ELECTRICAL RISER DIAGRAM VOLTAGE DROP COMPUTATION ILLUMINATION LEVEL COMPUTATION

Maximum Allowable Voltage Drop Floor Area = 492 sq.m


SERVICE LATERAL PROVIDED WITH 50mmØ
"TYPE F" CONDULETS FOR 230V, 2-WIRE, IIllumination Level = 150 Lux
60Hz, A.C. TO CONNECT TO AVAILABLE I
Feeder Circuit: 5%
POWER LINES.
Branch CirCuit : 3% Coefficient of Utilzation ( c.u.) = .35
NOTE:
ALL SIZES OF SERVICE FEEDER (WIRES IN CONDUIT)
5% of Line Voltage (220) = 11 V Maintenance Factor ( m.f. ) = .70
REFER TO SCHEDULE OF LOADS AND COMPUTATIONS
300mm

3% of Line Voltage (220) = 6.6 V 12 watts LED = 1080 lumens


3100mm (MIN.) - 5500mm (MAX.)

Vd = IR 150 x 492
Lamp Lumens = = 301,224
.35 x .70
IResistance of 80 mm2 THHN Wire, 10m Length
Number of 12 watts led
R = .2028 x .010 = 0.002028 ohms
301,224
"MDP" = = 279
I MDP = 183A 1080

say : 279 sets of 12 watts led


Voltage Drop for Feeder Circuit

FIN. FLOOR LINE Vd = 183 X 0.0020 = .3711 V ok Service Bay Area W/ Lifter = 45 sq.m
FIN. GRADE LINE
2 I
Illumination Level = 150 Lux
Resitance of 3.5 mm THHN Wire, 50m Length

R = 5.211 x .050 = 0.26 ohms Coefficient of Utilzation ( c.u.) = .35


1-14mm² THHN IN 20mmØ C. - CLAMPED
2- 80 mm² THHN TO A COPPERCLAD
IN 50mmØ RSC GROUNDING ELECTRODE Maintenance Factor ( m.f. ) = .70
I BC = 9.4 A

30 watts Highbay Aluminum Led Lights = 2,200 lumens


Voltage Drop for Branch Circuit

Vd = 9.4 X 0.26 = 2.4 V ok 150 x 45


Lamp Lumens = = 27,551
.35 x .70

Number of 30 watts Highbay Led Lights

27,551 = 12.5
=
2,200
say : 13 sets of 30 watts Highbay Led Lights

SCHEMATIC DIAGRAM

2
2 - 80 MM THHN

MDP

225 AT , 2P

1 2
15 AT 15 AT

3 4
15 AT 15 AT

5 6
15 AT 15 AT

7 8
20 AT 20 AT

9 10
20 AT 20 AT

11 12
20 AT 30 AT

13 14
30 AT 30 AT

15 16
30 AT 30 AT

17 18
30 AT SPARE

2
1 - 14 MM THHN GROUND WIRE