DSE7520 SPECIFICATION
AUTO MAINS (UTILITY) FAILURE & INSTRUMENTATION CONTROL MODULE

DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries

MAXIMUM OPERATING CURRENT


460mA at 12V. 245mA at 24V

MAXIMUM STANDBY CURRENT


375mA at 12V. 200mA at 24V

ELECTRONIC ENGINE CAPABILITY ALTERNATOR INPUT RANGE


15V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY


50Hz - 60Hz at rated engine speed (Minimum:
15V AC L-N)

MAGNETIC PICK-UP VOLTAGE RANGE


+/- 0.5V to 70V Peak

MAGNETIC INPUT FREQUENCY


The DSE7520 is an Automatic FEATURES LOAD SHARE FEATURES 10,000 Hz (max)
Mains (Utility) Failure Control • Electronic engine capability • No-break transfer
• RS232 or RS485 remote • Peak shaving/peak lopping MAINS (UTILITY) SENSING RANGE
Module designed to provide 15V(L-N) to 333V AC (L-N) absolute maximum
advanced load share functionality communications • KW on mains (utility) level
for diesel and gas generating sets • Modbus RTU • Mains (utility) decoupling test mode MAINS (UTILITY) SENSING INPUT
that include non electronic and • Pin number protected front panel • Manual speed/frequency adjust FREQUENCY
programming • Phase locking 50Hz-60Hz (Minimum: 15V AC L-N)
electronic engines. The module
• Exercise timer • ROCOF & vector shift START RELAY OUTPUT
also provides excellent engine
• Back-lit LCD 4-line text display • Dead bus sensing 15A DC at supply voltage
monitoring and protection features.
• Multiple language options • Direct governor & AVR
• Voltage measurement communication FUEL RELAY OUTPUT
The module monitors the mains 15A DC at supply voltage
• Configurable inputs (9) • Volts & frequency matching
(utility) supply and upon detection • Configurable outputs (5) • KW and Kvar load sharing AUXILIARY RELAY OUTPUTS
of a loss in power automatically • Automatic start • Manual voltage adjust Three outputs 2 Amp DC at supply voltage
starts the generating set. • Manual start Two outputs volt free 8 Amp at 250V AC
• Audible alarm BENEFITS GENERATOR LOADING RELAY OUTPUT
The module’s synchronising • LED indicators • Sends SMS messages to 8A AC 250V
functions include automatic • Built-in governor and AVR control engineers to notify specific engine
synchronising with built in for easy operation and panel problems (GSM Modem and SIM MAINS (UTILITY) LOADING RELAY OUTPUT
synchroscope and closing onto dead engineering card required) 8A AC 250V

bus. Direct and flexible outputs from • Engine history event log • On-site and remote module
CHARGE FAIL/EXCITATION RANGE
the module are provided to allow • Engine protection configuration (Modem required)
0V to 35V
connection to the most commonly • Fault condition notification to a • In-built engine diagnostics
designated PC removes the requirement for BUILT-IN GOVERNOR AND AVR CONTROL
used speed governors and
• Front panel mounting service equipment Fully Isolated
automatic voltage regulators (AVRs). Minimum Load Impedance:
• PC configuration • Full engine protection &
1000Ω
• Mains (utility) failure detection instrumentation without the need Gain Volts: 0V-10V DC
The module has the ability to • Configurable alarm timers for additional senders (Electronic Offset Volts: + / - 10V DC
monitor generator under/over • Configurable start & stop timers engines only)
volts, over current, generator • Automatic load transfer • Remote monitoring of the module DIMENSIONS
under/over frequency, under • SMS alert messaging using comprehensive DSE PC 240mm x 172mm x 57mm
9.4” x 6.8” x 2.2”
speed, over speed, charge fail, • Multi set communications software
emergency stop, low oil pressure, • Front panel mounting • License free PC software PANEL CUTOUT
high engine temperature, fail to • Remote control and monitoring • No-break return capability 220mm x 160mm
• Dedicated load test button 8.7” x 6.3”
start, low/high DC battery volts, fail
to stop, generator short circuit • KW overload alarms ENCLOSURE PROTECTION
protection, reverse power, • Engine temperature alarms IP65 (with optional gasket)
generator phase rotation error, • MV-LV synching IP42 (without gasket)

