DETAIL OF CONNECTED LOAD & MAX DEMAND

PROJECT: 4B+G+15TYP.+ROOF OWNER: MR. ABDULLA ALI HAMAD AREA: AL MAMZAR , DUBAI, U.A.E
(COMMERCIAL/RESIDENTIAL BUILDING) SAEED BUHALEEBA

PLANNED COMPLETION DATE: CONSULTANT: ENGINEERING ASSOCIATES PLOT NO: 134-1040

SMDB-1F LOCATION OF SMDB-1F : ELECTRICAL ROOM(TYPICAL)

Rating AMPS CABLE SIZE PROPOSED TYPE & No. OF


FAULT PVC/ XLPE CONNECTED LOAD - kW
CIRCUIT/ ECC SIZE- kWh METERS
SP/TP DUTY 2/4x1C 2 REMARKS
FEEDER F/S MCCB MCB kA 2 2/3/4C mm2 1C mm R-PH Y-PH B-PH TOTAL 1-PH 3-PH 3-PH LV/HV
SWA/ PVC mm
DB NO. ISO ACB kW kW kW kW CT
(1) (2) (3) (4)
300
INCOMER TP 25 XLPE/SWA/LSZH 4C-185 1x1C-95 43.88 43.83 43.82 131.53
N/A

OUTGOING

DB -1F-01 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.3 4.2 4.7 13.2 1


DB -1F-02 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.4 4.1 4.2 12.7 1
DB -1F-03 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.4 4.1 4.2 12.7 1
DB -1F-04 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.3 4.6 4.3 13.2 1
DB -1F-05 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 3.9 4.5 4.1 12.5 1
DB -1F-06 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.9 4.9 5.1 14.9 1
DB -1F-07 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.4 3.9 4.2 12.5 1
DB -1F-08 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 4.4 3.9 4.2 12.5 1
DB -1F-09 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 5.1 4.9 4.9 14.9 1
DB -1F-10 TP 40 25 XLPE/SWA/LSZH 4C-10 1x1C-10 3.9 4.5 4.1 12.5 1

SMDB-1F CONNECTED TO:


BB1-MDB-01
TOTAL CONNECTED LOAD PER PHASE 43.9 43.8 43.8 131.5 0 10 0 0 TOTAL

MAX DEMAND (3 PH) _______ 111.80 kW @ 0.85 DIVERSITY TOTAL CONNECTED LOAD (3PH) 131.5 kW

CONTRACTOR:

Type of Meter (Rating of Incomer): (1) Up to 60A (2) Up to 100A (3) Up to 125-160A (4) LV CT …../5A
( 1 PHASE ) ( 3 PHASE )
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-01

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 1 5 2 4 4 2 2 26 13 8 14 18 26 10 30 363

40A 4P
100 mA 2 Y1 10 2.5 2.5 MASTER BED + LIVING & DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB

3 B1 SPACE 0

4 R2 10 2.5 2.5 FCU 1 122 122

40A 4P
100 mA 5 Y2 SPACE 0
ELCB

6 B2 10 2.5 2.5 FCU 2 261 126 387

7 R3 20 4.0 4.0 MASTER BED ROOM 4 200 800

8 Y3 20 4.0 4.0 BED ROOM 2 200 400

9 B3 20 4.0 4.0 LIVING & DINING 4 200 800


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500

40A TPN
11 Y4 20 4.0 4.0 KITCHEN 3 200 600
ISOLATOR

12 B4 20 4.0 4.0 LAUNDRY 1 1500 1500

13 R5 SPACE 0

14 Y5 20 4.0 4.0 WATER HEATER 1 1500 1500

15 B5 20 4.0 4.0 ACP 2 50 100


40A 4P
30 mA
ELCB SPACE
16 R6 0

17 Y6 SPACE 0

18 B6 20 4.0 4.0 IRONING STORE & LOBBY 2 200 400

19 R7 4C 1C 1500

40A 4P
100 mA 20 Y7 20 X X CU-01 4500 1500 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1500

