DSE5510M SPECIFICATION
AUTO & MANUAL START CONTROL MODULE (ELECTRONIC ENGINE ENABLED)

DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries

MAXIMUM OPERATING CURRENT


460mA at 12V. 245mA at 24V

MAXIMUM STANDBY CURRENT


375mA at 12V. 200mA at 24V

ALTERNATOR INPUT RANGE


15V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY


50Hz - 60Hz at rated engine speed (Minimum:
15V AC L-N)

TYPE MAGNETIC PICK-UP VOLTAGE RANGE


+/- 0.5V to 70V Peak
APPROVED
PRODUCT MAGNETIC INPUT FREQUENCY
10,000 Hz (max)
Certificate no:
A-10081 START RELAY OUTPUT
16A DC at supply voltage

The DSE5510 is an Automatic generator short circuit protection, • Remote monitoring FUEL RELAY OUTPUT
• Magnetic pick-up 16A DC at supply voltage
Engine Control Module, designed reverse power, generator phase
to provide advanced load share rotation error, earth fault protection, AUXILIARY RELAY OUTPUTS
functionality for diesel and gas loss of speed signal, fail to open, LOAD SHARE FEATURES Three outputs 5A DC at supply voltage
generating sets that include non- fail to close, out of sync, MPU • ROCOF & vector shift Two outputs volt free 8A at 250V AC

