CONSULTANT:MODULE ENGINEERING
FED FROM: MDB LOCATION : TYPICAL FLOOR , ELEC RM
CONSULTANTS
PVC/ ECC
CIRCUIT/ SP/ RATING-AMPS FAULT CABLE SIZE CONNECTED LOAD-kW
XLPE SIZE
FEEDER DUTY IC,
TP F/S MCCB SWA/ 2/4x 2/3/4C R-PH Y-PH B-PH TOTAL 1-PH 3-PH REMARKS
DB No. kA mm2
MCB
OUTGOING:
DB-101 TP 63 25 XLPE/SWA/PVC 4CX25 1C X16 8.065 6.095 7.825 21.985 1
DB-102 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 4.800 4.495 4.700 13.995 1
DB-103 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 6.465 7.570 7.310 21.345 1
DB-104 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 6.565 7.570 7.075 21.21 1
DB-105 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 4.900 5.530 5.420 15.85 1
DB-106 TP 63 25 XLPE/SWA/PVC 4CX25 1C X16 8.305 7.745 7.695 23.745 1
TEL: ..............................................................
Type of Meter (Rating of Incomer) (2) UP to 60 A(1 Phase)
(3) 125 - 160 A
FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 106
1 R1 10 2.5 2.5 LOBBY & TOILET & LAUNDRY & CORRIDOR 6\1 1 1 35\100 445
5 Y2 10 2.5 2.5 BED RM 1 & BATH & BALCONY 1\3\1 1 50\35\100\200 290
6 B2 10 2.5 2.5 BED RM 2 & BATH & BALCONY 1\2\1\2 1 50\35\100\200 295
21 B7 SPACE FRIDGE
22 R8 SPACE
27 B9 SPACE
63A 28 R10 20 4.0 4.0 T-06BFCU (BED RM2&BED RM3) 1 240 240
100mA 4P
ELCB 29 Y10 32 6.0 6.0 T-06A(LIV&LIT&LOBBY) 1 3000 3000 UVR+TIMER
SEC. 6
30 B10 SPACE
63A 34 R12 32 6.0 6.0 T-06B(BED RM2&BED RM3) 1 3000 3000 UVR+TIMER
100mA 4P
ELCB 35 Y12 SPACE
SEC. 8
36 B12 20 4.0 4.0 T-06CFCU( TV&BED1&LAN&MAID) 1 300 300
1 X 4/C- 25 mm2 XLPE/SWA/PVC + CL / Ø 8305 7745 7695 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 8.305 7.745 7.695 kW
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 23.745 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 105
SEC. 2
11 Y4 16 4.0 4.0 BED RM & BATH 1 200 200
18 B6 SPACE
40A 22 R8 SPACE
100mA 4P
ELCB 23 Y8 SPACE
SEC. 5
24 B8 32 6.0 6.0 T-05B(BED&MAID) 1 3000 3000 UVR+TIMER
1 X 4/C- 16 mm2 XLPE/SWA/PVC + CL / Ø 4900 5530 5420 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 4.9 5.53 5.42 kW
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 15.850 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 104
1 R1 10 2.5 2.5 KITCHEN & LOBBY & CORRIDOR & BATH 4\2\1 1 1 35/100 575
40A 3 B1 10 2.5 2.5 BED RM1 & BATH 1\1\1 50\35 120
100mA 4P
ELCB
SEC. 1 4 R2 10 2.5 2.5 M.BED RM & DRESS & BATH 3\1\1 1 50\35\100 290
5 Y2 10 2.5 2.5 TV RM 2 35 70
40A 30mA 9 B3 16 4.0 4.0 BED RM1 & BATH 1 200 200
4P
ELCB
SEC. 2 10 R4 16 4.0 4.0 M.BED RM & DRESS & BATH 1 200 200
14 Y5 SPACE
4P
ELCB
SEC. 3 16 R6 SPACE
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 21.210 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 103
1 R1 10 2.5 2.5 KITCHEN & LOBBY & CORRIDOR & BATH 4\2\1 1 2 1 35\100 775
40A 1
3 B1 10 2.5 2.5 BED RM1 & BATH 2\1\1 50\35\100 255
100mA 4P
ELCB
SEC. 1 4 R2 10 2.5 2.5 BED RM2 & DRESS & BATH 3\1\1 50\35\100 190
5 Y2 10 2.5 2.5 TV RM 2 35 70
40A 30mA
9 B3 16 4.0 4.0 BED RM1 & BATH 1 200 200
4P
ELCB
SEC.2 10 R4 16 4.0 4.0 BED RM2 & DRESS & BATH 1 200 200
40A 30mA 1
40A TPN ISOLATOR
