You are on page 1of 2

PROJECT: DOWNTOWN HOTEL - THE EDITION DETAILS OF CONNECTED LOAD / MAX.

DEMAND & KWH METERING AREA: DOWNTOWN, DUBAI


OWNER: JARVIS CORPORATION LIMITED PLOT: 345-0792
LV PANEL-01 CONSULTANT: IBA ENGINEERS CONSULTANTS LOCATION: LV ROOM, BASEMENT-1
RATING - AMPS FAULT PVC/* CABLE SIZE LENGTH ECC CONNECTED LOAD.KWH PROPOSED TYPE & NO. OF
XLPE OF SIZE KWH METERS REMARKS
CIRCUIT/ FEEDER DB NO. SP / TP DUTY
F/S MCCB SWA/ 2/4X1C 2/3/4C CABLE 1C R-PH Y-PH B-PH TOTAL 1.PH. 3.PH. 3.PH CT
(kA)
ISO ACB PVC mm2 mm2 ( Mtrs. ) mm2 KW KW KW KW {1} {2} {3} {4}
2500
INCOMER-1 4P 65 DEWA 2Rx1C 150 386.57 388.83 316.94 1,092.35 1 2500/5A
set@0.9
2500/5A with
INCOMER-1 (Mobile generator 2500
4P 65 - electromechanical
provision) set@0.9
interlock

OUTGOINGS:
SMDB-B3-N TP 125 50 4C 50 1C 25 18.02 17.92 17.27 53.20
SMDB-B2-N TP 60 50 4C 16 1C 16 10.15 9.35 11.30 30.80
SMDB-B1-N TP 400 50 4C 300 1C 150 81.85 80.65 28.50 191.00 1
BB-N1 TP 630 50 BUSBAR 630A 114.12 118.98 97.74 330.84
ATS (SMDB-E) TP 630 50 2X4C 185 1C 185 110.77 110.27 109.07 330.11
Fire Pump TP 350 50 4C 240 1C 120 51.67 51.67 51.67 155.00 ELS+Alaram
DB-SS SP 40 50 1.40 1.40
Capacitor Bank TP 800 50 2X4C 300 1C 300 AUTO STEP 350 KVAR

MDB CONNECTED TO: DEWA TRANSFORMER-1 TOTAL CONNECTED LOAD PER PHASE : 386.57 388.83 316.94 1,092.35 0 2 TOTAL

DEMAND FACTOR 0.90 MAX. DEMAND 983.12 KW TOTAL CONNECTED LOAD (3 PH.): 1,092.35 KW. Total Build-up area

CONTRACTOR: BRIGHT ELECTRICAL WORKS L.L.C, TEL.: 04 - 3856 557 FAX: 04 - 3856 553 MAIL : brightew89@contractor.net
Type of Meter ( Rating of Incomer ) : (1) Up to 60A (2) Up to 100A (3) 125 - 160 A (4) LV CT / A / HV CT / A
( 1Phase ) ( 3phase )
PROJECT: DOWNTOWN HOTEL - THE EDITION DETAILS OF CONNECTED LOAD / MAX.DEMAND & KWH METERING AREA: DOWNTOWN, DUBAI
OWNER: JARVIS CORPORATION LIMITED PLOT: 345-0792
LV PANEL-02 CONSULTANT: IBA ENGINEERS CONSULTANTS LOCATION: LV ROOM, BASEMENT-1
RATING - AMPS FAULT PVC/* CABLE SIZE LENGTH ECC CONNECTED LOAD.KWH PROPOSED TYPE & NO. OF
CIRCUIT/ FEEDER DB NO. SP / TP DUTY XLPE OF SIZE KWH METERS REMARKS
F/S MCCB SWA/ 2/4X1C 2/3/4C CABLE 1C R-PH Y-PH B-PH TOTAL 1.PH. 3.PH. 3.PH CT
(kA)
ISO ACB PVC mm2 mm2 ( Mtrs. ) mm2 KW KW KW KW {1} {2} {3} {4}
1600
INCOMER-1 4P 65 DEWA 2Rx1C 150 238.00 243.94 219.38 701.32 1 1600/5A
set@0.9
1600/5A with
INCOMER-1 (Mobile 1600
4P 65 - electromechanical
generator provision) set@0.9
interlock
OUTGOINGS:
BB-N2 TP 1600 50 BUSBAR 1600A 238.00 243.94 217.98 699.92
DB-RMU SP 40 50 1.40 1.40
Capacitor Bank TP 630 50 2X4C 185 1C 185 AUTO STEP 230 KVAR

MDB CONNECTED TO: DEWA TRANSFORMER-1 TOTAL CONNECTED LOAD PER PHASE : 238.00 243.94 219.38 701.32 0 1 TOTAL

DEMAND FACTOR 0.90 MAX. DEMAND 631.19 KW TOTAL CONNECTED LOAD (3 PH.): 701.32 KW. Total Build-up area

CONTRACTOR: BRIGHT ELECTRICAL WORKS L.L.C, TEL.: 04 - 3856 557 FAX: 04 - 3856 553 MAIL : brightew89@contractor.net
Type of Meter ( Rating of Incomer ) : (1) Up to 60A (2) Up to 100A (3) 125 - 160 A (4) LV CT / A / HV CT / A
( 1Phase ) ( 3phase )