PROJECT : M/s.

CPWD, ANANTHAPUR
CLIENT : M/s. CPWD
CONTRACTOR : M/s. KMV

SHORT CIRCUIT CALCULATION


INPUT DATA:

Voltage rating of Transformer = 11kV/433V


% Impedance (Z) = 4.26 %
Short Circuit Fault level = 50 kA for 1SEC
Transformer Capacity (kVA) = 500 kVA
Secondary Line to Line Voltage (V) = 433 V

TO FIND :
The following Busbar will be withstand for 50 kA Short circuit Fault Level
Full load current I(F.L.A) = 666.7057801 A
Multiplier(M) = 23.4741784
Transformer Short Circuit Current, I(S.C) = 15.65037042 kA

FORMULA:
3 PHASE TRANSFORMER
TO CALCULATE SHORT CIRCUIT CURRENT [ I (S.C) ]

kVA X 1000
(i) 3 PHASE TRANSFORMER => I (F.L.A) = (Ampere)
E(L-L) X 1.732

100
(ii) MULTIPLIER , M =
%Z Transformer

(iii) TRANSFORMER SHORT CIRCUIT CURRENT, I(S.C) = I (F.L.A) X MULTIPLIER (M) (Ampere)

PPD:AKN CKD:RGN