Sym)

.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 Bus1 (Nom. kV=0.208, Plot Ref. kV=0.208)

Protective Device Settings

Project: Date: 12-16-2020


Location: Rev: Base
Contract: Fault: Phase