DETAILS OF CONNECTED LOAD MAX.

DEMAND

PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
PARK,DUBAI.
CONSULTANT : Ecogreen Arch& Engg. LOCATIO COMPOUND WALL
DESIGNATION : LOAD SUMMARY FED FROM : DEWA PLOT: 597-1203
CIRCUIT RATING -AMPS FAULT PVC / CABLE SIZE ECC CONNECTED LOAD (kW) KWH METER
FEEDER SP TP ISO MCCB ACB DUTY XLPE 2/4 x 1C 2/3/4C SIZE 1C R-PHASE Y-PHASE B-PHASE TOTAL 1-F 3F 3-F CT REMARKS
DB NO. DOT kA SWA/PVC MM2 MM2 MM2 (kW) (kW) (kW) KW (1) (2) (3) (4)

INCOMER 107.63 107.85 107.51 323.00

OUTGOING:-
METER CABINET-01 TP 350 50 XLPE DEWA 1C,120 57.63 57.85 57.51 173.00 1
METER CABINET-02 TP 300 50 XLPE DEWA 1C,95 50.00 50.00 50.00 150.00 1

DEWA AND GENERATOR INCOMMING BREAKERS ARE ELECTRICALY AND MECHANICALY INTERLOCKED

MAIN KWH METER IS INTEGRAL PART OF TRANSFORMER.


KWH METER IS PROVIDED IN LV PANEL AS DEWA CHECK METER

NOTE:- TOTAL CONNECTED LOAD PER PHASE 107.63 107.85 107.51 323.00 2

ENSURE THAT F/S DOES NOT ALLOW


REPLACEMENT OF FUSE RATED HIGHER THAN TOTAL 107.63 107.85 107.51 323.00
THAT 'SPECIFIED FOR' THE CIRCUIT CABLES MAX. DEMAND AT 0.9 DIVERSITY 323.00
MAX. DEMAND 3 PHASE IN KW
PROVIDE CT-METER ABOVE MAX. DEMAND > 160A/80kW

(1) 60 A (2) 100 A (3) 125-160 A (4) 400 / 5A


Net Max. Demand 290.70
DETAILS OF CONNECTED LOAD MAX. DEMAND

OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C


PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI.
CONSULTANT : Ecogreen Arch& Engg.
DESIGNATION : MDB-01 FED FROM : METER CABINET-01 PLOT: 597-1203
CIRCUIT RATING -AMPS FAULT PVC / CABLE SIZE ECC CONNECTED LOAD (kW) KWH METER
FEEDER SP TP ISO MCCB ACB DUTY XLPE 2/4 x 1C 2/3/4C SIZE 1C R-PHASE Y-PHASE B-PHASE TOTAL 1-F 3F 3-F CT REMARKS
DB NO. N/A DOT kA SWA/PVC MM2 MM2 MM2 (kW) (kW) (kW) KW (1) (2) (3) (4)
INCOMER TP 350 50 XLPE 4C,240 1C,120 57.63 57.85 57.51 173.00
OUTGOING:-
DB-GF-P TP 40 35 XLPE 4C,10 1C,10 3.40 3.20 3.40 10.00
DB-GF-L TP 40 35 XLPE 4C,10 1C,10 7.58 7.09 7.33 22.00
DB-GF-AC TP 63 35 XLPE 4C,16 1C,16 7.90 7.40 7.70 23.00
DB-FF-AC TP 100 35 XLPE 4C,35 1C,25 14.53 14.23 14.23 43.00
DB-FF TP 63 35 XLPE 4C,16 1C,16 8.32 9.88 8.80 27.00
DB-TEL TP 32 35 XLPE 4C,10 1C,10 1.62 1.67 1.72 5.00
DB-PUMP TP 32 35 XLPE 4C,10 1C,10 1.62 1.72 1.67 5.00
CARGO LIFT TP 32 35 XLPE 4C,6 1C,6 2.67 2.67 2.67 8.00 300 mA 4P ELCB
LIFT TP 32 35 XLPE 4C,6 1C,6 2.67 2.67 2.67 8.00 300 mA 4P ELCB
SMOKE VENT. FAN CONTROL PANEL TP 32 35 XLPE 4C,6 1C,6 2.67 2.67 2.67 8.00
SPARE TP 40 35 4.67 4.67 4.67 14.00
CAP BANK TP 125 35 XLPE 4C,50 1C,25 50 KVAR
NOTE:- TOTAL CONNECTED LOAD PER PHASE
57.63 57.85 57.51 173.00
SHEET 1 OF 1
ENSURE THAT F/S DOES NOT ALLOW
REPLACEMENT OF FUSE RATED HIGHER THAN
THAT 'SPECIFIED FOR' THE CIRCUIT CABLES