TOTAL CONNECTED LOAD: 4285 4239 4687 13.2

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-02

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 4 4 2 2 26 8 18 14 30 218

40A 4P
100 mA 2 Y1 10 2.5 2.5 LIVING & DINING 2 2 4 1 45 11 26 13 229
ELCB

3 B1 SPACE 0

4 R2 SPACE 0

40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU 2 158 81 239
ELCB

6 B2 SPACE 0

7 R3 SPACE 0

8 Y3 20 4.0 4.0 LIVING & DINING 5 200 1000

9 B3 20 4.0 4.0 KITCHEN 3 200 600


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500

40A TPN
11 Y4 20 4.0 4.0 LAUNDRY 1 1500 1500
ISOLATOR

12 B4 20 4.0 4.0 ACP 2 50 100

13 R5 20 4.0 4.0 WATER HEATER 1 1500 1500

14 Y5 SPACE 0

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
30 mA
ELCB SPACE
16 R6 0

17 Y6 SPACE 0

18 B6 20 4.0 4.0 BED ROOM 4 200 800

19 R7 4C 1C 1167

40A 4P
100 mA 20 Y7 20 X X CU-02 3500 1167 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1167

TOTAL CONNECTED LOAD: 4385 4135 4167 12.7

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-03

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 4 4 2 2 26 8 18 14 30 218

40A 4P
100 mA 2 Y1 10 2.5 2.5 LIVING & DINING 2 2 4 1 45 11 26 13 229
ELCB

3 B1 SPACE 0

4 R2 SPACE 0

40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU 2 158 81 239
ELCB

6 B2 SPACE 0

7 R3 SPACE 0

8 Y3 20 4.0 4.0 LIVING & DINING 5 200 1000

9 B3 20 4.0 4.0 KITCHEN 3 200 600


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500

40A TPN
11 Y4 20 4.0 4.0 LAUNDRY 1 1500 1500
ISOLATOR

12 B4 20 4.0 4.0 ACP 2 50 100

13 R5 20 4.0 4.0 WATER HEATER 1 1500 1500

14 Y5 SPACE 0

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
30 mA
ELCB SPACE
16 R6 0

17 Y6 SPACE 0

18 B6 20 4.0 4.0 BED ROOM 4 200 800

19 R7 4C 1C 1167

40A 4P
100 mA 20 Y7 20 X X CU-03 3500 1167 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1167

TOTAL CONNECTED LOAD: 4385 4135 4167 12.7

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-04

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 1 4 2 4 4 2 2 26 13 8 14 18 26 10 30 355

40A 4P
100 mA 2 Y1 10 2.5 2.5 MASTER BED + LIVING & DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB

3 B1 SPACE 0

4 R2 10 2.5 2.5 FCU 1 122 122

40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU 2 261 126 387
ELCB

6 B2 SPACE 0

7 R3 20 4.0 4.0 MASTER BED ROOM 4 200 800

8 Y3 20 4.0 4.0 BED ROOM 2 200 400

9 B3 20 4.0 4.0 LIVING & DINING 4 200 800


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500

40A TPN
11 Y4 20 4.0 4.0 KITCHEN 3 200 600
ISOLATOR

12 B4 20 4.0 4.0 LAUNDRY 1 1500 1500

13 R5 SPACE 0

14 Y5 20 4.0 4.0 WATER HEATER 1 1500 1500

15 B5 20 4.0 4.0 ACP 2 50 100


40A 4P
30 mA
ELCB SPACE
16 R6 0

17 Y6 SPACE 0

18 B6 20 4.0 4.0 IRONING STORE & LOBBY 2 200 400

19 R7 4C 1C 1500

40A 4P
100 mA 20 Y7 20 X X CU-04 4500 1500 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1500

TOTAL CONNECTED LOAD: 4277 4626 4300 13.2

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-05

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 5 3 1 1 1 26 8 18 13 14 30 177

40A 4P
100 mA 2 Y1 10 2.5 2.5 LIVING & DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB

3 B1 SPACE 0

4 R2 10 2.5 2.5 FCU 2 176 95 271

40A 4P
100 mA 5 Y2 SPACE 0
ELCB

6 B2 SPACE 0

7 R3 20 4.0 4.0 BED ROOM 4 200 800

8 Y3 20 4.0 4.0 LAUNDRY 1 1500 1500

9 B3 20 4.0 4.0 KITCHEN 3 200 600


40A 4P
40A TPN
30 mA
ISOLATOR
ELCB SPACE
10 R4 0

11 Y4 20 4.0 4.0 DISH WASHER 1 1500 1500

12 B4 20 4.0 4.0 LIVING & DINING 4 200 800

13 R5 20 4.0 4.0 WATER HEATER 1 1500 1500

14 Y5 20 4.0 4.0 ACP 2 50 100

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
100 mA
ELCB
16 R6 4C 1C 1167

