FAULT 3
SHORT CIRCUIT ANALYSIS A. FAULT 1
f - FACTOR:
KVA
IFLA = 1.73 (L) (ISC2)
SINGLE LINE DIAGRAM 1.73 x V f =
(C) (N) (V)
3 X 75 X 1000 VA
IFL = = 565.468 A 1.73 (32.8) (11940)
1.73 X 230 f =
UTILITY (3826) (3) (230)
M- FACTOR: f = 0.2566
100 M- FACTOR:
M= 1
3-75KVA %Z M=
TRANSFORMER
6.6KV / 0.23KV 100 1+f
%Z = 4.4%
M= = 22.72
4.4 M= 0.7958
FAULT 1
ISC1 = 565.468 A x 22.72 = 12847.43 AMPS
Isc3 = M x ISC1
Isc3 = 0.7958 (12847.43)
B. FAULT 2
4 sets 3-250mm² THHN 300KCMIL
Isc3 =
CU UNDER GROUND 65.62 FEET f - FACTOR: 10223.98 AMPS
NON MAGNETIC CONDUIT
1.73 (L) (ISC1)
225KVA f =
GENSET
(C) (N) (V)
240V, 3Ø , 60HZ 600 AT MCCB, ATS MOTOR CONTRIBUTION
1.73 (65.62) (12847.43)
f =
(20868) (4) (230) IFL x 4 = 2261.872
f = 0.07596
FAULT 2 @FAULT 1
3-22mm² THHN M- FACTOR:
NON MAGNETIC CONDUIT 1 ISC1 + 2261.872 = 15109.302 AMPS
M=
4 AWG 1+f
32.8 FEET @FAULT 2
FAULT 3 M= 0.9294
L ISC2 + 2261.872 = 14201.872 AMPS
100 AT MCCB ISC2 = M x ISC1
@FAULT 3
ISC2 = 0.9294 (12847.43)
M ELEVATOR MOTOR
ISC3 + 2261.872 = 12485.852 AMPS
ISC2 = 11940 AMPS