PROVIDE CT-METER ABOVE MAX. DEMAND > 160A/80kW

(1) 20 - 30 A (2) 30 - 90 A (3) 100 - 200 A (4) 2500 / 5A


DETAILS OF CONNECTED LOAD MAX. DEMAND

OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C


PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI.
CONSULTANT : Ecogreen Arch& Engg.
DESIGNATION : MDB-02 FED FROM : METER CABINET-02 PLOT: 597-1203
CIRCUIT RATING -AMPS FAULT PVC / CABLE SIZE ECC CONNECTED LOAD (kW) KWH METER
FEEDER SP TP ISO MCCB ACB DUTY XLPE 2/4 x 1C 2/3/4C SIZE 1C R-PHASE Y-PHASE B-PHASE TOTAL 1-F 3F 3-F CT REMARKS
DB NO. N/A DOT kA SWA/PVC MM2 MM2 MM2 (kW) (kW) (kW) KW (1) (2) (3) (4)
INCOMER TP 300 50 XLPE 4C,185 1C,95 50.00 50.00 50.00 150.00
OUTGOING:-
SMDB-MC TP 200 35 XLPE 4C,95 1C,50 33.33 33.33 33.33 100.00
FIRE PUMP TP 125 35 XLPE 4C,50 1C,25 13.33 13.33 13.33 40.00 ELS+ALARM
SPARE TP 32 35 3.33 3.33 3.33 10.00

CAP BANK TP 125 35 XLPE 4C,50 1C,25 45 KVAR


NOTE:- TOTAL CONNECTED LOAD PER PHASE
50.00 50.00 50.00 150.00
SHEET 1 OF 1
ENSURE THAT F/S DOES NOT ALLOW
REPLACEMENT OF FUSE RATED HIGHER THAN
THAT 'SPECIFIED FOR' THE CIRCUIT CABLES

PROVIDE CT-METER ABOVE MAX. DEMAND > 160A/80kW

(1) 20 - 30 A (2) 30 - 90 A (3) 100 - 200 A (4) 2500 / 5A


DETAILS OF CONNECTED LOAD MAX. DEMAND

OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C


PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI.
CONSULTANT : Ecogreen Arch& Engg.
DESIGNATION : SMDB-MC FED FROM : MDB-02 PLOT: 597-1203
CIRCUIT RATING -AMPS FAULT PVC / CABLE SIZE ECC CONNECTED LOAD (kW) KWH METER
FEEDER SP TP ISO MCCB ACB DUTY XLPE 2/4 x 1C 2/3/4C SIZE 1C R-PHASE Y-PHASE B-PHASE TOTAL 1-F 3F 3-F CT REMARKS
DB NO. N/A DOT kA SWA/PVC MM2 MM2 MM2 (kW) (kW) (kW) KW (1) (2) (3) (4)
INCOMER TP 200 35 XLPE 4C,95 1C,50 33.33 33.33 33.33 100.00
OUTGOING:-

ISO FOR PANIT BOOTH TP 40 25 XLPE 4C,10 1C,10 3.83 3.83 3.83 11.50 100 mA 4P ELCB
ISO FOR PANIT BOOTH TP 40 25 XLPE 4C,10 1C,10 3.83 3.83 3.83 11.50 100 mA 4P ELCB
ISO FOR PANIT BOOTH TP 63 25 XLPE 4C,16 1C,16 4.00 4.00 4.00 12.00 100 mA 4P ELCB
ISO FOR COMPRESSOR TP 40 25 XLPE 4C,10 1C,10 3.33 3.33 3.33 10.00 100 mA 4P ELCB
ISO FOR DUST COLLECTOR TP 40 25 XLPE 4C,10 1C,10 3.33 3.33 3.33 10.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB
ISO FOR WOOD FINING MACHINES TP 20 25 XLPE 4C,6 1C,6 1.00 1.00 1.00 3.00 100 mA 4P ELCB

