VOLTAGE DROP CALCULATION

BRANCH CIRCUIT USED: CIRCUIT NO. 1 OF PP1 CONVENIENCE OUTLET

BRANCH CIRCUIT USED: CIRCUIT NO. 1 OF PP1 CONVENIENCE OUTLET


88.98 ft. 159.74 ft.

For Service Entrance For Branch Circuit


VD= 0.697 V VD= 2.65V
Wire Size: 3 Sets of 3 - 100 mm2 Wire Size: 2 - 3.5 mm2 & 1 - 20 mm ø RSC
K = 12.87 (Cu Wire) K = 12.87 (Cu Wire)
L = 88.98 ft. L = 159.74 ft.
I = 209.19 A I = 10 A
SERVICE ENTRANCE 3-100mm² THHN Cu. WIRE 2-3.5mm² THHN Cu. WIRE CM = 197352.52 CM =6907.34
230V, 3P, 3WIRE + G, 60Hz
M.D.P Runs = 3

Substitution:
Substitution:
C.O. VD = (1.732 x K x I x L) / CM
VD = (1.732 x K x I x L) / 3CM
%VD = ( (VD) / V ) (100%)
%VD = ( (VD) / V ) (100%)
VD = (1.732 x 12.87 x 10 x 159.74) / ( 6907.34 )
VD = (1.732 x 12.87 x 209.19 x 88.98) / ( 3 x 197352.52 )
VOLTAGE DROP CALCULATION VD = 5.155 V
VD = 0.7008 V
%VD = (5.155 / 230) x (100%)
ITEM DESCRIPTION PHASE WIRE %VD = (0.7008 / 230) x (100%)
K L I VD %VD %VD = 2.2413 %
NO.
1Ø 3Ø CM SET %VD = 0.3047 %
1 SERVICE ENTRANCE 3 12.87 88.98 209.19 197352.52 3 0.7008 0.3047 %
2 CONVENIENCE OUTLET 2 12.87 159.74 10 6907.34 1 5.155 2.2413 %
TOTAL 5.8558 2.546 %

The computed Voltage drop of an INDUSTRIAL ESTABLISHMENT


with a total 2.546 percentage (%) of Voltage drop meet the
required allowable VD of Philippine Electrical Code.

LOGO NAME OF PROJECT NAME AND ADDRESS OF THE OWNER SHEET CONTENT DRAWN AND DESIGNED BY: CHECKED BY: NAME OF PEE PRC REG. NO.: SHEET NO.

ENGR. GILBERT B. HOLLMAN PTR NO.:


PROPOSED ELECTRICAL SYSTEM
DESIGN OF AN INDUSTRIAL PLANT
PANG HEE CORPORATION
KM 36, GOVERNOR'S DRIVE, IMUS,
CAVITE
VOLTAGE DROP
CALCULATION
ANTHOLYN C. RAMOS
ROCEL JAMES V. DEL ROSARIO
SCALE ENGR. GILBERT B. HOLLMAN DATE & PLACE ISSUED:
5
NTS TIN: 7
SHORT CIRCUIT CALCULATION

For the Rating & Specifications of OCB, MACB etc. For MACB: (Assume 8 cycle duty)
Assuming: MVA available S.C. capacity of Meralco at 1000 MVA (minimum) 1. Type: ACB
2. Voltage: 4.16 kV, 3 P, 60 Hz
3. Continuous rating: 600 Amp
4. Interrupting rating: 21 000 Amp
5. Momentary rating: 40 000 Amp
6. Tripping Speed: 8 cycle duty
7. BIL rating: 60 kV

For low voltage only one diagram for IC and MD


Xt = ( Xp + Xt3 ) ( Xqm”) = ( j 0.061 + j 0.28 ) ( j 2.0 ) = j 0.291 p.u.
Xp + Xt3 + Xqm” j 0.061 + j 0.28 + j 2.0
where:
Xp = 1 ÷ [ 1 / j 0.09 + 1 / j 1.0 + 1 / j 1.0 + 1 / j 1.0 + 1 / j 1.333
IF3 = IF2 = -j 15 421 Amp + 1 / j 1.333 + 1 / j 1.333 ]
Min. Ic = 15 421 ( 1.0 ) = 15 421 Amp Xp = j 0.061 p.u.
Icontinuous = IFL = 278 Amp ( from F – VII )

Xs” = MVAb = j10 = j 0.01 p.u.


