Professional Documents
Culture Documents
DEMAND
INCOMER-01 4P 2500A. ACB SET @ 0.85 50 BY DEWA 431.23 425.20 424.89 1281.33 1281.33 0.00 1153.19 0.90 1 2400/5A. CT METER
INCOMER-02 4P 2500A. ACB SET @ 0.85 50 BY GENERATOR SUPPLIER PROVISION FOR MOBILE GENERATOR WITH ELECTRICAL AND MECHANICAL INTERLOCK
OUT GOINGS
BB2-MDB-02 RYB1 TP 2500A. ACB 50 2500A TPN+E COPPER BUSBAR RISER 388.03 382.00 381.69 1151.73 1151.73 0.00 1036.55 0.90 48
SMDB-LIFT RYB2 TP 200A XLPE/SWA/LSZH 4C, 95 1C, 50 16.53 16.53 16.53 49.60 49.60 0.00 44.64 0.90
ISOLATOR FOR POOL RYB7 TP 160A XLPE/SWA/LSZH 4C, 70 1C, 35 26.67 26.67 26.67 80.00 80.00 0.00 72.00 0.90 ELS4
PFC 400 KVAR CAPACITOR BANK RYB9 TP 1000 50 XLPE/SWA/LSZH 3x4C 240 3x1C 120 CAPACITOR BANK - 400 KVAR
MAX. DEMAND ( 3 PH) : 1153.19 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ): 1281.33 kW
TOTAL STAND BY LOAD: 0.00 KW TOTAL CONNECTED LOAD WITH OUT STAND BY: 1281.33 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
( 1 Phase ) ( 3 Phase ) ( 3 Phase )
LV-P4-3S-01 Page 1 of 51
MAIN BUS BAR DETAILS OF CONNECTED LOAD / MAX. DEMAND
PROJECT 4B + G + 15 TYP. + ROOF Commercial and CLIENT : M/S BU HALEEBA MEP CONTRACTOR CONSULTANT:
Residential Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB BB2-MDB-02 AREA : Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM MDB-02 PLOT : 1341040 P.O.Box 233237 Dubai – UAE
LOCATION G.F - LV ROOM
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE ECC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ DUTY 2/4x1C 2/3/4C SIZE TOTAL LOAD ACTUAL STAND BY MAX DEMAND DEMAND
R Phase Y Phase B Phase
DB NO. TP ACB MCCB MCB IN kA SWA / PVC in mm2 in mm2 in mm2 IN kW LOAD IN kW LOAD kW LOAD IN kW FACTOR (1) (2) (2) (3) REMARKS
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 2500A 50 2500A TPN+E COPPER BUSBAR RISER 388.03 382.00 381.69 1151.73 1151.73 0.00 1036.55 0.90
OUT GOINGS
SMDB-09F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 52.57 52.10 52.42 157.09 157.09 141.38 0.90 10
SMDB-10F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 52.57 52.10 52.42 157.09 157.09 141.38 0.90 10
SMDB-11F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 55.83 55.70 55.56 167.09 167.09 150.38 0.90 10
SMDB-12F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 55.83 55.70 55.56 167.09 167.09 150.38 0.90 10
SMDB-13F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 55.83 55.70 55.56 167.09 167.09 150.38 0.90 10
SMDB-14F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 57.71 55.35 55.09 168.15 168.15 151.33 0.90 10
SMDB-15F TP 350 50 XLPE/SWA/LSZH 4C, 240 1C, 120 57.71 55.35 55.09 168.15 168.15 151.33 0.90 10
MAX. DEMAND ( 3 PH) : 1036.55 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ): 1151.73 kW
TOTAL STAND BY LOAD: 0.00 KW TOTAL CONNECTED LOAD WITH OUT STAND BY: 1151.73 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 2 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building CONSULTANT
MDB / SMDB : SMDB-9F AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : BB1-MDB-01 PLOT 1341040
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 52.57 52.10 52.42 157.09 141.38 0.00
OUT GOINGS
DB-1F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.01 4.93 5.17 15.11 13.60 1
DB-1F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.11 5.19 15.70 14.13 1
DB-1F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.11 5.19 15.70 14.13 1
DB-1F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.00 5.11 4.99 15.11 13.59 1
DB-1F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 4.83 5.57 5.09 15.49 13.94 1
DB-1F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.55 5.45 5.73 16.72 15.05 1
DB-1F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 4.91 5.19 15.50 13.95 1
DB-1F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 4.91 5.19 15.50 13.95 1
DB-1F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.69 5.45 5.59 16.73 15.06 1
DB-1F-10 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 4.85 5.57 5.09 15.51 13.96 1
MAX. DEMAND ( 3 PH) : 141.38 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 157.09 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 3 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building CONSULTANT
MDB / SMDB : SMDB-10F AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : BB1-MDB-01 PLOT 1341040
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 52.70 52.10 52.28 157.09 141.38 0.00
OUT GOINGS
DB-1F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.01 4.93 5.17 15.11 13.60 1
DB-1F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.11 5.19 15.70 14.13 1
DB-1F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.11 5.19 15.70 14.13 1
DB-1F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.00 5.11 4.99 15.11 13.59 1
DB-1F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 4.83 5.57 5.09 15.49 13.94 1