SPARE TP 40 25 5.00 5.00 5.00 15.00


NOTE:- TOTAL CONNECTED LOAD PER PHASE
33.33 33.33 33.33 100.00
SHEET 1 OF 1
ENSURE THAT F/S DOES NOT ALLOW
REPLACEMENT OF FUSE RATED HIGHER THAN
THAT 'SPECIFIED FOR' THE CIRCUIT CABLES

PROVIDE CT-METER ABOVE MAX. DEMAND > 160A/80kW

(1) 20 - 30 A (2) 30 - 90 A (3) 100 - 200 A (4) 2500 / 5A


LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-GF-P Sheet 1 of 1
Fed From MDB-01 Location GROUND FLOOR ELE. ROOM
CCT ECC LOAD PER CIRCUIT
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE IN KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhaus
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O t
1 R1 32 4.0 4.0 STORAGE 4 400 1600 RING

Sec 1
2 Y1 32 4.0 4.0 STORAGE & GARBAGE 4 400 1600 RING
40A,4P 3 B1 32 4.0 4.0 SHOW ROOM 4 400 1600 RING
30mA 4 R2 20 4.0 4.0 SHOW ROOM 2 400 800
ELCB
5 Y2 20 4.0 4.0 2 400 800
40A TP ISO

FACTORY
6 B2 32 4.0 4.0 FACTORY 3 400 1200 RING
7 R3 20 4.0 4.0 PAINT BOOTH 2 400 800
Sec 2
8 Y3 20 4.0 4.0 FACTORY 2 400 800
40A,4P 9 B3 20 4.0 4.0 FACTORY 1 200 200 CMP PANEL
30mA 10 R4 20 4.0 4.0 FACTORY 1 200 200 FACP
ELCB
11 Y4 SPACE
12 B4 20 SPARE 400 400
CABLE SIZE : 4C,10 sq mm XLPE/SWA/Cu/PVC + 1C,10 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 3400 3200 3400
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 10.00 KW
LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-GF-L Sheet 1 of 1
Fed From MDB-01 Location GROUND FLOOR ELE.ROOM
CCT ECC LOAD PER CIRCUIT
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE IN KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhaus
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O t
1 R1 10 2.5 2.5 ELECTRICAL ROOM 1 50 50
Sec 1
2 Y1 10 2.5 2.5 STORAGE & GARBAGE 8 50 400
40A,4P 3 B1 10 2.5 2.5 STORAGE 8 2 50 ,40 480
100mA 4 R2 10 2.5 2.5 FINISHED & PAINT BOOTH 14 50 700
ELCB
5 Y2 SPACE
6 B2 10 2.5 2.5 SHOW ROOM 6 150 900
7 R3 SPACE 0.0
Sec 2
8 Y3 10 2.5 2.5 SHOW ROOM 5 150 750
40A,4P 9 B3 10 2.5 2.5 NEAR ENTRANCE 58 5 290 EMERGENCY LIGHT
100mA 10 R4 SPACE 0.0
ELCB
11 Y4 10 2.5 2.5 SHOW ROOM 5 150 750
12 B4 10 2.5 2.5 SHOW ROOM 4 150 600
13 R5 10 2.5 2.5 SHOW ROOM 3 300 900
Sec 3
14 Y5 10 2.5 2.5 SHOW ROOM 3 300 900
40A,4P 15 B5 10 2.5 2.5 SHOW ROOM 3 300 900
100mA 16 R6 10 2.5 2.5 SHOW ROOM 3 300 900
ELCB
17 Y6 10 2.5 2.5 3 300 900
40A TP ISO

