You are on page 1of 1

Amps X 100 TAB 2AA (Nom. kV=0.22, Plot Ref. kV=0.

231)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
CF 02 B1 1AA POD
Ampacity 2AA PODFLA CB AA POD
500 500
359 Amps 403.6 Amps
FLA TAB PPL AA POD

CF 02 A1 403.6 Amps
300 CB 2 AA 300
Ampacity CB 1 AA

359 Amps

CB AA POD CF 02 A1
CF 02 B1
6-1/C 250
6-1/C 250
100 Square-D MICROLOGIC 6.0 100

CB 1 AA Sensor = 1200
Square-D ET1.0 (MG) LT Pickup = 1 (1200 Amps) TAB 1AA
TAB 2AA
50
Sensor = 600 LT Band = 0.5 50

LT Pickup = fixed (600 Amps) ST Pickup = 2.5 (3000 Amps)


30 LT Band = Fixed ST Band = 0 (I^x)t = OUT 30
Inst. Pickup = 2 (1200 Amps) Inst. Pickup = 2 (2400 Amps) 1AA POD
2AA POD
153.8 kVA
153.8 kVA
CB Override = 9.52 kA CB Override = 10.5 kA

10 10

5 CF 02 B1 - P 5
Seconds

6 - 1/C 250 kcmil


3 Copper THW 3
Tc = 75C
CB 2 AA Plotted - 2 x 250 kcmil
Square-D ET1.0 (MG)
Sensor = 600
1 LT Pickup = fixed (600 Amps) 1
LT Band = Fixed
Inst. Pickup = 2 (1200 Amps)
.5 CB Override = 9.52 kA .5

.3 CF 02 A1 - P .3
6 - 1/C 250 kcmil
Copper THW
Tc = 75C
Plotted - 2 x 250 kcmil
.1 .1

.05 .05

CB AA POD - 3P
.03 .03
1AA POD CB 1 AA - 3P
CB 2 AA - 3P
2AA POD LRC
LRC
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 100 TAB 2AA (Nom. kV=0.22, Plot Ref. kV=0.231) ETAP Star 19.0.1C