DB-1F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.68 5.45 5.59 16.72 15.05 1
DB-1F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 4.91 5.19 15.50 13.95 1
DB-1F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 4.91 5.19 15.50 13.95 1
DB-1F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.69 5.45 5.59 16.73 15.06 1
DB-1F-10 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 4.85 5.57 5.09 15.51 13.96 1
MAX. DEMAND ( 3 PH) : 141.38 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 157.09 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 4 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential CONSULTANT
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building NATIONAL ENGINEERING BUREAU LLC
MDB / SMDB : SMDB-11F AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : BB2-MDB-02 PLOT 1341040 P.O.Box 233237 Dubai – UAE
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 55.83 55.70 55.56 167.09 150.38 0.00
OUT GOINGS
DB-11F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.33 5.37 16.11 14.50 1
DB-11F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.51 5.39 16.70 15.03 1
DB-11F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.51 5.39 16.70 15.03 1
DB-11F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.40 5.51 5.19 16.11 14.49 1
DB-11F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.23 5.77 5.49 16.49 14.84 1
DB-11F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.75 5.85 6.13 17.72 15.95 1
DB-11F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.31 5.39 16.50 14.85 1
DB-11F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.31 5.39 16.50 14.85 1
DB-11F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.75 5.85 6.13 17.73 15.96 1
DB-11F-10 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.05 5.77 5.69 16.51 14.86 1
MAX. DEMAND ( 3 PH) : 150.38 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 167.09 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 5 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 55.83 55.70 55.56 167.09 150.38 0.00
OUT GOINGS
DB-12F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.33 5.37 16.11 14.50 1
DB-12F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.51 5.39 16.70 15.03 1
DB-12F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.51 5.39 16.70 15.03 1
DB-12F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.40 5.51 5.19 16.11 14.49 1
DB-12F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.23 5.77 5.49 16.49 14.84 1
DB-12F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.75 5.85 6.13 17.72 15.95 1
DB-12F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.31 5.39 16.50 14.85 1
DB-12F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.31 5.39 16.50 14.85 1
DB-12F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.75 5.85 6.13 17.73 15.96 1
DB-12F-10 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.05 5.77 5.69 16.51 14.86 1
MAX. DEMAND ( 3 PH) : 150.38 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 167.09 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 6 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 55.83 55.70 55.56 167.09 150.38 0.00
OUT GOINGS
DB-13F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.41 5.33 5.37 16.11 14.50 1
DB-13F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.51 5.39 16.70 15.03 1
DB-13F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.51 5.39 16.70 15.03 1
DB-13F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.40 5.51 5.19 16.11 14.49 1
DB-13F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.23 5.77 5.49 16.49 14.84 1
DB-13F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.75 5.85 6.13 17.72 15.95 1
DB-13F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.31 5.39 16.50 14.85 1
DB-13F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.81 5.31 5.39 16.50 14.85 1
DB-13F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.75 5.85 6.13 17.73 15.96 1
DB-13F-10 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.05 5.77 5.69 16.51 14.86 1
MAX. DEMAND ( 3 PH) : 150.38 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 167.09 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 7 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building CONSULTANT
MDB / SMDB : SMDB-14F AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : BB2-MDB-02 PLOT 1341040
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 57.71 55.35 55.09 168.15 151.33 0.00
OUT GOINGS
DB-14F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.97 5.76 5.63 17.36 15.63 1
DB-14F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.41 5.94 5.69 18.04 16.23 1
DB-14F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.41 6.11 5.52 18.04 16.23 1
DB-14F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.97 5.90 5.49 17.36 15.62 1
DB-14F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.35 6.07 5.42 17.85 16.06 1