SHOW ROOM
18 B6 10 2.5 2.5 SHOW ROOM 3 300 900
19 R7 10 2.5 2.5 SHOW ROOM 3 300 900
Sec 4
20 Y7 SPACE
40A,4P 21 B7 10 2.5 2.5 EXTERNAL 10 10 100
100mA 22 R8 10 3C X 4 mm EXTERNAL 10 10 100
ELCB
23 Y8 10 3C X 4 mm EXTERNAL 11 10 110
24 B8 10 2.5 2.5 STAIR 4 10 40
25 R9 10 2.5 2.5 STAIR 3 10 30
Sec 5
26 Y9 20 4.0 4.0 TOILET 1 300 300 EXF-01
40A,4P 27 B9 10 2.5 2.5 EXTERNAL 12 10 120
100mA 28 R10 20 4.0 4.0 CHECK POINT 1 2000 2000 ROLL UP SHUTTER
ELCB
29 Y10 20 4.0 4.0 CHECK POINT 1 2000 2000 ROLL UP SHUTTER
30 B10 10 2.5 2.5 EXTERNAL 1 1000 1000 POWER PROVISION
31 R11 20 4.0 4.0 NEAR SECURITY BOOTH 1 2000 2000 ROLL UP SHUTTER

Sec 6
32 Y11 20 SPARE 240 240
40A,4P 33 B11 20 4.0 4.0 FACTORY 1 2000 2000 ROLL UP SHUTTER
100mA 34 R12 SPACE 0
ELCB
35 Y12 20 SPARE 740 740.0
36 B12 SPACE 0
CABLE SIZE : 4C,10 sq mm XLPE/SWA/Cu/PVC + 1C,10 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 7580 7090 7330
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 22.00 KW
LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-GF-AC Sheet 1 of 1
Fed From MDB-01 Location GROUND FLOOR ELE.ROOM
CCT ECC LOAD PER CIRCUIT
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE IN KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhaus
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O t
1 R1 20 4.0 4.0 CHECK POINT 1 100 100 GAC-01

Sec 1
2 Y1 20 4.0 4.0 CHECK POINT 1 1700 1700 GAC-01
40A,4P 3 B1 20 4.0 4.0 FINISHED GOODS 1 200 200 GAC-02
100mA 4 R2 32 4.0 4.0 FINISHED GOODS 1 3700 3700 GAC-02
ELCB
5 Y2 20 4.0 4.0 GARBAGE 1 100 100 GAC-03
6 B2 20 4.0 4.0 GARBAGE 1 1700 1700 GAC-03
7 R3 20 4.0 4.0 STORE/ELE/TEL 1 200 200 GAC-04

Sec 2
8 Y3 20 4.0 4.0 SHOWROOM 1 300 300 GAC-5A
40A,4P 9 B3 20 4.0 4.0 SHOWROOM 1 300 300 GAC-5A
100mA 10 1233
ELCB
11 RYB4 20 4.0 4.0 STORE/ELE/TEL (GAC-04) 1 3700 1233 UVR+CON.+TIMER
63A TP ISO

12 1233
13 1333
Sec 3
14 RYB5 20 4.0 4.0 STORE/ELE/TEL (GAC-5A) 1 4000 1333 UVR+CON.+TIMER
40A,4P 15 1333
100mA 16 1333
ELCB
17 RYB6 20 4.0 4.0 STORE/ELE/TEL (GAC-5B) 1 4000 1333 UVR+CON.+TIMER
18 1333
19 R7 SPACE

Sec 4
20 Y7 20 SPARE 1400 1400
40A,4P 21 B7 20 SPARE 900 900
100mA 22 R8 SPACE
ELCB
23 Y8 SPACE 0
24 B8 20 SPARE 700 700
CABLE SIZE : 4C,16 sq mm XLPE/SWA/Cu/PVC + 1C,16 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 7900 7400 7700
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 23.00 KW
LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-FF-AC Sheet 1 of 1
Fed From MDB-01 Location FIRST FLOOR
CCT ECC LOAD PER CIRCUIT IN
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhau
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O st
1 R1 20 4.0 4.0 STORE 1 300 300 FAC-1A

Sec 1
2 Y1 20 4.0 4.0 STORE 1 300 300 FAC-1B
40A,4P 3 B1 20 4.0 4.0 STORE 1 300 300 FAC-1C
100mA 4 R2 20 4.0 4.0 STORE 1 300 300 FAC-1D
ELCB
5 Y2 20 4.0 4.0 OFFICE 1 300 300 FAC-2A
6 B2 20 4.0 4.0 OFFICE 1 300 300 FAC-2B
7 R3 20 4.0 4.0 OFFICE 1 300 300 FAC-3A

