DSEE800
DC SUPPLY
CONTINUOUS VOTLAGE RATING
8 V to 35 V continuous
CRANKING DROPUTS
ENGINE CONTROLLER Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries.
INPUTS
DIGITAL INPUTS A to K
Configurable as:
Positive switching
Negative switching
RATIOMETRIC INPUT A
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 480 Ω
RATIOMETRIC INPUTS B to L
Configurable as:
Negative switching digital input
0 V to 10 V
4 mA to 20 mA
0 Ω to 1920 Ω
OUTPUTS
DC OUTPUT A (FUEL) & B (START)
10 A short term,
5 A continuous at supply voltage
KEY FEATURES • CAN, Magnetic Pick-up or KEY BENEFITS VOLT-FREE OUTPUTS C & D
• Built-in governor control tachometer speed sensing • 132 x 64 pixel ratio display for 5 A DC at 35 V DC
8 A AC at 250 V AC
• Automatic speed control • Fuel usage monitor and low fuel clarity
• Manual speed control via push alarms • Real-time clock provides accurate DC OUTPUTS E, F, G & H
buttons, digital input or analogue • Charge alternator failure alarm event logging 2 A DC at supply voltage
input • Manual fuel pump control • Set maintenance periods can be PWMi OUTPUTS I, J, K & L
• Automatic speed ramping • “Protections disabled” feature configured to maintain optimum 4 A at supply voltage
• Flexible automatic start control • LED and LCD alarm indication engine performance 20 Hz to 250 Hz
• Clutch control • USB connectivity • Ethernet communications provides
PULSE PICK-UP
• 4-Line back-lit LCD text display • Backed up real time clock built in advanced remote VOLTAGE RANGE
• Multiple display languages • Fully configurable via DSE monitoring. ±0.5 V to 60 V RMS
• Five key menu navigation Configuration Suite PC software • Can be integrated into remote Fully isolated
• Front panel editing with PIN • Configurable display languag• monitoring systems FREQUENCY RANGE
protection • Remote SCADA monitoring via DSE • Increased input and output 10,000 Hz (max)
• Customisable status screens Configuration Suite PC software expansion capability via DSENet®
BUILT-IN GOVERNOR CONTROL
• Power save off mode • User selectable RS232, RS485 & • Licence-free PC software
MINIMUM LOAD IMPEDANCE
• Configurable digital inputs (11) Ethernet communications • IP65 rating (with supplied gasket) 1000 Ω
• Configurable ratiometric • Modbus RTU & TCP support offers increased resistance to water Fully isolated
inputs (12) • User configurable MODBUS pages ingress
GAIN VOLTAGE
• Configurable DC outputs (4) • Advanced SMS control and fault • Advanced PLC editor allows 0 V to 10 V DC
• Configurable volt-free outputs (2) messaging (additional GSM modem user configurable functions to meet
• Configurable PWMi outputs (4) required) application requirements. OFFSET VOLTAGE
±10 V DC
• Configurable timers and alarms • Start & stop capability via SMS • Automatic speed control
• 3 configurable maintenance alarms messaging • Manual speed control via push DIMENSIONS
• Multiple date and time engine • Additional display screens to help buttons, digital input or analogue OVERALL
scheduler with modem diagnostics input 240 mm x 172 mm x 57 mm
9.4” x 6.8” x 2.2”
• Configurable event log (250) • DSENet® expansion compatible
• CAN engine support • Data logging and trending PANEL CUTOUT
• Advanced Integral PLC editor 220 mm x 160 mm
8.7” x 6.3”
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
TEMPERATURE
BS EN 60068
The DSEE800 is an easy to use With the built in PLC editor the Using the DSE Configuration Suite Ab/Ae Cold Test -30oC
engine controller designed to provide controller is fully flexible and can PC Software the controller is easy BS EN 60068-2-2
flexible control with built in monitoring be adjusted to meet many different to use and configure which allows Bb/Be Dry Heat +70oC
and protection. The DSEE800 is needs, providing the user with the alteration of operating parameters, VIBRATION
compatible with both electronic and ability to achieve special operating sequences, timers and alarms. BS EN 60068-2-6
non-electronic diesel engines and modes which are unique to their Ten sweeps in each of three major axes
fully configurable for a wide range of machine and application. A range of 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
applications such as engine driven comprehensive communication and HUMIDITY
pumps, compressors, hydraulic power system expansion options ensures BS EN 60068-2-30
packs and off highway machinery. that the user can extend the input and Db Damp Heat Cyclic 20/55oC @ 95% RH
48 Hours
output capability and communicate BS EN 60068-2-78
Control of the application can be with other devices or systems offering Cab Damp Heat Static 40oC @ 93% RH
achieved both automatically and further advanced and high level use 48 Hours
manually with engine start, speed in very demanding applications.
SHOCK
and clutch control all built in. The On board event, data logging BS EN 60068-2-27
monitoring and configuration of and trending makes it possible to Three shocks in each of three major axes
system variables allows the controller determine preventative maintenance 15gn in 11mS
to start and stop the engine, increase and improved performance criteria for DEGREES OF PROTECTION
and decrease engine speed as the machine. PROVIDED BY ENCLOSURES
the output demands and program BS EN 60529
IP65 - Front of module when installed into the
ramping for loading/unloading of the
control panel with the supplied sealing gasket.
engine.
DSENET® RS232 AND USB USB CONFIGURABLE DC OUTPUTS RATIO-METRIC EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS INPUTS STOP SUPPLY 8-35V
ETHERNET +
VOLT FREE PWM OUTPUTS FUEL & START CHARGE ELECTRONIC MAGNETIC
OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
D+
PWMi + W/L
2 4
ISSUE 2