TRANSFORMER
V0 SUMMARY
X
BASED ON THE CALCULATIONS, THE
MDP OF DIFFERENT PANEL BOARDS ARE
PANEL
MDP
PB01
PB02
V1 V2 C#3
X X C#7
PB01 PB02
x V3 x V4
SUMMARY
MDP
WIRE= 3 - 50
LENGTH 12 M
Z= 0.12 + j 0.055
TOTAL LENGTH= 12 M
REMARKS
PASSED
PASSED
PASSED
PASSED
PASSED
IMPEDANCE DIAGRAM -1
sq.mm. R= 0.12
OHMS/1000FT
X= 0.055
V0
X TOTAL R & X @ V0
MDP PANEL
VD = I x Z
VD = 0 VA 12 M
x √(0.12)^2 + (0.055)^2 x
1.732 x 230 V 305
VD = 0.000 V
%VD = VD x 100
Vs
%VD = 0 x 100
230
%VD = 0.00%
R X
TRANSFORMER TO MDO TO PB1
MDP
0.12 WIRE= 3 - 80
LENGTH 10 M TRANSFORMER TO MDP
Z= 0.079 + j 0.052
0.055
PB01
0.12 0.055 WIRE= 2 - 30
LENGTH 5 M MDP TO PB01
Z= 0.19 + j 0.045
TOTAL LENGTH= 15 M
IMPEDANCE DIAGRAM -2
sq.mm. R= 0.079
TRANSFORMER TO MDP
OHMS/1000FT
X= 0.052
sq.mm. R= 0.19
MDP TO PB01
OHMS/1000FT
X= 0.045
V1
X
PB01 PANEL
VD = I x Z
VD = 0 VA 15 M
x √(0.269)^2 + (0.097)^2 x
230 V 305
VD = 0.000 V
%VD = VD x 100
Vs
%VD = 0 x 100
230
%VD = 0.00%
R X
TRANSFORMER TO MDP TO PB2
MDP
0.079 WIRE= 3 -
LENGTH 10 M
Z= 0.079 + j
0.052
PB02
0.190 WIRE= 1 -
LENGTH 17 M
Z= 0.19 + j
0.045
TOTAL LENGTH= 27 M
TOTAL R & X @ V1 0.269 0.097
IMPEDANCE DIAGRAM -3
80 sq.mm. R= 0.079
TRANSFORMER TO MDP
0.052 OHMS/1000FT
X= 0.052
30 sq.mm. R= 0.19
MDP TO PB02
0.045 OHMS/1000FT
X= 0.045
V2
X
PB02 PANEL
VD = I x Z
VD = 0 VA 27 M
x √(0.269)^2 + (0.097)^2 x
230 V 305
VD = 0.000 V
%VD = VD x 100
Vs
%VD = 0 x 100
230
%VD = 0.00%
R X
TRANSFORMER TO MDP TO PB1 TO
MDP
0.079 #1/0 WIRE= 3 -
LENGTH 12 M
Z= 0.12 + j
0.052
PB01
0.190 #6 WIRE= 3 -
LENGTH 15 M
Z= 0.49 + j
0.045
LONGEST CIRCUIT # #8
TOTAL R & X @ V2 0.269 0.097 #10 WIRE= 3 -
LENGTH 8 M
Z= 1.2 + j
TOTAL LENGTH= 35 M
IMPEDANCE DIAGRAM -4
CKT.8
50 sq.mm. R= 0.12
TRANSFORMER TO MDP
0.055 OHMS/1000FT
X= 0.055
14 sq.mm. R= 0.49
MDP TO PB01
0.064 OHMS/1000FT
X= 0.064
V3
X
VD = I x Z
VD = 10000 VA 35 M
x √(1.81)^2 + (0.169)^2 x
1.732 x 230 V 305
VD = 5.237 V
%VD = VD x 100
Vs
%VD = 2.28%
R X
TRANSFORMER TO MDP TO PB2 TO
MDP
0.12 #1/0 WIRE= 3 -
LENGTH 12 M
Z= 0.12 + j
0.055
PB02
0.490 #8 WIRE= 3 -
LENGTH 20 M
Z= 0.78 + j
0.064
0.05
TOTAL LENGTH= 36 M
IMPEDANCE DIAGRAM -5
CKT.4
50 sq.mm. R= 0.12
TRANSFORMER TO MDP
0.055 OHMS/1000FT
X= 0.055
8 sq.mm. R= 0.78
MDP TO PB02
0.065 OHMS/1000FT
X= 0.065
V4
X
VD = I x Z
VD = 3240 VA 36 M
x √(2.1)^2 + (0.17)^2 x
230 V 305
VD = 3.503 V
%VD = VD x 100
Vs
%VD = 1.52%
R X
0.12
0.055
0.780
0.065
1.200
0.05
TRANSFORMER
F0 SUMMARY
X
BASED ON THE CALCULATIONS, THE MINIMUM
MDP OF DIFFERENT PANEL BOARDS ARE AS FOLL
PANEL FAULT
MDP F1
PB01 F2
F1 F2
X X
PB01 PB02
MOTOR CONTRIBUTION
= 188.27
50% of IFL = 188.27 / 2 = 94.13
TRANSFORMER
Z%= 2.7%
Z%= 2.5 + j
D.T.= 3 -
SOURCE V= 13.2 /
A
IMPEDANCE DIAGRAM -1
X= 85000
85000
R= (2.5)(85000)
(100)(75)
0.9 %