DB-14F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 7.55 6.73 7.61 21.90 19.71 1
DB-14F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.14 6.05 5.69 17.87 16.09 1
DB-14F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 7.55 6.73 7.61 21.90 19.71 1
DB-14F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.35 6.07 6.42 17.85 16.06 1
MAX. DEMAND ( 3 PH) : 151.33 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 168.15 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 8 of 51
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building CONSULTANT
MDB / SMDB : SMDB-15F AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : BB2-MDB-02 PLOT 1341040
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 350A 25 XLPE/SWA/LSZH 4C, 240 1C, 120 57.71 55.35 55.09 168.15 151.33 0.00
OUT GOINGS
DB-14F-01 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.97 5.76 5.63 17.36 15.63 1
DB-14F-02 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.41 5.94 5.69 18.04 16.23 1
DB-14F-03 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.41 6.11 5.52 18.04 16.23 1
DB-14F-04 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.97 5.90 5.49 17.36 15.62 1
DB-14F-05 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.35 6.07 5.42 17.85 16.06 1
DB-14F-06 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 7.55 6.73 7.61 21.90 19.71 1
DB-14F-07 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 6.14 6.05 5.69 17.87 16.09 1
DB-14F-08 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 7.55 6.73 7.61 21.90 19.71 1
DB-14F-09 TP 40A 25 XLPE/SWA/LSZH 4C, 10 1C, 10 5.35 6.07 6.42 17.85 16.06 1
MAX. DEMAND ( 3 PH) : 151.33 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 168.15 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 9 of 51
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar, MEP CONTRACTOR CONSULTANT
Dubai,UAE
D B. NO. : DB-1F-01 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. NATIONAL ENGINEERING BUREAU LLC
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
13 R5 SPACE 0
17 Y6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.11 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-02 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.70 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-03 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.70 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-04 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-02 &03 - BED ROOMS 2 92 92 184
ELCB
6 B2 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
13 R5 SPACE 0
17 Y6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.11 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-05 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-04
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
6 B2 SPACE 0
18 B6 2 1 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.49 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-06 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN 1 121 121
ELCB
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 ACP 1 100 100
17 Y6 SPACE 0
18 B6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.72 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-07 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.50 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-08 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.50 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-09 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN 1 121 121
ELCB
6 B2 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 ACP 1 100 100
17 Y6 SPACE 0
18 B6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.73 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-1F-10 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-04
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
6 B2 SPACE 0
40 A 4P
4 14 Y5 20 4.0 4.0 ACP 1 100 100
30mA
16 R6 2190
40 A 4P
100mA 5 17 Y6 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
18 B6 2 1 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.51 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-01 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
13 R5 SPACE 0
17 Y6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.11 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-02 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.70 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-03 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.70 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-04 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-02 &03 - BED ROOMS 2 92 92 184
ELCB
6 B2 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
13 R5 SPACE 0
17 Y6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.11 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-05 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-04