17 Y6 20 X X CU-05 3500 1167 UVR+TIMER+CONTACTOR

18 B6 4.0 4.0 1167

TOTAL CONNECTED LOAD: 3915 4545 4067 12.5

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-06

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 1 4 2 4 4 2 2 26 13 8 14 18 26 10 30 355

40A 4P
100 mA 2 Y1 10 2.5 2.5 MASTER BED + LIVING & DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB

3 B1 SPACE 0

4 R2 SPACE 0

40A 4P
100 mA 5 Y2 10 4.0 4.0 FCU 1 230 230
ELCB

6 B2 10 4.0 4.0 FCU 2 144 86 230

7 R3 20 4.0 4.0 MASTER BED ROOM 4 200 800

8 Y3 20 4.0 4.0 BED ROOM 4 200 800

9 B3 20 4.0 4.0 IRONING STORE & LOBBY 2 200 400


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 ACP 2 50 100

40A TPN
11 Y4 20 4.0 4.0 KITCHEN 3 200 600
ISOLATOR

12 B4 20 4.0 4.0 LAUNDRY 1 1500 1500

13 R5 20 4.0 4.0 DISH WASHER 1 1500 1500

14 Y5 20 4.0 4.0 WATER HEATER 1 1500 1500

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
30 mA
ELCB
16 R6 20 4.0 4.0 LIVING & DINING 3 200 600

17 Y6 SPACE 0

18 B6 SPACE 0

19 R7 4C 1C 1500

40A 4P
100 mA 20 Y7 20 X X CU-06 4500 1500 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1500

TOTAL CONNECTED LOAD: 4855 4869 5130 14.9

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-07

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 4 4 2 2 26 8 18 14 30 218

40A 4P
100 mA 2 Y1 10 2.5 2.5 LIVING & DINING 2 2 4 1 45 11 26 13 229
ELCB

3 B1 SPACE 0

4 R2 SPACE 0

40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU 2 158 81 239
ELCB

6 B2 SPACE 0

7 R3 SPACE 0

8 Y3 20 4.0 4.0 LIVING & DINING 4 200 800

9 B3 20 4.0 4.0 KITCHEN 3 200 600


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500

40A TPN
11 Y4 20 4.0 4.0 LAUNDRY 1 1500 1500
ISOLATOR

12 B4 20 4.0 4.0 ACP 2 50 100

13 R5 20 4.0 4.0 WATER HEATER 1 1500 1500

14 Y5 SPACE 0

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
30 mA
ELCB SPACE
16 R6 0

17 Y6 SPACE 0

18 B6 20 4.0 4.0 BED ROOM 4 200 800

19 R7 4C 1C 1167

40A 4P
100 mA 20 Y7 20 X X CU-07 3500 1167 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1167

TOTAL CONNECTED LOAD: 4385 3935 4167 12.5

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-08

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 4 4 2 2 26 8 18 14 30 218

40A 4P
100 mA 2 Y1 10 2.5 2.5 LIVING & DINING 2 2 4 1 45 11 26 13 229
ELCB

3 B1 SPACE 0

4 R2 SPACE 0

40A 4P
100 mA 5 Y2 10 2.5 2.5 FCU 2 158 81 239
ELCB

6 B2 SPACE 0

7 R3 SPACE 0

8 Y3 20 4.0 4.0 LIVING & DINING 4 200 800

9 B3 20 4.0 4.0 KITCHEN 3 200 600


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 DISH WASHER 1 1500 1500

40A TPN
11 Y4 20 4.0 4.0 LAUNDRY 1 1500 1500
ISOLATOR

12 B4 20 4.0 4.0 ACP 2 50 100

13 R5 20 4.0 4.0 WATER HEATER 1 1500 1500

14 Y5 SPACE 0

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
30 mA
ELCB SPACE
13 R5 0

14 Y5 SPACE 0

15 B5 20 4.0 4.0 BED ROOM 4 200 800

16 R6 4C 1C 1167

40A 4P
100 mA 17 Y6 20 X X CU-08 3500 1167 UVR+TIMER+CONTACTOR
ELCB

18 B6 4.0 4.0 1167

TOTAL CONNECTED LOAD: 4385 3935 4167 12.5

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-09

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 1 5 2 4 4 2 2 26 13 8 14 18 26 10 30 363

