Voltage Drop = ( I ) ( L ) ( vd ) V
1000
I ( 3 phases ) = P A I ( 1 phase ) = P A
1.732 x V x cos ø V x cos ø
2.80 kW x 1000
TNB Source FP = A x 150 m x 0.99 mV/A/m
610.963
1000
= 414.32
= 414.32
1.732
= 239.21 V
VD = ( I4 ) x ( L ) x ( vd )
1000
I1 = P
239.21 cos ø
= 2 ( 250 + 30 )
203.33
= 2.75 A
= 0.07 V
P1 P4 I2 = P
239.21 - 0.07 cos ø
= 1 ( 250 + 30 )
239.15 cos ø
= 1 ( 250 + 30 )
203.27
= 1.38 A
= 0.36 V
= 0.07 0.36
= 0.43 V
Voltage Drop = ( I ) ( L ) ( vd ) V
1000
I ( 3 phases ) = P A I ( 1 phase ) = P A
1.732 x V x cos ø V x cos ø
2.80 kW x 1000
TNB Source FP = A x 150 m x 0.99 mV/A/m
610.963
1000
= 414.32
= 414.32
1.732
= 239.21 V
VD = ( I4 ) x ( L ) x ( vd )
1000
I1 = P
239.21 cos ø
= 2 ( 250 + 30 )
203.33
= 2.75 A
= 0.45 V
P2 P5 I2 = P
239.21 - 0.45 cos ø
= 1 ( 250 + 30 )
238.77 cos ø
= 1 ( 250 + 30 )
202.95
= 1.38 A
= 0.36 V
= 0.45 0.36
= 0.81 V