electronic and electronic engines. open circuit failure, negative phase • Automatic starting & stopping of
DIMENSIONS
The module also provides sequence and loss of excitation. generator on load demand 240mm x 172mm x 57mm
• Automatic hours run balancing of 9.4” x 6.8” x 2.2”
excellent engine monitoring and
generator sets
protection features. FEATURES PANEL CUTOUT
• Dead bus sensing
• Electronic engine capability • Module has the ability to interface
220mm x 160mm
• RS232 and RS485 remote 8.7” x 6.3”
The modules load share functions with existing load share lines
include, automatic synchronising communications • Direct communication from the CHARGE FAIL/EXCITATION RANGE
with built in synchroscope and • Modbus RTU module to the governor and AVR 0V to 35V
closing onto dead bus. Direct and • Pin number protected front panel • Link up to 16 generators
programming BUILT IN GOVERNOR CONTROL
flexible outputs from the module • Volts & frequency matching Fully Isolated
are provided to allow connection • Engine exercise timer • KW and Kvar load sharing with Minimum Load Impedence:
• Back-lit LCD 4-line text display multiple generators 1000Ω
to the most commonly used speed
• Multiple display languages Gain Volts 0V - 10V DC
governors and automatic voltage Offset Volts + / - 10V DC
• Voltage measurement BENEFITS
regulators (AVR’s). • Configurable inputs (9) • Sends SMS messages to BUILT IN AVR CONTROL
• Configurable outputs (5) engineers to notify specific Fully Isolated
The module has been designed to • Automatic start Minimum Load Impedence:
combine a maximum of 16 engine problems (GSM Modem 1000Ω
• Manual start and SIM card required) Gain Volts 0V - 10V DC
generators and 16 mains (utility) • Audible alarm • On-site and remote module Offset Volts + / - 10V DC
supplies up to a maximum of 20 in • LED indicators configuration
one system, e.g. 16 generators and • Built-in governor and AVR control • In-built engine diagnostics
ENCLOSURE PROTECTION
• Engine history event log (front of module)
4 mains (utility) supplies (DSE5560 removes the requirement for IP55 (with optional gasket)
required to synchronise with the • Engine protection service equipment IP42 (without gasket)
mains). • Fault condition notification to a • Full engine protection &
designated PC instrumentation without the need
The module has the ability to • Front panel mounting for additional senders (Electronic
monitor under/over generator • PC configuration engines only)
• Mains (utility) failure detection • Remote monitoring of the module
volts, over current, under/over
• Configurable alarm timers using comprehensive DSE PC
generator frequency, under speed,
• Configurable start & stop timers software
over speed, charge fail, emergency • Automatic load transfer
stop, low oil pressure, high engine • License free PC software
• SMS alert messaging
temperature, fail to start, low/high • Multi set communications
DC battery volts, fail to stop, • Front panel mounting ELECTRONIC ENGINE CAPABILITY
OPERATION TELEMETRY
ENVIRONMENTAL TESTING The module is operated using the front STOP/RESET, MANUAL, AUTO and The module gives the user full
STANDARDS START push buttons. Three of these push buttons include an LED indicator. telemetry facilities when using the
Additional push buttons provide LCD display scroll, lamp test, mute optional communications software.
ELECTRO MAGNETIC COMPATIBILITY functionality and breaker control. The module can be connected to a
(EMC) PC using the DSE810 PC interface
BS EN 50081-2 EMC Emission TIMERS & INPUT FUNCTIONS or by using a suitable modem.
Standard for the Industrial Environment
The module has been designed to include the following timers and input functions:
ELECTRICAL SAFETY The PC software is Microsoft
BS EN 60950 Low Voltage Directive/Safety of • Start delay timer Windows based. All access into
Information Technology Equipment, including • Stop delay timer the module can be configured to
Electrical Business Equipment
• Crank timer become password protected to
TEMPERATURE • Crank rest timer prevent unauthorised entry. The PC
COLD • Engage attempt & manual crank limit timers software allows the module to be
BS EN 60068-2-1 to -30oC • Safety on delay timer controlled from a remote location.
HOT
o
BS EN 60068-2-2 to 70 C • Warm up timer
• Cooling timer COMMUNICATIONS
BS EN 50082-2 EMC IMMUNITY • Energise to stop hold timer The DSE5510M has a number of
Standard for the Industrial Environment • Pre-heat timer different communication capabilities.
VIBRATION • Pre-heat bypass timer
BS EN 60068-2-6 Ten sweeps (up and back • Smoke limiting control timer SMS Messaging
down) at 1 octave/minute in each of the three • Fail to stop timer When the module detects an alarm
major axes • Over speed over shoot timer condition, it has the ability to send
5Hz to 8Hz @ +/-7.5mm constant
displacement • Breaker pulse control timers an SMS message to a dedicated
8Hz to 500Hz @2gn constant acceleration • DC battery alarm delay timers mobile number, notifying an engineer
• Sync/fail to sync timer of the problem. (GSM Modem and
HUMIDITY
o SIM Card required).
BS EN 2011 part 2.1 93% RH @ 40 C for 48
hours BUILT-IN FUNCTIONS
• Alternator under/over volts Remote Communications
SHOCK • Alternator under/over frequency When the module detects an alarm
BS EN 60068-2-27 Three half sine shocks in • Warning or shutdown on engine temperature, over/under speed, oil condition, it dials out to a PC notifying
each of the three major axes 15gn amplitude
11mS duration pressure the user of the exact alarm condition.
• Warning, shutdown or electrical trip on battery volts or over current
• Shutdown or electrical trip on reverse power, phase rotation or short Vessel Management
circuit fault The module has been designed to
TYPICAL LOAD SHARE • Earth fault shutdown be integrated into new and existing
APPLICATION • Adjustable crank cycle/attempts vessel management systems.
• Full remote control and telemetry
• 9 configurable digital inputs PC Software
• 5 configurable and 2 fixed relay outputs The module has the ability to be
G1
• System lock input configured and monitored from a
• Load switching control push-button inputs remote PC, using the DSE810
• ROCOF/vector shift (mains/utility decoupling) interface.
• Negative phase sequence
• Loss of excitation EVENT LOG
G2
The module includes a
INSTRUMENTATION AND ALARMS comprehensive event log that
The DSE5510M module provides advanced metering and alarm functionality shows the 25 most recent alarm
via the LCD display. The information can be accessed using the display scroll conditions and the date and time
G3 LOAD
push buttons. The table below shows the instrumentation and alarm features that they occurred.
the module provides.
This function assists the user when
Generator Volts L1-N, L2-N, L3-N fault finding and maintaining the
Generator Volts L1-L2, L2-L3, L3-L1 generating set.
Generator Amps L1, L2, L3
Generator Frequency Hz EXPANSION MODULES
Generator kVA L1, L2, L3, Total DSE123 Load Share Lines Interface
Generator kW L1, L2, L3, Total Module
Generator pf L1, L2, L3, Average DSE157 Relay Input Expansion
Generator kVAr L1, L2, L3, Total Module
Generator KWh DSE545 & DSE548 Remote
Generator KVAh Annunciation Expansion Module
Generator KVArh DSE130 Input Expansion Module
Generator Phase Sequence
Synchroscope Display ELECTRONIC ENGINE
Engine Speed RPM COMPATIBILITY
Engine Oil Pressure • Cummins
Engine Temperature • Deutz
Plant Battery Volts • John Deere
Engine Hours Run • MTU
Number of Start Attempts • Perkins
Maintenance Display • Scania
Engine ECU diagnostics information via industry standard CAN interface • Volvo
Enhanced metering via CAN when connected to an electronic engine • Generic
• Plus additional manufacturers
®