earth fault protection, loss of • Mains (utility) decoupling test


mode
speed signal, fail to open, fail to
close, out of sync, open circuit
failure, negative phase sequence
and loss of excitation.
OPERATION TELEMETRY
ENVIRONMENTAL TESTING The module is operated using the front STOP/RESET, MANUAL, AUTO and The module gives the user full
STANDARDS START pushbuttons. Three of these push buttons include an LED indicator. telemetry facilities when using the
Additional pushbuttons provide LCD display scroll, lamp test, mute optional communications software.
ELECTRO MAGNETIC CAPABILITY functionality and breaker control. The module can be connected to a
BS EN 61000-6-2 PC using the DSE810 PC interface
EMC Generic Emission Standard for the
BUILT-IN FUNCTIONS or by using a suitable modem.
Industrial Environment
BS EN 61000-6-4 • Alternator under/over volts
EMC Generic Emission Standard for the • Alternator under/over frequency The PC software is Microsoft
Industrial Environment • Warning or shutdown on engine temperature, over/under speed, oil Windows™ based. All access into
pressure the module can be configured to
ELECTRICAL SAFETY
BS EN 60950 • Warning, shutdown or electrical trip on battery volts or over current become password protected to
Safety of Information Technology Equipment, • Shutdown or electrical trip on reverse power, phase rotation or short prevent unauthorised entry. The
including Electrical Business Equipment circuit fault PC software allows the module to
• Earth fault shutdown be controlled from a remote location.
TEMPERATURE
BS EN 60068-2-2 • Adjustable crank cycle/attempts
Test Ab to +70oC 60067-2-2 Hot • Full remote control and telemetry COMMUNICATIONS
Test Ab to -30oC 60068-2-1 Cold • 9 configurable digital inputs The DSE7520 has a number of
• 5 configurable and 2 fixed relay/FET outputs different communication capabilities:-
VIBRATION
BS EN 60068-2-6 • System lock input
Ten sweeps in each of three major axes • Load switching control push-button inputs SMS Messaging
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn • Restricted access to programming via PIN number When the module detects an alarm
• Loss of excitation condition, it has the ability to send
HUMIDITY
BS 2011 part 2.1 60068-2-30 • Negative phase sequence an SMS message to a dedicated
Test Cb Ob Cyclic • ROCOF/vector shift (mains (utility) decoupling) mobile number, notifying an engineer
93% RH @ 40oC for 48 hours • Peak lopping of the problem. (GSM Modem and
• Peak shaving data enabled SIM Card required).
SHOCK
BS EN 60068-2-27 • Mains (utility) reverse power
Three shocks in each of three major axes Remote Communications
15gn in 11mS INSTRUMENTATION AND ALARMS When the module detects an alarm
The DSE7520 module provides advanced metering and alarm functionality condition, it dials out to a PC
via the LCD display. The information can be accessed using the display scroll notifying the user of the exact alarm
pushbuttons. The table below shows the instrumentation and alarm features condition (modem required).
TIMERS & INPUT FUNCTIONS the module provides.
The module has been designed to Building Management
include the following timers and input Engine Speed The module has been designed to
functions: Engine Oil Pressure integrate with new and existing
• Start delay timer Coolant Temperature building management systems.
• Stop delay timer Battery Voltage
• Crank timer Charge Alt Volts SCADA/PC Software
• Crank rest timer Engine Run Time The module has the ability to be
• Engage attempt & manual crank Number of Starts controlled, configured and monitored
limit timers Additional instrumentation as provided by the electronic ECU from a remote PC, using the
• Safety on delay timer Next Maintenance (if enabled) DSE810 interface.
• Warm up timer Fuel Level
• Cooling timer Generator Volts (L-N) EVENT LOG
• Energise to stop hold timer Generator Volts (L-L) The module includes a
• Pre-heat timer Generator Hz comprehensive event log that
• Pre-heat bypass timer Generator Amps shows the 25 most recent alarm
• Smoke limiting control timer Generator Earth Current conditions and the date and time
• Fail to stop timer Generator kW (L1,L2,L3) that they occurred. This function
• Over speed over shoot timer Generator Total kW assists the user when fault finding
• Breaker pulse control timers Generator pf (L1,L2,L3) and maintaining a generating set.
• DC battery alarm delay timers Generator Average pf
• Sync/fail to sync timer Generator Total kVAr EXPANSION MODULES
• Mains (utility) transient delay Generator kWh DSE157 Relay Output
• Transfer time Generator kVAh Expansion Module
• Mains (utility) fail to open/close Generator kVArh DSE545 & DSE548 Remote
• Parallel run time Generator Phase Sequence Annunciation Expansion Module
Synchroscope DSE130 Input Expansion Module
Mains (utility) Volts (L- N)
TYPICAL LOAD SHARE Mains (utility)Volts (L-L) ELECTRONIC ENGINE
APPLICATION Mains (utility)Hz COMPATIBILITY
Mains (utility)Amps • Cummins
Mains (utility)kW • Deutz
Mains (utility)kVA • John Deere
G
Mains (utility)pf • MTU
Mains (utility)kVAr • Perkins
Mains (utility)Phase Sequence • Scania
Generator kVA • Volvo
• Isuzu
LOAD
• Generic
• Plus additional manufacturers
®