25 KVA X= (0.9)(85000)
0.230 KV (100)(75)
50 sq.mm. R= (1)(0.12x12/305)(85000)
(1000)(0.23)^2
0.055 OHMS/1000FT
X= (1)(0.055x12/305)(85000)
F0 (1000)(0.23)^2
X TOTAL P.U. @ F0
FAULT @ F0
ZU
ZT
ZC
M
Motor
Contribution
IF0 = 85000
38.80 X 1.732
IF0 = 5,875.38 A
KVA BASE = 85000
KV BASE = 0.230
PUR PUX
UTILITY
1.00 85000 KVA SC
13.2 KV, SOURCCE
28.33 TRANSFORMER
Z%= 2.7%
Z%= 2.50 + j
10.20 D.T.= 3 -
Supply V= 13.2 /
MDP
7.59 #1/0 WIRE= 3 -
LENGTH 12 M
Z= 0.12 + j
3.48
35.92 14.68
TEST BENCH - 02
#10 WIRE= 3 -
LENGTH 10 M
Z= 1.2 + j
+ 376.53 A
X 0.23
KVA BASE =
IMPEDANCE DIAGRAM -2
X= 85000
85000
R= (2.5)(85000)
(100)(75)
0.9
25 KVA X= (0.9)(85000)
0.230 KV (100)(75)
50 sq.mm. R= (1)(0.12x12/305)(85000)
(1000)(0.23)^2
0.055 OHMS/1000FT
X= (1)(0.055x12/305)(85000)
(1000)(0.23)^2
F0
X TOTAL P.U. @ F0
F21
X TOTAL P.U. @ F1
FAULT @ F1
ZU
ZT
ZC
M
Motor
Contributi
on
IF1 = 85000
100.64 X 1.732
IF1 = 2,496.69 A
KVA BASE = 85000
KV BASE = 0.230
PUR PUX
UTILITY
1.00 85000 KVA SC
13.2 KV, SOURCCE
28.33 TRANSFORMER
Z%= 2%
Z%= 0.9 + j 1.8
10.20 D.T.= 3 - 25
Supply V= 13.2 / 0.230
MDP
7.59 WIRE= 3 - 100
LENGTH 15 M
Z= 0.062 + j 0.041
3.48
35.92 14.68
PB02
63.22 WIRE= 3 - 60
LENGTH 25 M
Z= 0.1 + j 0.043
2.63
99.14 17.31
+ 376.53 A
X 0.23
KVA BASE =
KV BASE =
IMPEDANCE DIAGRAM -3 PUR
X= 85000
0
R= (0.9)(0) 0.00
(100)(75)
KVA X= (1.8)(0)
KV (100)(75)
F2
X TOTAL P.U. @ F2 #DIV/0!
FAULT @ F2
ZU
ZT
ZC
M
Motor
Contribution
IF2 = 0
#DIV/0! X 1.732 X
IF2 = #DIV/0! A
0.00
0.000
PUX
#DIV/0!
0.00
#DIV/0!
#DIV/0!
#DIV/0!
#DIV/0!
+ 376.53 A
0
HAZARD_CATEGORY ARC_RATING
0 N/A
1 4
2 8
3 25
4 40
Note : Meltable fabrics and other similar synthetics are never permitted.
N/A = null.
PROTECTIVE_CLOTHING_DESCRIPTION
UNTREATED COTTON, WOOL, RAYON OR SILK, OR BLENDS OF THESE MATERIALS WITH
A FABRIC WEIGHT OF AT LEAST 4.5 oz/yd².
Arc rated FR shirt and FR pants or coverall.
Cotton underwear plus FR shirt and FR pants
Arc rated FR shirt and pants or coverall, and arc flash suit selected so that the system
arc rating meets the required minimum.
Arc rated FR shirt and pants or coverall, and arc flash suit selected so that the system
arc rating meets the required minimum.
milar synthetics are never permitted.
Input cells
IEEE Standard 1584-2002
1. Arcing Current Estimation: For LV application < 1kV
Ia in kA Configuration, K1 System, K2
3.52 Box Earthed
1.55 Open Unearthed
E = 4.184CfEn (t/0.2)(610/D)^X
T Cf D
DB = 610 x (4.184CfEn(t/0.2)(1/EB))^(1/x)
Cf En Eb
1.50 0.89 5.00
1.50 0.27 5.00
Configuration Gap Between Conductor, G
Box 25.00
Open 15.00
x E in J/cm²
1.64 0.06
2.00 0.01
t Db
0.01 105.20
0.01 79.30
En in cal/cm² Hazard Category Clothing Description
0.21
0.06
K1 K2 log En
-0.555 -0.113 (0.05)
-0.792 0 (0.57)
En
0.89
0.27
x
1.64
2.00