DSE5510M
AUTOMATIC MCCB
AUTOMATIC ACB
or CONTACTOR
CTs MUST BE 5 AMP
CONNECT TO 3 or 4 POLE
SECONDARY
BATTERY NEGATIVE
P1 P2
L1 L1
S1 S2

L2 L2

FROM
GENERATOR L3 L3 TO LOAD

N N

2 AMP 2 AMP
FUSES

SCREEN EARTHED AT
SCREEN EARTHED AT

FUSES

SCREEN TO ENGINE
SCREEN TO ENGINE
TO MAG PICK UP IF

DO NOT CONNECT
DO NOT CONNECT
TO GEN SWITCHING

TO ENGINE ECU

THIS END ONLY


DEVICE CIRCUITRY

THIS END ONLY


USED

49 50 51 53 52 45 46 47 48 39 40 20 21 22 37 38 54 55 56 29 30 31 23 24 25 41 42 43 44

CT1 CT2 CT3 CT4 COM L1 L2 L3 N SCR SCR B A SCR B L L1 L2 L3 N


UNUSED

L151 L251 L351 N52 MPU RS485 J1939


BUS VOLTS
GEN VOLTS CLOSE OUTPUT
GEN CURRENT GEN 5
OUTPUT
4
P810 TO OTHER 5510M’s
SCR 26 MSC CONNECTIONS
MAX 250 METERS
RS232

MODULE 5510M MSC H 27


120 OHM SCREEN CABLE
COMMON GROUND

L 28
CRANK
FUEL

OIL PRESSURE

WATER TEMP

CHARGE ALT

157

UNUSED
BATTERY 3 OUTPUTS THE FIRST AND LAST UNITS
PLANT +VE
GOVERNOR AVR
MSC MUST BE FITTED WITH A
FUEL

9 INPUTS
O/P O/P
+VE

-VE

B A B A 120 OHM RESISTOR ACROSS


2 1 3 4 5 57 58 59 60 9 10 11 12 13 14 15 16 17 18 6 7 8 19 32 33 34 35 36 H(27) AND L(28)
TO BATTERY NEGATIVE
TO CRANK SOLENOID MAX 16AMP
TO FUEL SOLENOID MAX 16AMP

CHARGE ALTERNATOR
FOR REMOTE EM STOP
REMOVE LINK FOR

USER CONFIGURATION INPUT 1

USER CONFIGURATION INPUT 2

USER CONFIGURATION INPUT 3

USER CONFIGURATION INPUT 4

USER CONFIGURATION INPUT 5

USER CONFIGURATION INPUT 6

USER CONFIGURATION INPUT 7

USER CONFIGURATION INPUT 8

USER CONFIGURATION INPUT 9

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT


FUEL TEMP
HIGH COOLANT TEMP
LOW OIL PRESSURE

TO TO
GOVERNOR AVR
CONECT SCREEN AT

CONECT SCREEN AT
GENERATOR ONLY

GENERATOR ONLY
TO BATTERY NEGATIVE

SCREEN EARTHED
AT THIS END ONLY
ANTI-SURGE FUSE

UPTO32 AMPS
MAX 20 AMP
MIN 2 AMPS

FUSE

BATTERY +VE
(12 OR 24 VDC ) BATTERY -VE

ALL BATTERY NEGATIVES MUST BE CONNECTED TOGETHER

RELATED MATERIALS
TITLE PART NO’S
DSE5510M Manual 057-080
DSE123 Data Sheet 055-044
Load Share Design & Commissioning 057-047
Guide to Synchronising and 057-045/6
Load Sharing
55xx Software manual 057-007
CAN & DSE wiring guide 057-004
DSE5510M Installation Instructions 053-048
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 sales@deepseaplc.com
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL


THAILAND +66 (0) 2678 3028 sales@dseplc.com
TPI Tower, Lobby 3
Floor 27, 26-56 Chan New Road FACSIMILE WEBSITE
Tungmahamek, Sathom +66 (0) 2670 6228 www.deepseaplc.com
Bangkok 10120, Thailand

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


USA +1 (815) 316 8706 sales@deepseausa.com
3230 Williams Avenue
Rockford FACSIMILE WEBSITE
IL 61101-2668 USA +1 (815) 316 8708 www.deepseausa.com

YOUR LOCAL DISTRIBUTOR.

TYPE
APPROVED
PRODUCT
Certificate no:
A-10081

DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.