18 B6 SPACE
22 R8 SPACE
40A
100mA 4P
ELCB 23 Y8 20 4.0 4.0 T-03A FCU (LIV&KIT&LOBBY) 1 300 300
SEC. 5
24 B8 32 6.0 6.0 T-03A (LIV&KIT&LOBBY) 1 3000 3000 UVR+TIMER
28 R10 SPACE
40A
100mA 4P
ELCB 29 Y10 32 6.0 6.0 T-03C(TV&AMID&LOBBY) 1 3000 3000 UVR+TIMER
SEC. 7
30 B10 20 4.0 4.0 T-03CFCU (TV&AMID&LOBBY) 1 300 300
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 21.345 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 102
SEC. 2
11 Y4 16 4.0 4.0 BED RM & BATH 1 200\400 200
12 B4 SPACE
14 Y5 SPACE
40A 30mA
4P 15 B5 SPACE
ELCB
16 R6 20 4.0 4.0 LAUNDRY 1 1500 1500
SEC. 3
17 Y6 SPACE
40A 19 R7 SPACE
100mA 4P
20 Y7 20 4.0 4.0 T-02A FCU (LIV&KIT) 1 300 300
ELCB
SEC. 4
21 B7 32 6.0 6.0 T-02A (LIV&KIT) 1 3000 3000 UVR+TIMER
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 13.995 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 101
1 R1 10 2.5 2.5 LOBBY & TOILET & LAUNDRY 6\1 1 1 35\100 445
6 B2 10 2.5 2.5 BED RM 2 & BATH & BALCONY 1\3\1\1 1 50\35\100 325
63A 30mA 22 R8 20 4.0 4.0 MAID RM BATH 1 1500 1500 WATER HEATER
4P
ELCB 23 Y8 SPACE
SEC. 8
24 B8 SPACE
63A 28 R10 20 4.0 4.0 T-01B FCU (BED RM 1&BED RM 2) 1 300 300
100mA 4P
ELCB 29 Y10 32 6.0 6.0 T-01B(BED RM 1&BED RM 2) 1 3000 3000 UVR+TIMER
SEC. 10
30 B10 20 4.0 4.0 T-01 C FCU (TV&MAID&LAN) 1 300 300
1 X 4/C- 25 mm2 XLPE/SWA/PVC + CL / Ø 8065 6095 7825 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 8.065 6.095 7.825 kW
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 21.985 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-SR CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: 1ST FLOOR - ELECTIRCAL RM
100mA
4P 8 Y3 10 2.5 2.5 ELECTRICAL RM 3 100 300 1ST,2ND,3RD
ELCB
SEC. 2 9 B3 10 2.5 2.5 GARBAGE RM 3 50 150 1ST,2ND,3RD
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized
TCL 13.800 kW
Smoke Fire Damper,FLEX OUT= For systems modules.
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND
FED FROM: SMDB-SR CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: 4TH FLOOR - ELECTIRCAL RM
4TH,5TH,6TH,7TH
13 R5 32 4.0 4.0 ELECTRICAL RM 4 200 800
40A FLOOR ,RING CIRCUIT
30mA 4P 4TH,5TH,6TH,7TH
14 Y5 32 4.0 4.0 GARBAGE RM 4 200 800
ELCB FLOOR ,RING CIRCUIT
SEC. 4 4TH,5TH,6TH,7TH
15 B5 32 4.0 4.0 CORRIDOR 4 200 800
FLOOR ,RING CIRCUIT
T-07 4TH F
16 R6 32 6.0 6.0 1 3000 3000 UVR+TIMER
(CORR&ELEC&TELE)
40A
100mA T-07 FCU 4TH F
4P 17 Y6 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)
ELCB
SEC. 5 T-07 5TH F
18 B6 32 6.0 6.0 1 3000 3000 UVR+TIMER
(CORR&ELEC&TELE)
19 R7 SPACE
40A
100mA T-07 6TH F
20 Y7 32 6.0 6.0 1 3000 3000 UVR+TIMER
4P (CORR&ELEC&TELE)
ELCB
SEC. 6 T-07 FCU 6TH F
21 B7 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)
T-07 7TH F
40A 22 R8 32 6.0 6.0 1 3000 3000
(CORR&ELEC&TELE)
100mA
4P T-07 FCU 7TH F
ELCB 23 Y8 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)
SEC. 7
24 B8 SPACE
1 X 4/C- 16 mm2 XLPE/SWA/PVC + CL / Ø 7850 5450 5040 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 7.85 5.45 5.04 kW
LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized
TCL 18.340 kW
Smoke Fire Damper,FLEX OUT= For systems modules.