40A 4P
100 mA 2 Y1 10 2.5 2.5 MASTER BED + LIVING & DINING 2 2 1 2 1 1 1 1 45 11 26 18 14 8 13 30 239
ELCB

3 B1 SPACE 0

4 R2 10 4.0 4.0 FCU 2 144 86 230

40A 4P
100 mA 5 Y2 10 4.0 4.0 FCU 1 230 230
ELCB

6 B2 SPACE 0

7 R3 20 4.0 4.0 MASTER BED ROOM 4 200 800

8 Y3 20 4.0 4.0 BED ROOM 4 200 800

9 B3 20 4.0 4.0 IRONING STORE & LOBBY 2 200 400


40A 4P
30 mA
ELCB
10 R4 20 4.0 4.0 ACP 2 50 100

40A TPN
11 Y4 20 4.0 4.0 KITCHEN 3 200 600
ISOLATOR

12 B4 20 4.0 4.0 LAUNDRY 1 1500 1500

13 R5 20 4.0 4.0 DISH WASHER 1 1500 1500

14 Y5 20 4.0 4.0 WATER HEATER 1 1500 1500

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500


40A 4P
30 mA
ELCB
16 R6 20 4.0 4.0 LIVING & DINING 3 200 600

17 Y6 SPACE 0

18 B6 SPACE 0

19 R7 4C 1C 1500

40A 4P
100 mA 20 Y7 20 X X CU-09 4500 1500 UVR+TIMER+CONTACTOR
ELCB

21 B7 4.0 4.0 1500

TOTAL CONNECTED LOAD: 5093 4869 4900 14.9

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.
PROJECT: 4B+G+15TYP.+ROOF (COMMERCIAL / RESIDENTIAL BUILDING) LOAD DISTRIBUTION SCHEDULE LOCATION: APARTMENT

DB No: DB-1F-10

FED FROM: SMDB-1F

CONNECTED LOADS / POINTS LOAD PER CIRCUIT-W


CCT ECC
RATG. MCB
RATING OF SL. CIR WIRE WIRE
OF RTG. ROOM / AREA SH EX. 13A 15 A W/H W / UNIT REMARKS
INCOMER No. No. SIZE SIZE
ELCB IN A LTG BELL FCU CU W/M D/W R Y B
mm² mm²
SO FAN S/O S/O

1 R1 10 2.5 2.5 BED ROOM 1 5 3 1 1 1 26 8 18 13 14 30 177

40A 4P
100 mA 2 Y1 10 2.5 2.5 LIVING & DINING 2 2 4 1 1 1 45 11 26 18 14 30 278
ELCB

3 B1 SPACE 0

4 R2 10 2.5 2.5 FCU 2 176 95 271

40A 4P
100 mA 5 Y2 SPACE 0
ELCB

6 B2 SPACE 0

7 R3 20 4.0 4.0 BED ROOM 4 200 800

8 Y3 20 4.0 4.0 LAUNDRY 1 1500 1500

9 B3 20 4.0 4.0 KITCHEN 3 200 600


40A 4P
40A TPN
30 mA
ISOLATOR
ELCB SPACE
10 R4 0

11 Y4 20 4.0 4.0 DISH WASHER 1 1500 1500

12 B4 20 4.0 4.0 LIVING & DINING 4 200 800

13 R5 20 4.0 4.0 WATER HEATER 1 1500 1500

40A 4P
30 mA 14 Y5 20 4.0 4.0 ACP 2 50 100
ELCB

15 B5 20 4.0 4.0 WATER HEATER 1 1500 1500

16 R6 4C 1C 1167

40A 4P
100 mA 17 Y6 20 X X CU-10 3500 1167 UVR+TIMER+CONTACTOR
ELCB

18 B6 4.0 4.0 1167

TOTAL CONNECTED LOAD: 3915 4545 4067 12.5

CABLE SIZE:4C-10mm2 CU.XLPE/SWA/LSZH,CU+1C-10mm2


CABLE SIZE: 4Core LSZH,CU ECC C.FAN = Ceiling Fan. EX. FAN = Exhaust Fan, SH, S/O = Shaver socket outlet DW=Dish washer

W/H = Water Heater, H/D = Hand Dryer, W= Window type & S= Split type.