Sec 2
8 Y3 20 4.0 4.0 OFFICE 1 300 300 FAC-3B
40A,4P 9 B3 20 4.0 4.0 OFFICE 1 300 300 FAC-3C
100mA 10 R4 20 4.0 4.0 PANTRY/DINING 1 300 300 FAC-04
ELCB
11 Y4 SPACE
12 B4 SPACE
13 1333
Sec 3
14 RYB5 20 4.0 4.0 FAC-01A 1 4000 1333 UVR+CON.+TIMER
40A,4P 15 1333
100mA 16 1333
ELCB
17 RYB6 20 4.0 4.0 FAC-01B 1 4000 1333 UVR+CON.+TIMER
18 1333
19 1333
100A TP ISO

Sec 4
20 RYB7 20 4.0 4.0 FAC-01C 1 4000 1333 UVR+CON.+TIMER
40A,4P 21 1333
100mA 22 1333
ELCB
23 RYB8 20 4.0 4.0 FAC-01D 1 4000 1333 UVR+CON.+TIMER
24 1333
25 1333
Sec 5
26 RYB9 20 4.0 4.0 FAC-02A 1 4000 1333 UVR+CON.+TIMER
40A,4P 27 1333
100mA 28 1333
ELCB
29 RYB10 20 4.0 4.0 FAC-02A 1 4000 1333 UVR+CON.+TIMER
30 1333
31 1333
Sec 6
32 RYB11 20 4.0 4.0 FAC-03A 1 4000 1333 UVR+CON.+TIMER
40A,4P 33 1333
100mA 34 1333
ELCB
35 RYB12 20 4.0 4.0 FAC-03B 1 4000 1333 UVR+CON.+TIMER
36 1333
37 1333
Sec 7
38 RYB13 20 4.0 4.0 FAC-03C 1 4000 1333 UVR+CON.+TIMER
40A,4P 39 1333
100mA 40 1333
ELCB
41 RYB14 20 4.0 4.0 FAC-04 1 4000 1333 UVR+CON.+TIMER
42 1333
CABLE SIZE : 4C,35 sq mm XLPE/SWA/Cu/PVC + 1C,25 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 14533 14233 14233
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 43.00 KW
LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-FF Sheet 1 of 1
Fed From MDB-01 Location FIRST FLOOR
CCT ECC LOAD PER CIRCUIT
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE IN KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhaus
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O t
1 R1 10 2.5 2.5 STAFF /PANTRY 6 40 240
Sec 1
2 Y1 10 2.5 2.5 OFFICE 9 40 360
40A,4P 3 B1 10 2.5 2.5 STORAGE 9 50 450
100mA 4 R2 10 2.5 2.5 TERRACE 4 10 40
ELCB
5 Y2 10 2.5 2.5 OFFICE 8 40 320
6 B2 10 2.5 2.5 STORAGE 5 50 250
7 R3 10 2.5 2.5 TOILET 13 4 15 ,10 235
Sec 2
8 Y3 10 2.5 2.5 STORE 7 50 350
100A,4P 9 B3 20 2.5 2.5 STORE 5 50 250
30mA 10 R4 20 4.0 4.0 TOILET 1 300 300 EXF-02
ELCB
11 Y4 10 2.5 2.5 STORE 7 50 350
12 B4 20 2.5 2.5 STORE 5 50 250
13 R5 32 4.0 4.0 OFFICE 4 400 1600 RING
14
63A TP ISO