DSE7520

FROM TO LOAD
AUTOMATIC MCCB
GENERATOR AUTOMATIC ACB TO
MAINS
or CONTACTOR (UTILITY)
CT’s 1 AMP OR 5 AMP
3 or 4 POLE CT’s 1 AMP OR 5 AMP
SECONDARY SECONDARY
PROTECTION CLASS INSTRUMENT CLASS

P1 P2 P2 P1
L1

S1 S2 S2 S1

L2

L3

N
TO MAINS SWITCHING

2 AMP 2 AMP
TO GEN SWITCHING

FUSES FUSES
DEVICE CIRCUITRY

DEVICE CIRCUITRY

MPU

51 52 53 55 54 43 44 45 46 41 42 24 22 23 39 40 56 57 47 48 49 50

CT1 CT2 CT3 CT4 COM U V W N SCR S1 S2 R S T N


RS485 L1S1 L2S1 L3S1 NS2 L1 L2 L3 L1 L2 L3
MPU CLOSE MAINS
CLOSE GEN OUTPUT C L1 MAINS
RS232 GEN CURRENT GEN VOLTS OUTPUT D CURRENT MAINS VOLTS
A

P810
B
COMMON GROUND

MODULE 7520
CRANK

157
OIL PRESSURE
FUEL

SCR
WATER TEMP

FUEL LEVEL

3 OUTPUTS
CHG ALT

PLANT +VE GOVERNOR AVR ENGINE ECU


BATTERY 9 INPUTS
O/P O/P
+VE

-VE

B A B A SCR H L

2 1 3 4 5 16 17 18 15 6 60 61 62 63 64 65 66 67 68 8 9 10 7 34 35 36 37 38 27 25 26
USER CONFIGURABLE +VE OUTPUT E

USER CONFIGURABLE +VE OUTPUT F

USER CONFIGURABLE +VE OUTPUT G


USER CONFIGURABLE -VE INPUT G
USER CONFIGURABLE -VE INPUT A
REMOVE LINK FOR REMOTE EM STOP

USER CONFIGURABLE -VE INPUT E


TO CRANK SOLENOID MAX 16AMP OUTPUT B
TO FUEL SOLENOID MAX 16AMP OUTPUT A

USER CONFIGURABLE -VE INPUT H


CHARGE ALTERNATOR

USER CONFIGURABLE -VE INPUT B


FUEL TEMP
HIGH COOLANT TEMP
LOW OIL PRESSURE

USER CONFIGURABLE -VE INPUT F


USER CONFIGURABLE -VE INPUT C

USER CONFIGURABLE -VE INPUT I

TO
MIN 2 AMPS MAX 20 AMP ANTI-SURGE FUSE

TO
CONECT SCREEN AT

CONECT SCREEN AT

GOVERNOR
GENERATOR ONLY

AVR
GENERATOR ONLY
USER CONFIGURABLE -VE INPUT D

SCREEN EARTHED
AT THIS END ONLY
UPTO32 AMPS

TO ENGINE EARTH
FUSE

120 R TERMINATING RESISTOR


BATTERY +VE(12 OR 24 VDC )

MAY BE REQUIRED EXTERNALLY


SEE ENGINE MANUFACTURERS
LITERATURE
BATTERY -VE

RELATED MATERIALS
TITLE PART NO’S
DSE7520 Manual 057-089
DSE7520 Installation Instructions 053-053
DSE75xx PC Software Manual 057-078
DSE7510 Data Sheet 055-065
DSE7560 Data Sheet 055-067
DSE123 Data Sheet 055-044
DSE810 Manual 057-052
Load Share Design and Commissioning 057-047
Guide to Synchronising and Load
Sharing 057-045/6
CAN and DSE Wiring Guide 057-004
DSE850 Comms Software Data Sheet 055-072
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 sales@deepseaplc.com
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


3230 Williams Avenue +1 (815) 316 8706 sales@deepseausa.com
Rockford
IL 61101-2668 USA FACSIMILE WEBSITE
+1 (815) 316 8708 www.deepseausa.com

YOUR LOCAL DISTRIBUTOR.

PENDING

DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-066/06/09 (4)

You might also like