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
6 B2 SPACE 0
18 B6 2 1 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.49 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-06 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN 1 121 121
ELCB
6 B2 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 ACP 1 100 100
17 Y6 SPACE 0
18 B6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.72 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-07 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.50 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-08 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500
17 Y6 SPACE 0
13 R7 2190
40 A 4P
5 14 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.50 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-09 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN 1 121 121
ELCB
6 B2 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 ACP 1 100 100
17 Y6 SPACE 0
18 B6 SPACE 0
13 R7 2190
40 A 4P
100mA 5 14 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
15 B7 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.73 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-10F-10 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-04
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
6 B2 SPACE 0
40 A 4P
4 14 Y5 20 4.0 4.0 ACP 1 100 100
30mA
16 R6 2190
40 A 4P
100mA 5 17 Y6 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
18 B6 2 1 2190
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 15.51 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar, MEP CONTRACTOR CONSULTANT
Dubai,UAE
D B. NO. : DB-11F-01 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. NATIONAL ENGINEERING BUREAU LLC
LOCATION :
TYPICAL 11-13 :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
13 R5 SPACE 0
19 R7 2190
40 A 4P
100mA 5 20 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
21 B7 2190
40 A 4P
30mA 5 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.11 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-02 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 5 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.70 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-03 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-03 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 5 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.70 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-04 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-02 &03 - BED ROOMS 2 92 92 184
ELCB
6 B2 SPACE 0
13 R5 SPACE 0
19 R7 2190
40 A 4P
100mA 5 20 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
21 B7 2190
40 A 4P
30mA 5 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.11 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-05 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 SPARE 1 200 200
40 A 4P
4 14 Y5 20 4.0 4.0 ACP 1 100 100
30mA
16 R7 2190
40 A 4P
100mA 5 17 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
18 B7 2190
40 A 4P
30mA 5 20 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.49 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-06 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN 1 121 121
ELCB
19 R7 2190
40 A 4P
100mA 5 20 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.72 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-07 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.50 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-08 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.50 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-09 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN 1 121 121
ELCB
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 200 200
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.73 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-11F-10 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
FED FROM : SMDB-11F
LOCATION :
TYPICAL 11-13 :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
6 B2 SPACE 0
40 A 4P
4 14 Y5 20 4.0 4.0 ACP 1 100 100
30mA
16 R6 2190
40 A 4P
5 17 Y6 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
18 B6 2190
19 R7 SPACE 0
20 Y7 SPACE 0
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 16.51 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-01 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
FED FROM : SMDB-14F
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Incomer ELCB tion No. No.
Rtg in
Size Size
ROOM / AREA Watt / Unit Remarks
Amp Ltg BELL FCU CU W/M D/W W/H MISC R Y B
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
13 R5 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 333 333
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.36 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-02 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-02
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 333 333