Sec 3
Y5 32 4.0 4.0 OFFICE 4 400 1600 RING
40A,4P 15 B5 20 4.0 4.0 STORE 2 400 800
30mA 16 R6 20 SPARE 1000 1000
ELCB
17 Y6 20 4.0 4.0 TOILET 1 500 500 HAND DRAYER
18 B6 32 4.0 4.0 OFFICE 3 400 1200 RING
19 R7 20 4.0 4.0 STORE 2 400 800
Sec 4
20 Y7 32 4.0 4.0 STAFF PANTRY 1 2000 2000 WATER HEATER
40A,4P 21 B7 32 4.0 4.0 OFFICE 4 400 1600 RING
30mA 22 R8 32 4.0 4.0 OFFICE 4 400 1600 RING
ELCB
23 Y8 32 4.0 4.0 TOILET 1 2000 2000 WATER HEATER
24 B8 32 4.0 4.0 STORE 3 400 1200 RING
25 R9 20 SPARE 2000 2000
Sec 5
26 Y9 20 4.0 4.0 STORE 2 400 800
40A,4P 27 B9 32 4.0 4.0 STAFF PANTRY 3 400 1200 RING
30mA 28 R10 20 4.0 4.0 STAFF PANTRY 1 500 500 OVEN
ELCB
29 Y10 32 4.0 4.0 OFFICE 4 400 1600 RING
30 B10 32 4.0 4.0 OFFICE 4 400 1600 RING
CABLE SIZE : 4C,16 sq mm XLPE/SWA/Cu/PVC + 1C,16 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 8315 9880 8800
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 27.00 KW
LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-TEL Sheet 1 of 1
Fed From MDB-01 Location GROUND FLOOR TELEPHONE ROOM
CCT ECC LOAD PER CIRCUIT
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE IN KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhaus
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O t
1 R1 10 2.5 2.5 TEL ROOM 1 50 50
Sec 1
2 Y1 SPACE 0.0
40A,4P 3 B1 10 SPARE 900 900
100mA 4 R2 10 SPARE 100 100
ELCB
5 Y2 10 200 200
32A TP ISO

SPARE
6 B2 10 SPARE 150 150
7 R3 20 4.0 4.0 TEL ROOM 2 400 800
Sec 2
8 Y3 20 4.0 4.0 TEL ROOM 2 400 800
40A,4P 9 B3 SPACE 0.0
30mA 10 667
ELCB
11 RYB4 20 4.0 4.0 TEL ROOM 1 2000 667
12 667
CABLE SIZE : 4C,10 sq mm XLPE/SWA/Cu/PVC + 1C,10 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 1617 1667 1717
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 5.00 KW
LOAD DISTRIBUTION SCHEDULE
Project PROPOSED G+1 WAREHOUSE ON PLOT NO 597-1203 AT INVESTMENTS PARK,DUBAI. OWNER : M/S TURNKEY PLUSE CONTRACTING L.L.C
Consultant : Ecogreen Arch& Engg. Plot No 597-1203
DB No. DB-PUMP Sheet 1 of 1
Fed From MDB-01 Location PUMP ROOM
CCT ECC LOAD PER CIRCUIT
RATING MCB CONNECTED LOADS/POINTS
RATING OF WIRE WIRE IN KW
OF CIRCUIT RATING ROOM (OR) AREA REMARKS
INCOMER SL.NO SIZE SIZE MIR 13A 13 A Exhaus
ELCB NO IN AMP LTG LTG W/H H/D AC 15 A ISO W/UNIT R Y B
SQ.MM SQ.MM ROR S/O D/O t
1 R1 10 2.5 2.5 PUMP ROOM 3 50 150
Sec 1
2 Y1 SPACE
40A,4P 3 B1 20 4.0 4.0 SUMP PUMP 1 1000 1000 ELS+ALARM
100mA 4 667
ELCB
5 RYB2 20 4.0 4.0 BOOSTER PUMP 1 2000 667
32A TP ISO

6 667
7 R3 20 4.0 4.0 PUMP ROOM 2 400 800
Sec 2
8 Y3 20 SPARE 800 800
40A,4P 9 B3 SPACE
30mA 10 R4 SPACE
ELCB
11 Y4 20 SPARE 250 250
12 B4 SPACE
CABLE SIZE : 4C,10 sq mm XLPE/SWA/Cu/PVC + 1C,10 sq mm PVC as ECC TOTAL FOR SHEET 1 of 1 1617 1717 1667
NOTE:- ALL LED LIGHTS PROPOSED WHERE EVER APPLICABLE
TOTAL CONNECTED LOAD 5.00 KW