EQUIPMENT

EQUIPMENT DESCRIPTION TAG TEST ACCORDING TO 048-PEMEX COMENTARIOS


QUANTITY
Todos los tranformadores
INSULATION RESISTANCE TO WINDINGS / TC'S
son tipo seco
1 TR-101 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
13.8-4.16 Kv 1 TR-102 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
7.5/8.625 MVA
1 TR-103 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-104 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-105 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-106 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-107 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-108 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-109 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
4.16-0.48 kV 1 TR-110 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1500/1725 kVA 1 TR-111 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-112 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-113 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
POWER 1 TR-114 TRANSFORMATION RATIO TO WINDINGS / TC'S
TRANSFORMER OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
DISTRIBUTION
1 TR-115 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-116 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-117 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-118 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-119 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
480-220/127V 1 TR-120 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
150/172.5 kVA 1 TR-121 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-122 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-123 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-124 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-125 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
480-220/127V 1 TR-126 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
150/172.5 kVA 1 TR-127 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO WINDINGS / TC'S
1 TR-128 TRANSFORMATION RATIO TO WINDINGS / TC'S
OHMIC RESISTANCE TO WINDINGS / TC'S
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
INSULATION RESISTANCE TO INSOLATOR BLADES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
EL TABLERO CUENTA CON 2
INTERRUPTORES
PRINCIPALES MAS UN
1 TDMT-101 ENLACE CON
TRANFERENCIA
AUTOMATICA
4.16.kV
SIMULTANEITY (POLES SYNCHRONISM) TO SET OF CONTACTS
EL TABLERO CUENTA CON 2
HUMIDITY
INTERRUPTORES
APPLIED POTENTIAL TO SWITCHES PRINCIPALES MAS UN
1 TDMT-101 CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP) ENLACE CON
CONTROL TESTS TO AUTOMATIC TRANSFERS TRANFERENCIA
AUTOMATICA
4.16.kV TRANSFORMATION RATIO TEST TO TC´S & TP´S
SWITCHGEAR
3F, 3H, 60Hz(15 CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
SECCIONES(12 INSULATION RESISTANCE TO CIRCUIT BREAKERS
INTERRUPTOR Y 3 INSULATION RESISTANCE TO BUSES
FUSIBLE) MARCA INSULATION RESISTANCE TO INSOLATOR BLADES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
SIEMESN SIMULTANEITY (POLES SYNCHRONISM) TO SET OF CONTACTS
EL TABLERO CUENTA CON 2
HUMIDITY
INTERRUPTORES
APPLIED POTENTIAL TO SWITCHES PRINCIPALES MAS UN
1 TDMT-102 CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP) ENLACE CON
CONTROL TESTS TO AUTOMATIC TRANSFERS TRANFERENCIA
AUTOMATICA
TRANSFORMATION RATIO TEST TO TC´S & TP´S

CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS


SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
INSULATION RESISTANCE TO INSOLATOR BLADES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
SIMULTANEITY (POLES SYNCHRONISM) TO SET OF CONTACTS
EL TABLERO CUENTA CON 2
HUMIDITY
INTERRUPTORES
APPLIED POTENTIAL TO SWITCHES PRINCIPALES MAS UN
1 TDP-101 CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP) ENLACE CON
CONTROL TESTS TO AUTOMATIC TRANSFERS TRANFERENCIA
AUTOMATICA
TRANSFORMATION RATIO TEST TO TC´S & TP´S
13.8.kV
SWITCHGEAR CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
3F, 3H, 60Hz(12 SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
SECCIONES CON INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
INTERRUPTOR) INSULATION RESISTANCE TO INSOLATOR BLADES
MARCA SIEMENS OHMIC RESISTANCE TO CIRCUIT BREAKERS
SIMULTANEITY (POLES SYNCHRONISM) TO SET OF CONTACTS
EL TABLERO CUENTA CON 2
HUMIDITY
INTERRUPTORES
APPLIED POTENTIAL TO SWITCHES PRINCIPALES MAS UN
1 TDP-102 CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP) ENLACE CON
CONTROL TESTS TO AUTOMATIC TRANSFERS TRANFERENCIA
AUTOMATICA
TRANSFORMATION RATIO TEST TO TC´S & TP´S

CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS


SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
CCM-101( 2 HUMIDITY
CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
INTERRUPTORES CONTROL TESTS TO AUTOMATIC TRANSFERS
1 PRINCIPALES Y UN
ENLACE MAS 13 TRANSFORMATION RATIO TEST TO TC´S & TP´S
SILLETAS)
CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
NO-LOAD STARTING TESTS IN CCM'S STARTERS
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
CCM-102( 2 HUMIDITY
CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
INTERRUPTORES CONTROL TESTS TO AUTOMATIC TRANSFERS
1 PRINCIPALES Y UN
ENLACE MAS 13 TRANSFORMATION RATIO TEST TO TC´S & TP´S
SILLETAS)
CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
NO-LOAD STARTING TESTS IN CCM'S STARTERS
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
CCM-103( 2 HUMIDITY
CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
INTERRUPTORES CONTROL TESTS TO AUTOMATIC TRANSFERS
1 PRINCIPALES Y UN
ENLACE MAS 13 TRANSFORMATION RATIO TEST TO TC´S & TP´S
SILLETAS)
CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS

