DSEPower ®

DSE9470 MKII SPECIFICATIONS

24 Volt, 10 Amp Battery Charger AC SUPPLY


VOLTAGE RANGE
90 V to 305 V (L to N)

FREQUENCY RANGE
48 Hz to 64 Hz (L to N)

DC OUTPUT
DSE9470 MKII OUTPUT
10 A DC at 24 V DC (Configurable)

RIPPLE AND NOISE


<1%
SUPPORTS LI-ION
CHARGING PROFILE EFFICIENCY
>86%

REGULATION
LINE
<0.5%

LOAD
2%

TEMPERATURE SENSOR INPUT


PT1000

PROTECTIONS
Short circuit
DC over voltage
DC over current
Reverse polarity
Over temperature
AC under & over voltage

CHARGE FAILURE RELAY


3 A at 30 V DC volt free relay

DIMENSIONS
OVERALL
70 mm x 200 mm x 130 mm
2.7” x 7.9” x 5.1”

WEIGHT
0.75 kg

OPERATING TEMPERATURE RANGE


-30 ºC to +70 ºC
ADVANCED FEATURES Full Protection Communication -22 ºF to +158 ºF
• Intelligent three and four stage • AC input under voltage • Can be integrated into external STORAGE TEMPERATURE RANGE
charging profiles • AC input over voltage systems through MODBUS RTU -30 ºC to +70 ºC
• Configurable to suit 12V and 24V • Battery charger output over voltage using RS485 -22 ºF to +158 ºF
applications • Battery charger output over current • Fully configurable via DSE
• Adjustable current limit • Battery under voltage alarm Configuration Suite PC Software
• Can be used as a battery charger, • Automatic battery detection • External remote display option -
power supply or both at the same • Automatic battery charger self test DSE2541
time • Output short circuit and inversion
• Automatic or manual boost and polarity with auto recovery KEY BENEFITS
storage charge functions to help • Max current mode • Fully flexible to maximise the life of
maintain battery condition • SCADA digital input status the battery
• Digital microprocessor technology information • Suitable for a wide range of battery
• Temperature compensation for • Automatic power de-rating at high types
battery charging ambient temperatures. • Minimum 86% efficiency
• Low output ripple and superb line • Optional battery temperature throughout full operating range
regulation compensation using PT1000 • No external intervention for boost
• Three LED indicators temperature sensor with over mode
• Switched mode design temperature protection • Multiple chargers can be linked
• Fully customisable battery charging Automatic Boost Mode together to provide larger current
curves • Boosts and equalises cell charge, output
• Battery health check improving battery performance • Can be permanently connected
• Battery voltage sensing and life to a battery and AC supply. No
• Deep sleep mode Power Save Mode need to disconnect through high
• PSU only mode • Once the battery is fully charged, load conditions such as cranking
• Automatic voltage detection the chargers switch to eco-power or when the engine is running.
• Wide output current range to save energy

RELATED MATERIALS
TITLE PART NO.
DSE9400 Series Configuration Suite PC Software Manual 057-159
DSE Configuration Suite Installation & Operators Manual 057-151
DSE9000 Series Installation Instructions 053-049
DSE9000 Series Operators Manual 057-085

DEEP SEA ELECTRONICS LTD UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com EMAIL usasales@deepseaelectronics.com WEBSITE www.deepseaelectronics.com
Deep Sea Electronics Ltd maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-158/10/19 (5)
DSEPower ®

DSE9470 MKII ENVIRONMENTAL TESTING STANDARDS

24 Volt, 10 Amp Battery Charger ELECTRO-MAGNETIC COMPATIBILITY


BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
The DSE9470 MKII is an intelligent The chargers do not include any EMC Generic Emission Standard for
battery charger fully configurable for moving parts for additional the Industrial Environment
use at 12 V or 24 V / 5 Amp or 10 durability and reliability. Each charger
OPERATING TEMPERATURE RANGE
Amp. will continue to operate during BS EN 60068-2-1
engine running. Ab/Ae Cold Test -30 ºC
The charger features automatic BS EN 60068-2-2
Bb/Be Dry Heat +80 ºC
voltage detection and battery voltage Multiple chargers can be linked * Refer to de-rating curve in the DSE9000
sensing down to 1 Volt and has together to provide a larger current Operator Manual
an output current range down to 1 output where required.
VIBRATION
A. The charger can also be easily
BS EN 60068-2-6
programmed for different charging The battery chargers are programmed Ten sweeps in each of three
curves, to maximise the life of a using the user-friendly DSE major axes
battery. Configuration Suite PC software. 5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn

The charger can be DIN rail HUMIDITY


or chassis mounted, using the BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 oC
fixing holes that are built into the @ 95% RH 48 Hours
case. The chargers stylish design BS EN 60068-2-78
includes three coloured LEDs to Cab Damp Heat Static 40 oC
indicate charging status and fault @ 93% RH 48 Hours
conditions. SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF BATTERY


CHARGER APPLICATIONS
PC MODBUS

1ph
N

CHARGE OUTPUT USB PORT RS485 AC POWER SUPPLY

COMPATIBLE WITH ALL


DSE MODULES

DSE9470 MKII
7

OTHER

TEMPERATURE SENSOR VOLT FREE CHANGE OVER CONFIGURABLE INPUT


FAULT OUTPUT

PT1000 ONLY

1 1