MVAsc 1000
For OCB: Choose 10 MVA as base Xt” = j0.08 ( 10 / 10 ) = j 0.08 p.u.
XT = j 0.01 + j 0.08 = j 0.09 p.u.
IF = 1000 x 103
IF2 = 1.0 / j 0.09 10 000 ÷ [ (√3)(4.16)] = -j 15 421 Amp
√3 (34.5 kV)
= 16 734.79 Amp
Icontinuous = 10 000 ÷ (√3)(4.16) = 1 387.86 Amp
Assuming 5 cycle duty OCB:
Min. Ic = ( IF2 ) ( M ) = 15 421 ( 1.0 ) = 15 421 Amp
Icontinuous = 10 000 Min. MD = ( IF2 ) ( M ) = 15 421 ( 1.5 ) = 23 413.15 Amp
√3 (34.5 kV)
= 1 200 Amp
Xt = j 0.291 p.u.
Specifications of MACB: IF-H = ( 1 / j 0.291 ) 10 000 ÷ [ ( √3 )( 0.380)] = -j 52 211.1 Amp
Min Ic = ( IF1 ) ( M ) = 16 734.79 (1.3 ) = 21 755.227 Amp
1. Type: ACB Min. Ic = 52 211.1 (1.0) = 52 211.1 Amp
Min MD = ( IF1 ) ( M ) = 16 734.79 (1.6 ) = 26 775.6 Amp 2. Voltage: 4.16 kV Xim”5 to Xim”4 = j 0.20 (10 000 / 2 000 ) = j 1.0 p.u. Min. MD = 52 211 (1.25) = 65 264 Amp
3. Continuous Rating: 2 000 Amp Icontinuous = Isubfeeder-1 = 453.5 Amp @ 500AT
4. Interrupting rating: 36 000 Amp Xim”1 to Xim”3 = j 0.20 ( 10 000 / 1 000 ) = j 1.333 p.u.
5. Momentary rating: 58 000 Amp Xqm” = j 0.25 ( 10 000 / 1 250 ) = j 2.0 p.u.
Specifications of OCB:
6. Tripping Speed: 8 cycle duty 1. Type: ACB
1. Type: OCB Xt3 = j 0.035 ( 10 000 / 1 250 ) = j 0.28 p.u.
7. BIL rating: 60 kV 2. Voltage: 480 kV, 3 P, 60 Hz
2. Voltage: 34.5 kV, 3 P, 60 Hz
3. Continuous rating: 1200 Amp 3. Continuous rating: 600 Amp
4. Interrupting rating: 21 000 Amp 4. Interrupting rating: 65 000 Amp
Xt = 1 ÷ [ 1 / j 0.09 + 1 / j 1.0 + 1 / j 1.0 + 1 / j 1.333 + 1 / j 1.333+ 1 / j 1.333
5. Momentary rating: 38 000 Amp 5. Momentary rating: 72 000 Amp
6. Tripping Speed: 5 cycle duty + 1 / j 1.333 + 1 / j 2.28 ] 6. Tripping speed: 8 cycle duty
7. BIL rating: 350 kV 7. BIL rating: 7 kV
Xt = j 0.0633 p.u.
8. Temperature Rise: 550oC

LOGO NAME OF PROJECT NAME AND ADDRESS OF THE OWNER SHEET CONTENT DRAWN AND DESIGNED BY: CHECKED BY: NAME OF PEE PRC REG. NO.: SHEET NO.

6
ENGR. GILBERT B. HOLLMAN PTR NO.:
PANG HEE CORPORATION SHORT CIRCUIT ANTHOLYN C. RAMOS
PROPOSED ELECTRICAL SYSTEM
KM 36, GOVERNOR'S DRIVE, IMUS, CALCULATION ROCEL JAMES V. DEL ROSARIO ENGR. GILBERT B. HOLLMAN
DESIGN OF AN INDUSTRIAL PLANT SCALE DATE & PLACE ISSUED:
CAVITE

NTS TIN: 7
RESUME

LOGO NAME OF PROJECT NAME AND ADDRESS OF THE OWNER SHEET CONTENT DRAWN AND DESIGNED BY: CHECKED BY: NAME OF PEE PRC REG. NO.: SHEET NO.

ENGR. GILBERT B. HOLLMAN PTR NO.:


PROPOSED ELECTRICAL SYSTEM
DESIGN OF AN INDUSTRIAL PLANT
PANG HEE CORPORATION
KM 36, GOVERNOR'S DRIVE, IMUS,
CAVITE
RESUME ANTHOLYN C. RAMOS
ROCEL JAMES V. DEL ROSARIO
SCALE ENGR. GILBERT B. HOLLMAN DATE & PLACE ISSUED:
7
NTS TIN: 7