DSE8661 SPECIFICATION
DC SUPPLY
1.2 km
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)
RS485
FREQUENCY RANGE
3.5 Hz to 75 Hz
LOAD
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
BUS
KEY FEATURES • Can be integrated into building VOLTAGE RANGE
• Mains (utility) failure detection • Customisable status screens management systems (BMS) and 15 V to 333 V AC (L-N)
• Mains (utility) power monitoring • Configurable inputs (11) programmable logic control
FREQUENCY RANGE
(kW, kV Ar, kV A and pf) • Configurable outputs (8) (PLC) 3.5 Hz to 75 Hz
• Comprehensive synchronising • Configurable timers and alarms • Increased input and output
expansion capability via DSENet® OUTPUTS
and loadsharing capabilities • Multiple entry scheduler OUTPUTS C & D
• Peak lopping & shaving • Configurable event log (250) • Licence-free PC software 8 A at 250 V AC (Volt free)
functionality • Easy access diagnostic pages • IP65 rating (with supplied gasket)
offers increased resistance to AUXILIARY OUTPUTS E,F,G,H, I & J
• Mains (utility) kW export • LED and LCD alarm indication 2 A DC at supply voltage
protection • USB connectivity water ingress
• Mains (utility) de-coupling • Backed up real time clock • Advanced Internal PLC editor DIMENSIONS
allows user configurable OVERALL
protection • Fully configurable via DSE 240 mm x 181 mm x 42 mm
• Advanced integral PLC editor Configuration Suite PC Software functions to meet specific 9.4” x 7.1” x 1.6”
• User configurable RS232, RS485 KEY BENEFITS application requirements.
& Ethernet communications • Improved support for multi- PANEL CUT-OUT
• Two part solution allows up to 1.2 220 mm x 160 mm
• MODBUS RTU & TCP support voltage systems. 8.7” x 6.3”
km between mains (utility) &
• User configurable MODBUS • Clear demarcation between
bus breakers.
pages genbus and mains breakers MAXIMUM PANEL THICKNESS
• Compatible with DSE5510, 8 mm
• Advanced SMS control and fault EXPANSION DEVICES 0.3”
DSE7510 & DSE8x10 series of
messaging (addition GSM • DSE124 CAN/MSC Extender
modules OPERATING TEMPERATURE RANGE
modem required) • DSE2130 Input Expansion Module
• 132 x 64 pixel ratio display for -30°C to +70°C
• DSENet expansion compatible • DSE2131 Ratio-metric Input
clarity
• Data logging and trending Expansion Module STORAGE TEMPERATURE RANGE
• Real-time clock provides -40°C to +85°C
• 4-Line back-lit LCD text display • DSE2133 RTD & Thermo-couple
accurate
• Multiple display languages Expansion Module
event logging
• Five key menu navigation • DSE2152 Ratio-metric Output
• Ethernet communication
• Front panel editing with PIN Expansion Module
provided built in advanced
protection remote monitoring
• DSE2157 Output Expansion
Module
• DSE2548 LED Expansion Module
RELATED MATERIALS
TITLE PART NO’S
DSE8661 Installation Instructions 053-091
DSE8661 Operator Manual 057-204
DSE8600 PC Configuration Suite Manual 057-119
DSE8610 Data Sheet 055-083
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-169/05/16 (2) US
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457
®
DSEGenset
DSE8661
ENVIRONMENTAL TESTING STANDARDS
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE8661 is an easy-to-use Comprehensive communications With all communication ports TEMPERATURE
two part mains controller with are also available via RS232, capable of being active at the same BS EN 60068-2-1
automatic transfer switch capability RS485 & Ethernet for remote PC time, the DSE8xxx Series is ideal Ab/Ae Cold Test -30oC
for a wide variety of demanding BS EN 60068-2-2
between remote breakers of upto control and monitoring, and Bb/Be Dry Heat +70oC
1.2 km . Designed to synchronise integration into building load share applications.
VIBRATION
single or multiple DSE8x10s and management systems. BS EN 60068-2-6
DSE8680s with a single mains The comprehensive event log will KEY LOAD SHARE FEATURES:
Ten sweeps in each of three major axes
(utility) supply, the DSE8661 will record up to 250 events to facilitate • Peak lopping/sharing 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
automatically control the change maintenance. • Sequential set start
HUMIDITY
over from mains (utility) to generator • Manual voltage/frequency BS EN 60068-2-30
supply or run generators in An extensive number of fixed and adjustment Db Damp Heat Cyclic 20/55oC @ 95% RH 48
• R.O.C.O.F. and vector shift Hours
synchronisation with the mains flexible monitoring and protection BS EN 60068-2-78
(utility) to provide no-break, peak features are included. Easy protection Cab Damp Heat Static 40oC @ 93% RH 48
lopping and peak shaving power alteration of the sequences, timers • Generator load demand Hours
solutions. and alarms can be made using the • Automatic hours run balancing SHOCK
DSE PC Configuration Suite • Mains (Utility) de-coupling BS EN 60068-2-27
• Mains (Utility) de-coupling Three shocks in each of three major axes
The module can indicate Software. Selected configuration is 15gn in 11mS
operational status and fault also available via the module’s front test mode
conditions on the LCD screen panel. • Bus failure detection DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
(multiple languages available), by • Volts and frequency matching. BS EN 60529
illuminated LED, audible sounder • kW & kV Ar load sharing IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
and SMS messaging.
2 x DSE8661 MSC
RS485
7
5510 7510 8x10 8661 8661
OTHER
1of2DSE8661 1of2DSE8661
MAINS (UTILITY) SENSING VOLT FREE LOAD LOAD VOLT FREE BUS
OUTPUTS SENSING SENSING OUTPUTS SENSING
CURRENT VOLTS
ISSUE 1