DESIGN ANALYSIS

SHORT CIRCUIT & VOLTAGE DROP CALCULATION

C = Conductor Constants C - Values


60mm^2 = 11424
50mm^2 = 9317

L = Lenght in ft.

f = (2 * L * Isc)/(C * n * E(L-L))
75 KVA, 1ø Transformer
1.22%X 75

M = Multiplier 1/(1+f)
68%R
1.4%Z
240V
n = Number of Conductors per phase

E(L-L) = System Voltage


FAULT
1

@ X1
I(FLA) = 75000VA / 240 V
I(FLA) = 312.5 A

M = 100/1.4 = 71.43
L = 49.2 ft.
133100 Cmil
M = 71.43
Non-Magnetic Conduit
I(SC1) = I(FLA)/(%Z*0.9)
I(SC1) = 312.5/(1.4*0.9)
I(SC1) = 24801 A
@ X2
f = (2 * (49.2 ft)(24801 A))/((11424)(240 V)
f = 0.8902

M = 1/(1+0.8902)
FAULT 2 M = 0.529

I(SC2) = M + I(SC1)
300 A I(SC2) = 0.529 * 24801 A
I(SC2) = 13120 A
@ X3
f = (2 * (85.3 ft)(13120 A))/((9317)(240 V)
f = 1.0009
M = 1/(1+1.0009)
M = 0.4999

I(SC3) = M + I(SC2)
I(SC3) = 0.4999 * 13120 A
I(SC3) = 6558.7 A

Motor Contribution
150 A X1 = 312.5 A * 4
X1 = 1250 A
L = 85.3 ft.
I(SC1) sym RMS = 24801 A + 1250 A
105600 Cmil =26 KA , USE 42 kAIC
Non-Magnetic Conduit

FAULT X2 = 312.5 A * 4
3 X2 = 1250 A
I(SC2) sym RMS = 13120 A + 1250 A
= 14.3 KA , USE 22 kAIC
X3 = 312.5 A * 4
X3 = 1250 A
I(SC3) sym RMS = 6558A + 1250 A
= 7.8 KA , USE 10 KAIC
M
PROJECT TITLE:
PROPOSED JRS EXPRESS BRANCH
OFFICE FIT-OUT
OWNER D:\download.png
JRS Business Corporation
LOCATION: KM. 30 Brgy., Zone 1-A, Along Gen. E. Aguinaldo Highway Dasmariñas PROFESSIONAL ELECTRICAL ENGINEER