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 18.04 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-03 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 45 11 26 13 229
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 500 500
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 18.04 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-04 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-02 &03 - BED ROOMS 2 92 45 137
ELCB
6 B2 SPACE 0
13 R5 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 333 333
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.36 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-05 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-04
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
40 A 4P
100mA 2 5 Y2 SPACE 0
ELCB
6 B2 SPACE 0
40 A 4P
30mA 3
ELCB 10 R4 20 4.0 4.0 SPARE 1 1000 1000
40 A 4P
4 14 Y5 20 4.0 4.0 ACP 1 100 100
30mA
16 R7 2190
40 A 4P
5 17 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
18 B7 2190
40 A 4P
30mA 6 20 Y8 20 SPARE 1 500 500
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.85 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-06 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED +BED ROOM 2 2 4 2 1 2 26 8 18 14 13 30 241
ELCB
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN/ BEDROOM-2 2 121 45 166
ELCB
6 B2 SPACE 0
19 R7 2190
40 A 4P
100mA 5 20 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
21 B7 2190
22 R8 SPACE 0
24 B8 SPACE 0
40 A 4P
30mA 6
ELCB 25 R9 20 SPARE 1 500 500
D B. NO. : DB-14F-07 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-03
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 5 2 1 45 11 26 13 8 18 30 335
ELCB
3 B1 SPACE 0
4 R2 SPACE 0
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - BED ROOM/DINING/KITCHEN 2 92 95 187
ELCB
6 B2 SPACE 0
7 R3 SPACE 0
14 Y5 SPACE 0
19 R7 2190
40 A 4P
5 20 Y7 32 6.0 6.0 CU-02 1 6570 2190 UVR+TIMER+CONTACTOR
100mA
21 B7 2190
40 A 4P
30mA 6 23 Y8 20 SPARE 1 333 333
ELCB
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.87 kW
PROJECT : 4B + G + 15 TYP. + ROOF Commercial and Residential Building on Plot No.1341040 @ Al Mamzar,
Dubai,UAE
D B. NO. : DB-14F-06 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED +BED ROOM 2 2 4 2 1 2 26 8 18 14 13 30 241
ELCB
40 A 4P
100mA 2 5 Y2 20 4.0 4.0 FCU-01 - LIVING/DINING/KITCHEN/ BEDROOM-2 2 121 45 166
ELCB
6 B2 SPACE 0
19 R7 2190
40 A 4P
100mA 5 20 Y7 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
21 B7 2190
22 R8 SPACE 0
24 B8 SPACE 0
40 A 4P
30mA 6
ELCB 25 R9 20 SPARE 1 500 500
D B. NO. : DB-14F-09 LOAD DISTRIBUTION SCHEDULE EMAC ELECTROMECHANICAL CO. L.L.C. National Engineering Bureau
LOCATION :
TYPICAL :FLAT-01
CONNECTED LOAD LOAD PER CIRCUIT - WATT
CKT CPC
MCB SH EX 13A 13A 15 A
Rating of Rating of Sec Srl. Ckt. Wire Wire
Rtg in ROOM / AREA Watt / Unit Remarks
Incomer ELCB tion No. No. Size Size Ltg BELL FCU CU W/M D/W W/H MISC R Y B
Amp
mm2 mm2 SO FAN SO T SO SO
40 A 4P
100mA 1 2 Y1 10 2.5 2.5 LIGHTING IN MASTER BED ,LIVING&DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB
3 B1 SPACE 0
6 B2 SPACE 0
40 A 4P
30mA 4 14 Y5 20 4.0 4.0 ACP 1 100 100
ELCB
16 R6 2190
40 A 4P
100mA 5 17 Y6 32 6.0 6.0 CU-01 1 6570 2190 UVR+TIMER+CONTACTOR
ELCB
18 B6 2190
19 R7 SPACE 0
20 Y7 SPACE 0
Cable size : 1 x 4C 10mm² CU./XLPE/SWA/LSZH,CU C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer
CPC size : 1 x 1C, 10mm² CPC (LSZH), W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type. TCL = 17.85 kW
DETAILS OF CONNECTED LOAD / MAX. DEMAND
4B + G + 15 TYP. + ROOF Commercial and Residential
PROJECT : CLIENT M/S BU HALEEBA MEP CONTRACTOR
Building CONSULTANT
MDB / SMDB : SMDB-LIFT AREA Al Mamzar, Dubai,UAE EMAC ELECTROMECHANICAL CO. L.L.C.
FEED FROM : MDB-02 PLOT 1341040
CIRCUIT / RATINGS - AMPS FAULT PVC / XLPE CABLE SIZE CPC CONNECTED LOAD - KW
PROPOSED TYPE & No. OF KWH METERS
FEEDER SP/ F/S MCCB MCB DUTY 2/4x1C 2/3/4C SIZE
TCL
MAX DEMAND STAND BY LOAD
DB NO. TP ISO ACB ELCB IN kA SWA / PVC in mm2 in mm2 in mm2 R-Phase Y-Phase B-Phase INCLUDING
LOAD IN KW IN KW (1) (2) (3) (4) REMARKS
STAND BY
kW kW kW 1 PH 3-PH 3-PH LV/HV CT
INCOMER TP 200A (N/A) 25 XLPE/SWA/LSZH 4C, 95 1C, 50 16.53 16.53 16.53 49.60 44.64 0.00
OUT GOINGS
ISOLATOR FOR LIFT-01 TP 63A 25 XLPE/SWA/LSZH 4C, 16 1C, 16 4.13 4.13 4.13 12.40 11.16 ELS2
ISOLATOR FOR LIFT-02 TP 63A 25 XLPE/SWA/LSZH 4C, 16 1C, 16 4.13 4.13 4.13 12.40 11.16 ELS2
ISOLATOR FOR LIFT-03 TP 63A 25 XLPE/SWA/LSZH 4C, 16 1C, 16 4.13 4.13 4.13 12.40 11.16 ELS2
ISOLATOR FOR LIFT-04 TP 63A 25 XLPE/SWA/LSZH 4C, 16 1C, 16 4.13 4.13 4.13 12.40 11.16 ELS2
MAX. DEMAND ( 3 PH) : 44.64 kW @ DIVERSITY FACTOR : 0.90 TOTAL CONNECTED LOAD ( 3 PHASE ) 49.60 kW
Type of Meter ( Rating of Incomer) : (1) Up to 60A (2) Upto 100A (3) Up to 125 - 160A (4) LV CT ……..../..…......A / HV CT …../... A
LV-P4-3S-01 Page 51 of 51