SWITCHGEAR
&
CCM
CCM-103( 2
INTERRUPTORES
1 PRINCIPALES Y UN
ENLACE MAS 13
SILLETAS)

NO-LOAD STARTING TESTS IN CCM'S STARTERS


SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
SWITCHGEAR INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
&
CCM-104( 2 HUMIDITY
CCM CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
INTERRUPTORES CONTROL TESTS TO AUTOMATIC TRANSFERS
1 PRINCIPALES Y UN
ENLACE MAS 13 TRANSFORMATION RATIO TEST TO TC´S & TP´S
SILLETAS)
CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
NO-LOAD STARTING TESTS IN CCM'S STARTERS
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
CCM-105( 2 HUMIDITY
CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
INTERRUPTORES CONTROL TESTS TO AUTOMATIC TRANSFERS
1 PRINCIPALES Y UN
ENLACE MAS 13 TRANSFORMATION RATIO TEST TO TC´S & TP´S
SILLETAS)
CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
NO-LOAD STARTING TESTS IN CCM'S STARTERS
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
CCM-106( 2 HUMIDITY
480V CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
SWITCHGEAR INTERRUPTORES CONTROL TESTS TO AUTOMATIC TRANSFERS
1 PRINCIPALES Y UN
&
ENLACE MAS 13 TRANSFORMATION RATIO TEST TO TC´S & TP´S
MCC
SILLETAS)
3F, 3H, 60Hz
CONFIGURATION AND TRIP TESTS TO PROTECTION RELAYS
NO-LOAD STARTING TESTS IN CCM'S STARTERS
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
TD-101(2 INSULATION RESISTANCE TO BUSES
INTERRUPTORES OHMIC RESISTANCE TO CIRCUIT BREAKERS
HUMIDITY
PRINCIPALES Y UN CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
1 ENLACE MAS 8 CONTROL TESTS TO AUTOMATIC TRANSFERS
SECCIONES CON
INTERRUPTORES TRANSFORMATION RATIO TEST TO TC´S & TP´S
TERMO)
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
TD-102( 2 INSULATION RESISTANCE TO BUSES
INTERRUPTORES OHMIC RESISTANCE TO CIRCUIT BREAKERS
HUMIDITY
PRINCIPALES Y UN CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
1 ENLACE MAS 8 CONTROL TESTS TO AUTOMATIC TRANSFERS
SECCIONES CON
INTERRUPTORES TRANSFORMATION RATIO TEST TO TC´S & TP´S
TERMO)
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
TD-103( 2 INSULATION RESISTANCE TO BUSES
INTERRUPTORES OHMIC RESISTANCE TO CIRCUIT BREAKERS
HUMIDITY
PRINCIPALES Y UN CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
1 ENLACE MAS 8 CONTROL TESTS TO AUTOMATIC TRANSFERS
SECCIONES CON
INTERRUPTORES TRANSFORMATION RATIO TEST TO TC´S & TP´S
TERMO)
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
INSULATION RESISTANCE TO BUSES
TD-104( 2 OHMIC RESISTANCE TO CIRCUIT BREAKERS
INTERRUPTORES HUMIDITY
PRINCIPALES Y UN CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
1 CONTROL TESTS TO AUTOMATIC TRANSFERS
ENLACE MAS 8
SECCIONES CON TRANSFORMATION RATIO TEST TO TC´S & TP´S
INTERRUPTORES
TERMO) SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
TD-105( 2 INSULATION RESISTANCE TO BUSES
OHMIC RESISTANCE TO CIRCUIT BREAKERS
INTERRUPTORES
HUMIDITY
PRINCIPALES Y UN CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
1 ENLACE MAS 8 CONTROL TESTS TO AUTOMATIC TRANSFERS
SECCIONES CON
INTERRUPTORES
TERMO)
TD-105( 2
INTERRUPTORES
PRINCIPALES Y UN
1 ENLACE MAS 8
SECCIONES CON
INTERRUPTORES TRANSFORMATION RATIO TEST TO TC´S & TP´S
TERMO)
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE
INSULATION RESISTANCE TO CIRCUIT BREAKERS
TD-106( 2 INSULATION RESISTANCE TO BUSES
INTERRUPTORES OHMIC RESISTANCE TO CIRCUIT BREAKERS
HUMIDITY
PRINCIPALES Y UN CONTROL TESTS ACCORDING TO OPERATING PHILOSOPHY (LOOP)
1 ENLACE MAS 8 CONTROL TESTS TO AUTOMATIC TRANSFERS
SECCIONES CON
INTERRUPTORES TRANSFORMATION RATIO TEST TO TC´S & TP´S

TERMO)
SHOOTING TESTS TO PROTECTION UNITS WITH MANUFACTURER'S TEST CASE